Key wordFull nameMeaningUnitDefault value

Kotva
wt
wt
WT

Wait TimeoutTimeout to receive a response or one of its fragments.s.ms1.5 s

Kotva
fa
fa
FA

Fragmented answer is expectedThe response may consist of several UDP packets (fragments).-False

Kotva
adoi
adoi
ADOI

Actual Data Object ID

The address of the object (16-bit number) that contains information about the instant values (analogs). A value of 0 disables reading of the instant values as well as their 1 and 15-minute archives.

-8

Kotva
a15oi
a15oi
A15OI

15min Archive Data Object ID

The address of the object (a 16-bit number) that contains information about 15-minute values. A value of 0 disables reading of 15-minute values.

-5

Kotva
a1oi
a1oi
A1OI

1min Archive Data Object IDThe address of the object (a 16-bit number) that contains information about 1-minute values. A value of 0 disables reading of 1-minute values.-9

Kotva
abii
abii
ABII

Binary data Object ID

The address of the object (a 16-bit number) that contains information about binary values. A value of 0 disables reading of binary values.

-0

Kotva
gadoi
gadoi
GADOI

Generic Actual Data Object ID

The address of the object (16-bit number) that contains information about the generic instant values (addresses of I/O tags of GA type). A value of 0 disables reading of generic instant values.

-0

Kotva
geoi
geoi
GEOI

Generic Event Object ID

The address of the object (16-bit number) that contains event information from the event log of RemiaKME. A value of 0 disables work with the event archivelog.
A specific event is read from the archive by writing to the I/O tag with RECNR address.

-0

Kotva
emnr
emnr
EMNR

Number of EMs

The number of electrometers (1-255) whose instant data from impulse measurement (instant counter value, instant power, average power since the start of the current time interval, validity of the meter's data) are in response to reading the Actual Data Object ID, and whose historical data 1 and The 15-minute minutes (end-of-period counter value,, average power per period) are in response to reading 1min Archive Data Object ID and 15min Archive Data Object ID.

-41

Kotva
einr
einr
EINR

Number of EIs

The number of meters (1-255) whose instant data from IEC communication (instant counter value, numbers of last 3 accumulations, counter values for the last 3 accumulations) are in response to reading the Actual Data Object ID, and historical data (last accumulation number, counter value for the last accumulation) are in response to reading 1min Archive Data Object ID and 15min Archive Data Object ID objects.

-6

Kotva
eivr
eivr
EIVR

Number of values in EI

The number of measurements (1-255) in the EI section (data from IEC communication) in response to reading the Actual Data Object ID1min Archive Data Object ID15min Archive Data Object ID objects.

-16

Kotva
wcnr
wcnr
WCNR

Number of word counters

The number of 16-bit counters (0-255) whose values are in response to reading the Actual Data Object ID object.

-0

Kotva
pbd
pbd
PBD

Debug Packet Binary Contents

Activates advanced debugging with listing of binary data being sent and received.


YES/NOYES

Kotva
full_debug
full_debug
FULL_DEBUG

Debug Values

Activates advanced debugging with listing of I/O tag values.

YES/NONO

...