ZMD405CT44 is an electricity meter from the international manufacturer Landis+Gyr. Under the front cover of the electricity meter, there is a shaft for connecting a plug-in module that complements the communication interfaces.

Figure 4 - ZMD405CT44 with and without covers

Figure 5 - ZMD405CT44 communication interfaces
On the Figure 5, the main elements on the terminal board of the electricity meter and its communication interfaces are marked:
The MAP120 utility software was supplied with the electricity meter, which can be used to configure the electricity meter settings, but not to read the values of common registers.
The tested electricity meter had a fixed IP address, and to communicate with it, it was practical to set up 2 IP addresses on one interface on our computer - one for Internet access and one for communication with the electricity meter. However, the MAP120 software could not use the IP interface with two IP addresses. Only one IP address had to be set on the interface. It was also not possible to set the parameters for communication via the optical head, and due to the RS485 master mode, this interface could not be used either.

Figure 6 - Sample from the Landis+Gyr MAP120 application
The MAP120 application contains detailed user documentation, accessible via the F1 key, in which individual configuration parameters of the electricity meter are described.
The electricity meter uses HDLC on the relational layer.