  • EiNr - electrometer number in EI structure (1..255). The total number of electrometers that the concentrator sends must be set in the "Number of EIs" protocol parameter.
  • EiInd - measurement index of electrometer within the EI structure (1..255). The total number of measurements for one electrometer that the concentrator sends must be set in the "Number of values in EI" protocol parameter.
  • EiParam - measurement parameter: AV|AV1|AV15|N|N1|N15|VN|1N|1V|2N|2V|3N|3V
    • AV - Instant value of the counter [kWh, kVArh]
    • AV1 - Instant value of the counter at the end of 1-minute interval
    • AV15 - Instant value of the counter at the end of 15-minute interval
    • N - Number of the last accumulation
    • N1 - Number of the last accumulation at the end of 1-minute interval
    • N15 - Number of the last accumulation at the end of 15-minute interval
    • VN - Value of the counter at the last accumulation [kWh, kVArh]
    • 1N - Number of the previous (1-st older) accumulation
    • 1V - Value of the counter at the previous (1st older) accumulation
    • 2N - Number of 2-nd older accumulation
    • 2V - Value of the counter at the 2-nd older accumulation
    • 3N - Number of 3-rd older accumulation
    • 3V - Value of the counter at the 3-rd older accumulation

...

  • EmNrelectrometer number in EM structure (1..255). The total number of electrometers that the concentrator sends must be set in the the "Number of EMs" protocol parameter.
  • EmParam - measurement parameter: CA|CA1|CA15|OV|PV|PV1|PV15|PPO
    • CA - Instant value of the counter (0..9_9999_9999)
    • CA1 - Instant value of the counter (0..9_9999_9999) at the end of 1-minute interval
    • CA15 - Instant value of the counter (0..9_9999_9999) at the end of 15-minute interval
    • OV - Instant power [kW, kVAr]
    • PV - Average power since the beginning of current 15-minute interval [kW, kVAr]
    • PV1Average power at the end of the 1-minute interval [kW, kVAr]
    • PV15Average power at the end of the 15-minute interval [kW, kVAr]
    • PPO - Electrometer's data validity (a 16-bit number specifying the number of seconds)

...

  • EwNr ordinal number of the counter (1..255) within a response. The total number of counters that the concentrator sends must be set in the the "Number of word counters" protocol parameter.

Examples of addresses:

...