Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

Group
(highlighted can be configured for I/O tags)

Variations

Supported operationsNote
Binary Input (1)

Packed format (1)
With flags (2)

Reading (Read)Binary inputs
Binary Input Event (2)Without time (1)
With absolute time (2)
With relative time (3)
Analysis*Reporting of binary inputs' changes
Double-bit Binary Input (3)Packed format (1)
With flags (2)
Reading (Read)Double-bit binary inputs
Double-bit Binary Input Event (4)Without time (1)
With absolute time (2)
With relative time (3)
Analysis*Reporting of double-bit binary inputs' changes
Binary Output (10)Packed format (1)
Output status with flags (2)

Reading (Read)
Writing (Write, Select+Operate)

Binary outputs
Binary Output Event (11)Status w/o time (1)
Status with time (2)
Reading (Read)Reporting of binary outputs' changes
Binary Command (12)Control relay output block (CROB) (1)
Pattern control block (PCB) (2)
Pattern mask (3)
-Not supported yet
Binary Output Command Event (13)Command status without time (1)
Command status with time (2)
Analysis*Reporting of changes (results of third party commands)
Counter (20)32-bit with flag (1)
16-bit with flag (2)
32-bit with flag, delta (obsolete) (3)
16-bit with flag, delta (obsolete) (4)
32-bit w/o flag (5)
16-bit w/o flag (6)
32-bit w/o flag, delta (obsolete) (7)
16-bit w/o flag, delta (obsolete) (8)
Reading (Read)Counters
Frozen Counter (21)32-bit with flag (1)
16-bit with flag (2)
32-bit with flag, delta (obsolete) (3)
16-bit with flag, delta (obsolete) (4)
32-bit with flag and time (5)
16-bit with flag and time (6)
32-bit with flag and time, delta (obsolete) (7)
16-bit with flag and time, delta (obsolete) (8)
32-bit w/o flag (9)
16-bit w/o flag (10)
32-bit w/o flag, delta (obsolete) (11)
16-bit w/o flag, delta (obsolete) (12)
Reading (Read)Counters- values captured when the object was frozen
Counter Event (22)32-bit with flag (1)
16-bit with flag (2)
32-bit with flag, delta (obsolete) (3)
16-bit with flag, delta (obsolete) (4)
32-bit with flag and time (5)
16-bit with flag and time (6)
32-bit with flag and time, delta (obsolete) (7)
16-bit with flag and time, delta (obsolete) (8)
Analysis*Reporting of counters' changes
Frozen Counter Event (23)32-bit with flag (1)
16-bit with flag (2)
32-bit with flag, delta (obsolete) (3)
16-bit with flag, delta (obsolete) (4)
32-bit with flag and time (5)
16-bit with flag and time (6)
32-bit with flag and time, delta (obsolete) (7)
16-bit with flag and time, delta (obsolete) (8)
Analysis*Reporting of counters' changes when the object was frozen
Analog Input (30)32-bit with flag (1)
16-bit with flag (2)
32-bit w/o flag (3)
16-bit w/o flag (4)
Single-prec flt-pt with flag (5)
Double-prec flt-pt with flag (6)
Reading (Read)Analog inputs
Frozen Analog Input (31)32-bit with flag (1)
16-bit with flag (2)
32-bit with time-of-freeze (3)
16-bit with time-of-freeze (4)
32-bit w/o flag (5)
16-bit w/o flag (6)
Single-prec flt-pt with flag (7)
Double-prec flt-pt with flag (8)
Reading (Read)Analog inputs - values captured when the object was frozen
Analog Input Event (32)32-bit w/o time (1)
16-bit w/o time (2)
32-bit with time (3)e
16-bit with time (4)
Single-prec flt-pt w/o time (5)
Double-prec flt-pt w/o time (6)
Single-prec flt-pt with time (7)
Double-prec flt-pt with time (8)
Analysis*Reporting of analog inputs' changes
Frozen Analog Input Event (33)32-bit w/o time (1)
16-bit w/o time (2)
32-bit with time (3)
16-bit with time (4)
Single-prec flt-pt w/o time (5)
Double-prec flt-pt w/o time (6)
Single-prec flt-pt with time (7)
Double-prec flt-pt with time (8)
Analysis*

