Supported device types and versions
Communication line configuration
Station configuration
I/O tag configuration
Document revisions
The protocol supports reading data from electrometers (active and reactive energies) that were collected by the ABB Microscada system and published via files.
The files are expected to have a name in a format coding both the date and the time Dyyyymmddhhmi.CSV, e.g. D201706301247.CSV.
The files are read with the time parameters (period, delay) configured on the station's Time parameters tab.
The protocol only supports data readout.
Dialog window station configuration - tab "Protocol parameters".
They influence some optional protocol parameters. The following station protocol parameters can be entered:
Parameter | Description | Unit | Default Value |
---|---|---|---|
Delay after processing of a file. The parameter can be useful if the communication has been offline for a longer time, i.e. a larger number of files are accumulated and their fast processing could flood the system. | s | 0 |
Supported value types of I/O tags: Ai.
I/O tag address is an integer 16-bit number (1-65535) specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
It defines an electrometer number, which is specified on every line of a data file.
This is an example of the first 15 rows of a specific file (I/O tag addresses would be 1-15):
E001;0 E002;6504 E003;0 E004;0 E006;3620 E007;1160 E008;196 E009;884 E010;152 E011;400 E012;140 E013;3588 E014;0 E015;0