Supported device types
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
Siemens SAPHIR is used to configure and monitor the controllers of Saphir and Climatix product lines produced by Siemens. Supported controllers: Saphir ACX32/ACX34 (via TCP/IP as well as via serial interface) and Climatix POL63x (specifically POL638 via TCP/IP).
Dialog window for station configuration - Protocol parameters.
They influence some optional parameters of the protocol. Following line protocol parameters can be entered:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Logging of detailed debug information about communication in the line log. | NO | ||
Type of used regulator. | ACX32 | ||
Maximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error. | 2 | ||
Timeout before resending a request if no response has been received. | s | 0,1 | |
The delay after sending the request and before reading the response. | s | 0,1 | |
The delay between the response readings. | s | 0,1 | |
The maximum number of retries of the response reading. | - | 20 |
Possible value types: Ai, Ao, Ci, Co, Di, Dout, TxtI, TxtO, TiA, TiR.
In Siemens Saphir, the I/O tag address is defined as a combination of "Base address", "Data block" and a particular element in a given data block.
"Base address" is a 32-bit number that uses hexadecimal format.
"Data block" is a type of data block located on a specified base address. The current implementation supports these data blocks:
Each data block is an N-tuple (different for every type of data block) of primitive data types. Supported primitive types:
-