This protocol supports data reading and writing to the devices "Transcon DAP 128TC data transfer system, the communication format D" and "Temar PRES-COM V2.00".
If only data reading from the central unit Transcon CU-16 or Temar PRES from the transmitter on the lines is used, the communication may be connected directly to the communication computer. In the case of full-duplex transmission, as communication concentrator KPX-02 is required. It is due to strict timing and synchronization of data that are sent to the central unit in synchronization of the received data. Its application firmware "DAP128 V1.00" executes correct synchronization of transmitted data, which are received from the master communication computer asynchronously, to the central unit. The central unit CU-16 is connected to port A of KPX-02 and the communication computer to the port C of KPX-02. Both ports are fitted with the DB9M connectors.
The physical communication lines of DAP 128TC can be equipped with so-called transmitters or receivers. Every physical line can be fitted with at the most 16 transmitters/receivers, the address 0 up to 15.
The system Transcon DAP 128TC in D communication format supports 16 physical lines. Temar PRES supports 8 physical lines.
The transmitter contains 7 inputs. Their values can be received by the D2000 system as I/O tags, value type Digital input (Di) or Analog input (Ai) or Cardinal input (Ci). The values Ai/Ci are 8-bit, serialized in eight cycles. Input No. 7 is an odd parity, which is used to check the transmission of input data on the inputs 0 to 6.
Each receiver/transmitter is configured as a single station. The communication line in D2000 is shared by all the lines of a particular Transcon CU-16 device (16 physical lines) or Temar (8 lines), i.e. it is determined by the RS232 interface of the device. The physical line number, to which the receiver/transmitter is connected, is configured in the station address.
Configuration dialog box - tab Protocol parameters.
The parameters of the line influence some optional parameters of the protocol. You can define the following parameters:
Table 1
Parameter | Meaning | Unit | Default value |
---|---|---|---|
Enables to choose a protocol mode. | DAP 128TC format D PRES-COM V2.00 | DAP 128TC format D | |
Activates the mode which enables only data reading from the transmitters. Data sending to the receivers is disabled. | YES/NO | NO | |
The delay between the line readings. | ms | 50 ms | |
Timeout for receiving valid data. If within this time no valid packet is received, the stations (transmitters) are switched to the status of a communication error. | sec | 10 sec | |
When using a redundant configuration of MOXA NPort serial/UDP converters on SerialOverUDP Device Redundant line, it defines a timeout to switch over between them if an error occurs on a converter that is currently active (being used for communication). | sec | 10 sec | |
Enables a display of debug info that contains the binary data. | YES/NO | YES | |
Shows debug info about the station status (transmitters) after it receives a valid packet (parity errors etc.). | YES/NO | NO |
Configuration dialog box - tab Protocol parameters
The parameters of the line influence some optional parameters of the protocol. You can define the following parameters of the station:
Table 2
Parameter | Unit | Default value | |
---|---|---|---|
Type of station - Transmitter or receiver. | Transmitter Receiver | Transmitter |
In case of a communication error, the value of the communication station switches immediately to the status of soft communication error COMM_ERR. If the error is repeated, the station switches to the status HARD_ERR (hard error) according to the setting of the "Time filter" parameter. As two cycles of reading per second are executed, the station can switch to the HARD_ERR status very quickly.
The error statuses are indicated by the attributes of the value of the communication station. These attributes of value are used:
I/O tag types: Di, Ai, Ci, Dout.
I/O tag address is the number of input/output on the module in the range of 0 to 6 (receiver) or 0 to 7 (transmitter). Input 7 has the value of an odd parity for the inputs 0 to 6 and can serve for checking the functionality of the transmitter. The status of transmitter parity is also signaled by the error attribute.
-