The protocol supports the communication withwith ELCOR-2 and microELCOR-2 devices (made by the ELGAS company ) that recalculate a gas quantity.

...

Full nameMeaningUnitDefault value
Anchor
devt
devt
Device Type
Selection of device type.ELCOR-2 or microELCOR-2ELCOR-2
Anchor
rc
rc
Retry Count
The delay between request retries in case of a communication failure.
3
Anchor
wft
wft
Wait First Timeout
Delay after sending the request before reading the response.ms100 ms
Anchor
wt
wt
Wait Timeout
Delay between response readings until it is completed.ms100 ms
Anchor
mwr
mwr
Max. Wait Retry
Retry count of response reading until it is completed.
30
Anchor
srdtm
srdtm
Static Data Read Period
Static - configuration data read period (microELCOR-2 only).min60 min
Anchor
hardp
hardp
Hourly Archive Periodic Reading
A period for the reading of hourly archives (0-60 min). Value 0 disables the reading.min0 min
Anchor
wusl
wusl
Wake Up Sequence Length
Length of 'wake-up' data sequence, which is sent before the request after a longer communication pause.0 .. 50 bytes25 bytes
Anchor
wueq
wueq
Wake Up Each Query
Insert 'wake-up' data sequence before each request.YES/NONO
Anchor
wuch
wuch
Wake Up Character
Form 'wake-up' data sequence from the specified characters.0 .. 255255
Anchor
ga
ga
Group Source Address
Group source address (address of the D2000 KOM process).0 .. 655350
Anchor
sa
sa
Source Address
Source address (address of the D2000 KOM process).0 .. 2550
Full DebugHigh A high level of communication tracking, the received values of I/O tags and other debug information is shown.YES/NONO

...

Possible value types of I/O tags: Di, Ai, Ci, TxtI, TiA.

Device The ELCOR-2 device

Table 2 contains the list of main parameters of the device.
Tables 3 to 8 contains the list of variable configuration and informative data according to the parameter type. DESC(ind) parameter represents the common data of all parameters. It describes the quantity. The current value of quantity can be acquired by the configuration of the I/O tag with numerical address - index ind (number from 1 and higher). To find out the technical units - configure text of I/O tag with address UNIT(ind).

...

Object descriptionValue typeAddressUnits
The serial number of the deviceCi, TxtISN
Referential temperatureAiTB°C
Referential pressureAiPBkPa
Firmware versionTxtIFW
Station nameTxtIDESC
CO2 concentrationAiTAB(0)%
N2 concentrationAiTAB(1)%
Heat of combustionAiTAB(2)MJ/m3
Relative densityAiTAB(3)
H2 concentrationAiTAB(4)%
H2S concentrationAiTAB(5)%
He concentrationAiTAB(6)%
H2O concentrationAiTAB(7)%
O2 concentrationAiTAB(8)%
Ar concentrationAiTAB(9)%
CO concentrationAiTAB(10)%
C1H4 concentrationAiTAB(11)%
C2H6 concentrationAiTAB(12)%
C3H8 concentrationAiTAB(13)%
iC4H10 concentrationAiTAB(14)%
nC4H10 concentrationAiTAB(15)%
iC5H2 concentrationAiTAB(16)%
nC5H2 concentrationAiTAB(17)%
C6H14 concentrationAiTAB(18)%
C7H16 concentrationAiTAB(19)%
C8H18 concentrationAiTAB(20)%
C9H20 concentrationAiTAB(21)%
C10H22 concentrationAiTAB(22)%

...

Object descriptionValue typeAddressUnits
Standard flow rate - primary flow numberCiCNT(ind)
Standard flow rate - calculation numberCiCLC(ind)
Standard flow rate - technical unitsTxtIUNIT(ind)
Standard flow rate - nameTxtIDESC(ind)

...



The microELCOR-2 device

As an address of the I/O tag, also the data from "Address" or "Alternate address" columns can be used.

...