MODBUS protocol, version RTU, supports data reading from a Valmet Damatic control system Valmet Damatic by means of gateway RTU GTW:LIS gateway.

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

  • Communication line category: Serial.
  • Parameters of the asynchronous line depending on the design and type of device connection – literature see the documentation "Overview of the Damatic XD System – VALMET Automation V.5.4 rev.7".

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: Valmet MODBUS RTU GTW:LIS.
  • Station The station address is a decimal number in the range of 0 to 255.

...

There can be defined the following parameters:

Table 1

Key word
KeywordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry Count
Number of retry calls when
The number of request retries when an error in communication occurs.-2
Kotva
rt
rt
RT
Retry Timeout
Delay between retry calls
The delay between request retries if an error in communication occurs.ms300 millisec.
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting
on the
for a response after sending a
call
request.ms200 millisec.
Kotva
wt
wt
WT
Wait TimeoutDelay between the readings of a response until it is completed.ms100 millisec.
Kotva
mwr
mwr
MWR
Max Wait Retry
Number
The number of
retry
reading the response
reading
until it is completed.-10

String with protocol parameters is written according to this rule:

Key_word=value;Key_word=value; ...

Example:

RC=1;RT=500;

If a key word keyword with a valid value has not been found in the initial string, the default value is used according to Table 1.

Kotva
merany_bod
merany_bod
I/O tag configuration

...

I/O tags: Ai, Di

Address – a decimal number in the range of 0 to 65535 – number of MODBUS register.

In general, 2 bytes are read (sign signed integer) from a particular register. For Ai points, IEE 754 standard can be used, which is means a reading of 4 bytes in format FLOAT, i.e. the registers on with addresses Address and Address+1.

For Di points, the bit number of bit must be from the specified, withing range of 0 to 15 – it represents one bit from a 16 bits from -bit MODBUS register which was read.

...

  • Ver. 1.0 – February 9, 2000

Info
titleRelated pages: