Supported device types and versions

...

The Protocol supports the communication with gas-volume conversion devices ELCOR-94 (made produced by ELGAS company ELGAS) directly or through the DATCOM concentrator (tested with DATCOM-K1 under test).

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: Elcor ELGAS Daniel.
  • Station address: value from 0 to 255. If the address is 0, the device must reply obligatorily.

...

A station configuration dialog - tab "Protocol parameters".
The protocols affected some of the protocol optional parameters. The following station protocol parameters can be entered:

Table No. 1

Key word
KeywordFull nameDescriptionMeasuring UnitDefault value
Kotva
rc
rc
RC
Retry CountPoll repetition count in case of a communication error.
 

3
Kotva
wft
wft
WFT
Wait First TimeoutFirst waiting for a response after sending the
poll
request.ms50 ms
Kotva
wt
wt
WT
Wait TimeoutDelay between response readings
till
until its finalization.ms50 ms
Kotva
mwr
mwr
MWR
Max. Wait RetryRepetition count of response readings
till
until its finalization.
 

60
Kotva
fd
fd
FULL_DEBUG
Full Debug
Communication monitoring
A high level of communication logging, received values of I/O tags are displayed.
 

NO
Kotva
srdtm
srdtm
SRDTM
Static Data Read TimeoutStatic values reading period (1-240 min). Static value is a configuration constant ELCOR-94, see table No. 2.min60 min
Kotva
hardp
hardp
HARDP
Hourly Archive Periodic ReadingA period for the reading
value
of the values of hourly archives (0-60 min). Value 0 disables the reading.min0 min

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible I/O tag types: Di, Ai, Ci, TxtI, Ao, Co.

The address of the I/O tag is entered in the form of text as follows:

...

         S - Static value - it is read with the timeout which is defined by value of station protocol parameter Static Data Read Timeout.
           Group - number of GROUP, only one obligatory direct parameter
                 B - BCD coded number
                    Type - value type: 'F'-Float[4], 'c'-Char[1], 'L'-Long[4], 'U'-Ulong[4], 'i'-Int[2], 'u'-Uint[2]
                          .Offset - position in packet, implicitly at the beginning (0)
                                  .Bit - bitsbit number 1..8


The following special addresses different from text can be entered , tooas a text:

NOStandardized volume, it is calculated internally according to the formula:  (G63 + G70 + (G37 * 1000000000)) * G30
OP
Momentary
The current pressure, it is calculated internally according to the formula: G61 * G29
OT
Momentary
The current temperature, it is calculated internally according to the formula:  G69 * G64
NPO
Momentary
The current standardized flow, it is calculated internally according to the formula:  (G60 * G27) + G28

A typical addresses configuration of device the ELCOR-94 device is mentioned shown in the table No. 2:

Table No. 2

Object descriptionValue typeAddressMeasurement units
Battery statusInteger inputS35L%
Relative densityAnalog inputS17
 

CO2 concentrationAnalog inputS15%
N2 concentrationAnalog inputS16%
Impulse constantAnalog inputS30
 

Alternate compressibilityAnalog inputS22
 

Pressure lower limitAnalog inputS25kPa
Pressure upper limitAnalog inputS26kPa
Alternate pressureAnalog inputS21kPa
Referential pressureAnalog inputS19kPa
Flowage lower limitAnalog inputS32m3/hour
Flowage upper limitAnalog inputS33m3/hour
Temperature lower limitAnalog inputS23°C
Temperature upper limitAnalog inputS24°C
Alternate temperatureAnalog inputS20°C
Referential temperatureAnalog inputS18°C
Device, FW versionText inputS46
 

Customer numberText inputS4
 

Serial No. ELCOR-94Text inputS3
 

Gas meter serial No.Text inputS2
 

Temperature sensor serial No.Text inputS0
 

Pressure sensor serial No.Text inputS1
 

Momentary pressureAnalog inputOPkPa
Momentary operating flowageAnalog input69m3/hour
Momentary standardized flowageAnalog inputNPONm3/hour
Momentary temperatureAnalog inputOT°C
Accumulated error - pressure sensor errorLogical input71c.4.7
 

Accumulated error - pressure above maximumLogical input71c.4.2
 

Accumulated error - pressure under minimumLogical input71c.4.1
 

Accumulated error - flowage above maximumLogical input71c.4.6
 

Accumulated error - temperature sensor errorLogical input71c.4.5
 

Accumulated error - temperature above maximumLogical input71c.4.4
 

Accumulated error - temperature under minimumLogical input71c.4.3
 

Error - pressure sensor errorLogical input71c.3.7
 

Error - pressure above maximumLogical input71c.3.2
 

Error - pressure under minimumLogical input71c.3.1
 

Error - flowage above maximumLogical input71c.3.6
 

Error - temperature sensor errorLogical input71c.3.5
 

Error - temperature above maximumLogical input71c.3.4
 

Error - temperature under minimumLogical input71c.3.3
 

Grade of compressibility KAnalog input52
 

Standardized volumeAnalog inputNONm3
Diagnostics resetInteger output57
 

Alternate standardized volumeAnalog input67UNm3
Alternate operating volumeAnalog input66Um3
Operating volumeAnalog input62Um3
Current time - dayInteger input39Bc.3
 

Current time - hourInteger input39Bc.4
 

Current time - minuteInteger input39Bc.5
 

Current time- monthInteger input39Bc.2
 

Current time - secondInteger input39Bc.6
 

Current time - yearInteger input39Bc.1
 

Conversion number ZAnalog input64
 

The protocol supports data archive reading from the ELCOR-94 readingdata archive. It is possible to obtain the hour hourly records of the following values:

  • Momentary The current temperature (I/O with "OT" address),
  • Momentary The current pressure (I/O with "OP" address),
  • Operating volume (I/O with group "62" address),
  • Standardized volume (I/O with "NO" address).

...