ParameterMeaningUnitDefault value
Anchor
telnr
telnr
Modem Telephone Number
Phone number for connection via modem with this station (only lines of MODEM category).

Anchor
dialtm
dialtm
Dial Timeout
Maximal waiting time on connection via modem (only lines of MODEM category).sec60
Anchor
dialrc
dialrc
Dial Retry Count
Maximum number of attempt to connect via modem (only lines of MODEM category).1..201
Anchor
dialrt
dialrt
Dial Retry Timeout
Delay before attempting to dial after an unsuccessful connection attempt (only lines of MODEM category).sec30
Anchor
wft
wft
Wait First Timeout
Time delay between sending the request and reading the answer.
Note: a device sends a 3-character manufacturer's identification in the identification message. Standard defines that if the 3-rd character is a lower case letter, (e.g. in identifications ELm or UNi), minimum reaction time for such device is 20 ms instead of 200 ms. If the 3-rd character is an upper case letter, this does not preclude supporting a 20 ms reaction time.
ms200
Anchor
wt
wt
Wait Timeout
Time delay between reading the answer till it is completed. See the note of parameter Wait First Timeout.ms200
Anchor
mwr
mwr
Max Wait Retry
Retry count of reading response till its completion.1 .. 10020
Anchor
rt
rt
Retry Timeout
Delay between the request retry if the error communication occurs.ms1000 ms
Anchor
rc
rc
Retry Count
Retry count of request as far as the error communication.1 .. 203
Anchor
dt
dt
Disconnect Timeout
Timeout for waiting for answer to modem hangup operation (only lines of MODEM category).sec15
Anchor
ad
ad
Ack Delay
Delay after transmitting acknowledgement of received data (ACK).ms100
Anchor
brch
brch
Baudrate Changeover (Z)
Value of parameter 'Z' - Baud rate identification (for baud rate changeover) of request Acknowledgement/option select message of protocol C mode.

Option AUTO finds out automatic the value 'Z' from acknowledgement of answer and uses it.

300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud
115200 Baud
AUTO
2400 Baud
Anchor
lc
lc
Data Readout
Permission to read the current values ("data readout").YES/NOYES
Anchor
mnfs
mnfs
Manuf. Spec. Table Readout Nr.1 (Y)
Permission to read the "manufacturer specific table" values, 1-st block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Manuf. Spec. Table Readout Nr.2 (Y)Permission to read the "manufacturer specific table" values, 2-nd block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Manuf. Spec. Table Readout Nr.3 (Y)Permission to read the "manufacturer specific table" values, 3-rd block.
Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read.
-
6
7
8
9
-
Anchor
lp
lp
Load Profile
Permission to load the historical data from profile.YES/NOYES
Anchor
prof
prof
Profile
Profile name - OBIS code of load profile used during loading of historical data from profile.
P.01
Anchor
ptmas
ptmas
Profile Time Mask
Date and time mask used to read historical data from profile. Meaning of the "z" flag - see the description of the Session Recognition Flag parameter.
The letter " z" is used to set the time and is replaced by a value of 0, 1 or 2 according to the parameter the Session Recognition Flag parameter.

zyymmddhhmi
Anchor
tf
tf
Profile History Depth
Time depth of historical profile readings.hour24
Anchor
tr
tr
Time Round
Time round of data from profile.min15
Anchor
tlx
tlx
Profile Read Step
Time range of data which is queried from profile in one request. It is entered as a multiple of the parameter "Time Round".x Time Round2

Anchor
prl
prl
Profile Read Level

Access level used to read historical data from profile.0-95

Anchor
prm
prm
Profile Read Mode

Method of reading from profile:

  • VDEW read command (R5) : READ command will be used (the R5 default level can be changed by parameter Profile Read Level).
  • VDEW block read command (R6) : BLOCK READ command will be used (the default level should be changed to R6 by parameter Profile Read Level).
  • P1 + VDEW read command (R5) : first, a Level 1 password will be set (see the parameter Password - level 1) and then READ command will be used 
  • P1 + VDEW block read command (R6): first, a Level 1 password will be set (see the parameter Password - level 1)  and then BLOCK READ command will be used 

BLOCK READ divides the data into several blocks with the size of Profile Read Block Length rows. Block reading makes sense on lines with higher error rates.