Reporting of analog inputs' changes when the object was frozen

Analog Input Reporting Deadband (34)16-bit (1)
32-bit (2)
Single-prec flt-pt (3)
Reading (Read)
Writing (all functions)
Deadbands of analog inputs
Analog Output Status (40)32-bit with flag (1)
16-bit with flag (2)
Single-prec flt-pt with flag (3)
Double-prec flt-pt with flag (4)
Reading (Read)Reading of analog outputs
Analog Output (41)32-bit (1)
16-bit (2)
Single-prec flt-pt (3)
Double-prec flt-pt (4)
Writing (Select+Operate,
Direct Operate,
Direct Operate No Response
,
but not Write)
Writing of analog outputs
Analog Output Event (42)32-bit w/o time (1)
16-bit w/o time (2)
32-bit with time (3)
16-bit with time (4)
Single-prec flt-pt w/o time (5)
Double-prec flt-pt w/o time (6)
Single-prec flt-pt with time (7)
Double-prec flt-pt with time (8)
Analysis*Reporting of analog outputs' changes
Analog Output Command Event (43)32-bit w/o time (1)
16-bit w/o time (2)
32-bit with time (3)
16-bit with time (4)
Single-prec flt-pt w/o time (5)
Double-prec flt-pt w/o time (6)
Single-prec flt-pt with time (7)
Double-prec flt-pt with time (8)
Analysis*

Reporting of analog outputs' changes
(results of third party commands)

Time and Date (50)Absolute time (1)
Absolute time and interval (2)
Absolute time at last recorded time (3)
Reading (Read)Current time
Time and Date CTO (51)Absolute time, synchronized (1)
Absolute time, unsynchronized (2)
Analysis*Common timestamp **
Class Objects (60)Class 0 data (1)
Class 1 data (2)
Class 2 data (3)
Class 3 data (4)
PollRequesting values for all objects of the respective class
Binary-Coded Decimal Integer (101)Small (1)
Medium (2)
Large (3)
Reading (Read)Reading of 1,2 and 4-byte signed BCD numbers
Unsigned Integer (102)8-bit (1)Reading (Read)Reading of 8-bit unsigned numbers
Octet String (110)Variations 0-255 correspond to octet strings of 0-255 bytes in lengthReading (Read)
Writing (Write)
Reading + writing of octet strings
Octet String Event (111)Variations 0-255 correspond to octet strings of 0-255 bytes in lengthAnalysis*Reporting of octet strings' changes
Virtual Terminal Output Block (112)Variations 0-255 correspond to strings of 0-255 bytes in lengthWriting (Write)Writing to a virtual terminal
Virtual Terminal Event Data (113)Variations 0-255 correspond to trings of 0-255 bytes in lengthReading (Read)Reading from a a virtual terminal

Kotva
poz*
poz*
* Note: Operation Analysis means that D2000 KOM can analyze the message and assign values to the appropriate I/O tag. For example, for a Binary Input Event (2) group, values are assigned to the I/O tags from the Binary Input (1) group.

Kotva
poz**
poz**
** Note: The outstation can send object values from the Time and Date CTO (51) group, defining the Common Time of Occurence (CTO) for subsequent events. Afterwards, values with relative time are sent - Binary Input Event (2) and Double-bit Binary Input Event (4), using With relative time (3) variations.

Note: D2000 KOM supports sending a message with the writing type outside the range allowed by the standard - e.g. for the Analog Output (41) group, a write operation with Write (2) function can be configured.

...

Kotva
tell_cmd
tell_cmd
Tell commands

...


CommandSyntaxMeaning
STWATCHSTWATCH StationNameTell command sends commands for reading of values of all configured I/O tag. This command sends Poll requests to all Classes according to the station parameter configuration and sends request for reading of all I/O tags with the Explicit Read parameter active.

Kotva
literatura
literatura
Literature

...