  • accumulated work for 3 tariffs
  • instantaneous power
  • quarter-hour power take-offconsumption, including the archival data

...

  • Communication protocol: Incos/VUVT PMEL 04.
  • A station address is a decimal number (or a hexadecimal number with a hash at the beginning, e.g. #0A) - according to the settings of PMEL configuration jumpers.
  • A time Time synchronization of the station is required.


Station protocol parameters

Communication station - configuration dialog box - tab "Protocol parameters".
They could influence some optional protocol parameters. You can set the following parameters:

Table 1

Key wordKeywordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry CountNumber The number of call request retries when an error in communication occurs.-2
Kotva
rt
rt
RT
Retry TimeoutDelay The delay between the retry call when an error in communication occurs.ms1000
Kotva
wft
wft
WFT
Wait First TimeoutThe first timeout for response reading after sending the message.ms500
Kotva
wt
wt
WT
Wait TimeoutTimeout between the response readings until it is completed.ms500
Kotva
mwr
mwr
MWR
Max Wait RetryNumber The number of retries of response reading until it is completed.-8
Kotva
sa
sa
SADDR
Source AddressCommunication address of the source (PCD2000 KOM).0 up to 254126
Kotva
04b
04b
PMEL04B
PMEL04BCommunication with PMEL04B device.YES/NONO
Kotva
ts
ts
TIMEST
TimestampThere is used PMEL04B with the support of time stamp timestamp transmission is used.YES/NONO
Kotva
tsy
tsy
TMSYNC
Allow Automatic Time SynchroReal-time will be synchronized after the bit EM_TIM bit is set by a device (PMEL04B only PMEL04B).YES/NOYES

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Table 2: I/O tag addresses distribution:

Electro meterElectrometerInstantaneous power (Ai)Accumulation work tariff 1 (Ai)Accumulation work tariff 2 (Ai)Accumulation work tariff 3 (Ai)Quarter-hour power take-off (Ai)Time difference between curr. and prev.  state (TiR)
1016171864200
2119202165201
3222232466202
4325262767203
5428293068204
6531323369205
7634353670206
8737383971207
9840414272208
10943444573209
111046474874210
121149505175211
131252535476212
141355565777213
151458596078214
161561626379215


Table 3: Di values, status bits (PMEL04A only

...

):

AddressMeaning
0EPROM error.
1RAM error.
5Program restart on a process module.
6Exceeding the time difference.
7Acknowledgement Acknowledgment of time settings.

Di values, digital inputs (only PMEL04B), addresses 0 up to 15.

...