-VDEW read command (R5)

Anchor
bl
bl
Profile Read Block Length

Block size (number of rows) if BLOCK READ from the profile is used - if Profile Read Mode is VDEW block read command (R6) or P1 + VDEW block read command (R6)row4

Anchor
prfe
prfe
Profile Read Formatted Execution

This parameter enables specifying a special sequence which may be required by some electrometers. So far the only known sequence is F101()
(The whole sequence sent to electrometers is <SOH>E2<STX>F101()<ETX><SOH> ).
-
Anchor
pass1
pass1
Password - level 1
Password necessary for changing configuration of device (level 1) used to set the date and time.
"00000000"
Anchor
srflag
srflag
Session Recognition Flag
Flag that indicates type of date/time used by the device. Electrometers LZQJ manufactured by EMH Elektrizitätszähler indicate type of date/time by this flag (0=Normal Time, 1=Summer Time, 2=UTC Time).
This flag is used by parameters Time Mask and Date Mask to set the time and by parameter Profile Time Mask to read historical data from profile.
Note: Both Normal Time and Summer Time values will cause the flag to be set depending on the time currently set or read.
Normal Time
Summer Time
UTC Time
Normal time
Anchor
treg
treg
Time Register
Register used to set the time.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.

0.9.1
Anchor
tmask
tmask
Time Mask
Mask used to set the time.
The letter " z" is used for time conversion according to the parameter Session Recognition Flag.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.
Note: some meters are disturbed by summer / winter time ("z") flag and require mask hhmiss

zhhmiss
Anchor
dreg
dreg
Date Register
Register used to set the date.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.

0.9.2
Anchor
dmask
dmask
Date Mask
Mask used to set the date.
The letter " z" is used for dátumu conversion according to the parameter Session Recognition Flag.
The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station.
Note: some meters are disturbed by summer / winter time ("z") flag and require mask ddmmyy or require a year-month-day order (zyymmdd or yymmdd)

zddmmyy

Anchor
tm
tm
Time Date Mode

Special settings used when setting the date and time. These may be required by some electricity meters.

  • Normal: no special settings
  • (00000000): this string is added after the written date / time.
    Example: if Date Mask is zddmmyy,  is zddmmyy, the date 31 Dec 2019 is written as (0311219)(00000000)
Normal
(00000000)
Normal

Anchor
atcmd1
atcmd1
AT Command 1

A special initial string of modem 1 (only for MODEM lines).
AT&FE0V1Q0B0X3L0M0
Anchor
atcmd2
atcmd2
AT Command 2
A special initial string of modem 2 (only for MODEM lines).

Explanation of recommended settings:

S37=5   1200bps DTE-DTE speed - limits the speed for modems. Many devices use modems with limited transfer speeds and this setting can speed-up the connection establishment process. Higher transfer speeds must be negotiated individualy.

&D2   DTR drop to hangup - for matching with tha parameter of modem line (line configuration, tab "Modem - parameters", check the option "Use DTR for Hangup").

S0=0   Disable auto-answer. Auto-answer will not be used.

S30=2   20 sec inactivity timeout - automatic hangup after idle timeout expired. Necessary for assuring connection termination after the communication with the last device is over.



ATS37=5&D2S0=0S7=60S30=2
Anchor
fd
fd
Full Debug
Full tracing of communication, loaded values of I/O tags and other debug information are shown.YES/NONO
Anchor
ud
ud
Unicontrols Devices
It activates data processing according to software implementation of protocol from Unicontrols.YES/NONO
Anchor
ur
ur
Unicontrols Read Index
Activates reading of profile index (map of records stored in memory) within reading of historical data from profile (Unicontrols device only). Retrieved index is not processed further and serves only as debugging information for Unicontrols.YES/NONO

...