Since version D2000 v7.1.0, release A050525000, a new ASDU 252 has been implemented into the communication protocols IEC 870-5-104 and IEC 870-5-104 Server. The ASDU 252 allows data transfer between two D2000 Systems, one of them uses the protocol IEC 870-5-104 and the other one uses IEC 870-5-104 Server.
ASDU 252 should be used if you need to transfer:
Communication station parameters:
Keyword | Full name | Meaning | Unit | Default value |
---|---|---|---|---|
D2CLS | D2000 Copy Limit Status | The parameter is set on the station that is the parent of input I/O tags for which the partner station sends ASDU 252. Such I/O tag then ignores its defined limits and copies the ValueLimitStatus (basic object attribute) of its control object. If there are configured process alarms for input I/O tag, they will be evaluated according to the ValueLimitStatus copied from the control object. Note: The parameter D2VCO must be set on the partner station. | - | False |
D2CPA | D2000 Copy Process Alarms | The parameter is set on the station that is the parent of input I/O tags for which the partner station sends ASDU 252. Such I/O tag then ignores its configuration and copies process alarms of the control object of partner output I/O tag. Note: The parameter D2VCO must be set on the partner station. | - | False |
D2VCO | D2000 ASDU Value from Control Object | The parameter is set on the station that is the parent of output I/O tags with defined ASDU 252. If a control object is defined for such I/O tag, then the value of the control object is sent to communication as the output value (along with its basic object attributes - ValueType, ValueTime, ValueStatus, ValueLimitStatus, ValueProcAlarmStatus, ...). Warning: In this case, there are ignored all configuration of output I/O tag concerning process alarms, limits and value conversion ! Value of output I/O tag seems to be correct within D2000 system, but there is sent "raw" value of control object into communication. Note: To send "raw" value of control object, the value types of control object and output I/O tag must be the same, otherwise there is sent ordinary output value. | - | False |
Notes: