Circutor CVMk MODBUS communication protocol

Supported device types and versions 
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Kotva
typy_verzie
typy_verzie
Supported device types and versions

...

MODBUS RTU MASTER supports data reading from the analyzers Circutor CVMk analyzers.

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

  • Communication line category: Serial.
  • Parameters of the asynchronous line depending on the design and type of device connection – see literature about Circutor.

...

  • Communication protocol: MODBUS Circutor CVMk.
  • Station The station address is a decimal number in the range of 0 up to 255 specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #1A).

...

There can be defined the following parameters:

Table 1

Key word
KeywordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry Count
Number of retry calls when
The number of request retries when an error in communication occurs.-2
Kotva
rt
rt
RT
Retry TimeoutDelay between
retry calls
request retries if an error in communication occurs.ms200 millisec.
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting
on
for the response after sending a
call
request.ms100 millisec.
Kotva
wt
wt
WT
Wait TimeoutDelay between the readings of a response until it is completed.ms100 millisec.
Kotva
mwr
mwr
MWR
Max Wait Retry
Number
The number of
retry
response reading retries until
it
the response is completed.-15

String with protocol parameters is written according to this rule:

Key_word=value;Key_word=value;...

Example:

RC=1;RT=500;

If a key word keyword with a valid value has not been found in the initial string, the default value is used according to Table 1.

Kotva
merany_bod
merany_bod
I/O tag configuration

...

I/O tags: Ai

Addressdecimal a number in the range of 0 to 65535 – number of MODBUS double register, . It can be specified as a decimal number or a hexadecimal number with a hash at the beginning (e.g. #0ABC).

The values are read by 2 registers and interpreted as a 4-byte integer. The addresses of values are described in the literature about Circutor.

...

Kotva
revizie
revizie
Document revisions

...

  • Ver. 1.0 – May 9, 2000 – the creation of the document