  • Communication line category: Serial, SerialOverUDP Device Redundant, TCP/IP-UDP.
  • Parameters of the serial line:
    • Baud rate - 1200 Baud
    • No parity, 8 data bits, 1 stop bit
  • Parameters of UDP line:
    • Host: IP address of the controller
    • Port: UDP port of the controller where requests are sendsent.
    Note: The parameters of the backup server (Host and Port) are not used in this protocol.

...

  • Communication protocol: Remia E3.
  • Station The station address is set according to the address on a device (0 to 15) specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #6A).

...

Station protocol parameters

Configuration dialog The configuration dialog box of station - the tab "Protocol parameters".

Table 1

Key wordKeywordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry CountNumber of retry calls when an error in communication occursMaximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.-2
Kotva
rt
rt
RT
Retry TimeoutDelay between the retry calls if an error in communication occursTimeout before resending a request if no response has been received.ms100 millisec.ms
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting on the response after sending a callThe delay after sending the request and before reading the response.ms100 millisec.ms
Kotva
wt
wt
WT
Wait TimeoutDelay The delay between the response readings of a response until it is completed.ms300 millisec.ms
Kotva
mwr
mwr
MWR
Max Wait RetryNumber of retry The maximum number of retries of the response reading until it is completed.-10

Kotva
merany_bod
merany_bod
I/O tag configuration

...

The address is a number in the range from 0 to 300 (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A).
The meaning of the addresses is stated in the Table 2:

Table 2

Value typeAddressDescriptionRead/Write
Ai
Ai0Instantaneous power.R
Ai1Average power.R
Ai2Peak VT.R
Ai3Peak NT.R
Ai4Measurement 1 (main) - the last 1/4 hour (see Note).R
Ai5Measurement 2 (secondary) - the last 1/4 hour (see Note).R
Ci
Ci0Number The number of electrometers.R
Ci1Number The number of regulatory degrees.R
Ci2Number The number of appliances.R
Ci3Regulatory degree.R
Ci4Tariff (0=VT, 1=NT).R
Ci5Current regulatory degree.R
Ci6Current average power (%).R
Co
Co0Regulated power VT.R/W
Co1Regulated power NT.R/W
Di
Di0 až 7Type of electro meter (FALSE=active power [kW], TRUE=reactive power [kVAr]).R
Di100 až 164Appliances (FALSE=idle state, TRUE=control state).R
Di200 až 264Status signal (FALSE=inactive, TRUE=active).R
TiR
TiR0Time The time within a 15-minute interval.R
TiA
TiA0Date and time of initialization.R
TiA1Date and time of power failure.R
TiA2Date and time of the configuration change.R
TiA3Date and time of the last reset.R
TiA4Current date and time.R
TiA5Time to reach peak VT.R
TiA6Time to reach peak NT.R
TiA7Time of the last quarter-hour.R

Kotva
poznamka
poznamka
Note: You can obtain also the values from an archive of the device per for the current and previous month for both the main and secondary measurement. The reading of archive values may be started in the station dialog box or by Tell the GETOLDVAL Tell command GETOLDVAL.