Supported device types and versions

...

Communication allows implements data reading from devices that support the M-Bus protocol by the Rev. 4.8 specification. Communication was tested against with MULTICAL® III, MULTICAL® 5 measuring devices by KARMSTRUP Company, CALSTREEM EEM-C measuring device by Danfoss Company, and PolluTherm Pt500 by Sensus.
The communication was also verified against the water flow meter Sensus MeiStream 150 with communication module HRI-Mei using EthMBus-5 converter manufactured by JC-e (it was necessary to configure a converter to TCP mode and use a TCP/IP-TCP line category).

...

...

The following station protocol parameters can be defined:

KeywordFull nameMeaningUnitDefault value
Kotva
chbr
chbr
CHBR
Change BaudrateValue Yes means that communication will be switched between modes 1 and 2 (only Serial line).
Value No means that communication will be performed using
the
mode 1 (300 Bauds).-No
Kotva
snkebr
snkebr
SNKEBR
Send SND_NKE as BroadcastThe Yes value means that the SND_NKE (slave device initialization) command is sent as Broadcast before reading from the first station on the line.
The No value means that the SND_NKE command is sent to each device individually before the start of the reading.
Note: if the parameter is set to Yes, after sending Broadcast, there is a delay configurable by parameter WAI.
-Yes

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: M-Bus Rev 4.8
  • Station The station address is a decimal number within the range of 1..250 – slave address, it is derived from the serial number of the measurement device (last three digits). If the last three digits are greater than 250, the highest digit is not to be taken into account. If the serial number is one of the numbers of 000, 300, 400, 500, 600, 700, 800, 900, then it must be changed.


Station protocol parameters

The following station protocol parameters can be defined:

KeywordFull nameMeaningUnitDefault value
Kotva
ascm
ascm
ASCM
Address Scan ModeEach reading of values increments the station address. This mode can be used to find a device with an unknown address.-No
Kotva
rc
rc
RC
Retry Count
Poll
Request repetition count in case of a communication error.-2
Kotva
rt
rt
RT
Retry TimeoutDelay between
poll
request repetition in case of a communication error.ms100 ms
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting for a response after sending the
poll
request.ms800 ms
Kotva
wt
wt
WT
Wait TimeoutDelay after transmitting the
poll
request before reading the response.ms500 ms
Kotva
mwr
mwr
MWR
Max Wait RetryRepetition count of response readings till its finalization.-40

Kotva
wai
wai
WAI
Wait After SND_NKE BroadcastDelay after sending a broadcast SND_NKE, before reading from the first station on a communication line.ms8000 ms
Kotva
wbr
wbr
WBR
Wait before REQ_UD2 RequestDelay before sending the REQ_UD2
poll
request to a slave.ms4000 ms
Kotva
sfai
sfai
SFAI
Set FCB Bit after SND_NKE
Parameter
The parameter specifies whether an FCB bit in a
poll
first request after sending SND_NKE
shoult
should be
ste
set to 1 (YES) or 0 (NO).-YES
Kotva
afor
afor
AFOR
Accept Following Records (0=disable,255=read all)If the slave station has Variable Data available, the parameter specifies the number of records read during one polling of the station. A value of 255 means that all available records will be read.-0
Kotva
resb
resb
RESB
Send Application Reset before REQ_UD2Optional sending of "application reset" message (50h) prior to reading the values from the station.-NO
Kotva
wul
wul
WUL
WakeUp LengthLength (given in characters) of the so-called wake-up message sent before each
poll
request. Value 0 disables the sending of the wake-up message.bytes0
Kotva
wud
wud
WUD
WakeUp Delay
Delay
The delay between the wake-up message and
poll
a request.ms400

Kotva
arb
arb
ARB

Accept Reply To Broadcast

If the station has address 254 (according to the protocol definition it is a broadcast address to which stations can respond), this parameter allows processing the response from any station. The practical use is on lines with a single station - in case of its exchange, it is not necessary to find out the address of a new device.

-YES

Kotva
fd
fd
FULL_DEBUG
Full DebugEnables debug logs on the communication and acquired data.-NO

Kotva
m3
m3
MULTICALIII
Multical IIIEnables decoding the Manufacture specific data of Multical III device.-NO

String A string containing the protocol parameters is being defined as follows:

Keyword=value;Keyword=value; ...

Example:

RC=1;RT=500;LBR=1;

If there is used a keyword with an invalid value in the initialization string , there will be used is used, a corresponding default value according to the table 1 will be used.

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible I/O tag types: Ai, Ci, TiA, TiR, TxtI

Two types of addresses can be configured:

  • Simple address: a number that is an index of the value in the M-Bus data packet. To get detailed information on unknown device devices, activate debug logs using the parameter the FULL_DEBUGDEBUG parameter.
    An example of debug log (individual rows correspond with addresses 1 to 9, value is displayed at the end of listing after the text "Val"):
    >> Adr.1,DF:0CH (8 digit BCD)(inst. val),VIF:05H=Energy 0*10^2 [Wh],VIFE:7DH=Multiplicative corr. factor 10^3,Val:0
    >> Adr.2,DF:0CH (8 digit BCD)(inst. val),VIF:15H=Volume 0*10^-1 [m3],Val:0
    >> Adr.3,DF:0CH (8 digit BCD)(inst. val),VIF:3DH=Volume Flow 0*10^-1 [m3/h],Val:0
    >> Adr.4,DF:0CH (8 digit BCD)(inst. val),VIF:2DH=Power 0*10^2 [W],Val:0
    >> Adr.5,DF:02H (16 bit int)(val during err),VIF:5AH=Flow temperature 0*10^-1 [C],Val:0
    >> Adr.6,DF:02H (16 bit int)(val during err),VIF:5EH=Return temperature 0*10^-1 [C],Val:0
    >> Adr.7,DF:03H (24 bit int)(val during err),VIF:60H=Temperature difference 0*10^-3 [K],Val:0
    >> Adr.8,DF:0CH (8 digit BCD)(inst. val),VIF:78H=Fabrication No.,Val:53155203
    >> Adr.9,DF:0CH (8 digit BCD)(inst. val),VIF:7DH=Extension of VIF-codes,VIFE:10H=Customer location,Val:53155203
    
  • Address of header objects:

    in format

    in 0.subadr format enables to address objects located in a header of an answer. A device can answer using

    a

    fixed or variable

    respond

    responses that have different header contents.

    Following

    The following table lists header objects and their addresses for

    fix

    fixed and variable respond.

    ObjectValue typeAddress in fix respondAddress in variable respond
    Identification No.Ci, TxtI0.00.0
    ManufacturerTxtI (3 characters)-0.1
    VersionCi-0.2
    MediumCi-0.3
    Access No.Ci0.10.4
    StatusCi0.20.5
    SignatureCi-0.6


    An example of a debug log for variable

    respond

    response:

    Variable data respond CI=0x72 mode 1 from St:'B.MBUS_SENSUS'(0) detected.
    >> Adr.0.0,Identification No.,Val=53155203
    >> Adr.0.1,Manufacturer,Val='SEN'
    >> Adr.0.2,Version,Val=12
    >> Adr.0.3,Medium,Val=4
    >> Adr.0.4,Access Nr.,Val=50
    >> Adr.0.5,Status,Val=16
    >> Adr.0.6,Signature,Val=0
       

...

Multical III device sends extended "manufacture specific data". Activating the parameter MULTICALIII allows to configure I/O tags according to the following table:

AddressValue descriptionType
12Access counterCi
13Number of customer 1Ci
14Number of customer  2Ci
15InfoCi
16TAR2Ci
17TL2Ci
18TAR3Ci
19TL3Ci
20AUX1Ai
21AUX2Ai
22Prog_NoCi
23ConfigCi
24DateTiA
25Date*TiA

Kotva
nastavenia
nastavenia
Parameters settings and data acquisition method

...

Recommended polling parameters are at least 1 minute. When the polling time comes, the before polling the first station on the line a , an SND_NKE(255) datagram is broadcasted, i.e. init for all measuring devices (Slaves) and the KOM process waits for a period specified by the WAI parameter WAI. The slaves prepare all current measured values and implicitly change their Baudrate to 300.

Then the communication speed can be optionally changed to a higher speed (specified on the communication line as mode 2) by SND_UD data , if it configured by the means of the line parameter Change Baudrate line parameter. Only baudrates baud rates 300/600/1200/2400/9600/19200/3840 are supported by M-Bus protocol.
Note: change of baudrate baud rate is supported only on a Serial lineon SerialMOXA IP Serial Library, and RFC2217 Client line.

Then a REQ_UD2 poll request is sent to every slave , (after waiting according to the value specified by the WBR parameter WBR) to which they all should respond by the data datagram RSP_UD data datagram.

Times of individual values are not set to the time when the telegram was received, but to the time of the required polling period. So if the period is set to 1 hour, all the times of values are set to the given hour.


Note: Polling period, as well as station parameters, should be the same on all stations and one on a single line.

Kotva
literatura
literatura
Literature

...


Info
titleBlog

You can read a blog about M-Bus protocol: Communication – M-Bus


Kotva
zmeny_upravy
zmeny_upravy
Changes and modifications

...

  • Ver. 1.0 - June 26th, 2000 – document Document creation.
  • Ver. 1.1 – November 9th, 2000 – testing Testing Danfoss CALSTREEM.
  • Ver. 1.2 – December 14th, 2000 – Change of the outputs AUX1 and AUX2 from Ci to Ai
  • Ver. 1.3 - November 22nd, 2005 - Redesigned by M-Bus Rev. 4.8.
  • Ver. 1.4 - March 10th, 2021 - Added "Accept Reply To Broadcast" parameter


Info