Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

Kotva
subscription
subscription
Subscription: an object on the OPC UA server that is defined by the client. It returns the notifications about the change of of monitored items.


Kotva
inicializacia_komunikacie
inicializacia_komunikacie
Initiation of communication

...

Parameter nameMeaningUnitDefault value

Kotva
ct
ct
Client Type

Type of used client (driver for OPC UA communication):

  • Default - an original implementation of OPC UA client. Supports authentication (parameter Authentication Type) of Anonymous/Username types only. It does not support message encryption or signing.
  • Secure - a new implementation of OPC UA client with security support. Supports advanced authentication, encryption, and message signing capabilities.

Default

Secure

Default

Kotva
sn
sn
Session Name

Session text identifier. The Session identifier should be unique within the client instance, making it possible to search problems faster in the client or server logs.StringKom process
Kotva
cl
cl
Requested Channel Lifetime
The channel must be reopened before this time limit elapses. If the time is exceeded, the channel will be closed and unable to change data.hh:mm:ss01:00:00
Kotva
st
st
Requested Session Timeout
Any message should be changed between client and server before this time limit elapses. If it is not sent, the sources within the session that are kept on the server are released. The primary work of this parameter is to remove the sessions that became inactive because of some unexpected reason.mm:ss01:00
Kotva
at
at
Authentication Type
Type of authentication used with the OPC UA server. Supported types are:
  • Anonymous: logon is anonymous
  • Username: logon uses the user name and password
  • Certificate: logon uses x509 certificate (only for Client Type = Secure)
Anonymous / UsernameAnonymous
Kotva
tun
tun
Token User Name
If Authentication type = Username, then the user name used in the authentication.
If Authentication type = Certificate, then the path to the user certificate (e.g. D:\user_cert.der).


Kotva
pwd
pwd
Token Password
If Authentication type = Username, then the password used in the authentication.
If Authentication type = Certificate, then the path to the user private key (e.g. D:\user_private_key.pem).


Kotva
sp
sp
Security Policy

Security policy (only for Client Type = Secure; for Client TypeDefault a security policy None is used):

  • None - security policy None
  • Basic128Rsa15 - security policy Basic128Rsa15 (considered to be obsolete due to using a weak SHA-1 hashing algorithm)
  • Basic256 - security policy Basic256 (considered to be obsolete due to using a weak SHA-1 hashing algorithm)
  • Basic256Sha256 - security policy Basic256Sha256
  • Aes128Sha256RsaOaep - security policy Aes128Sha256RsaOaep
  • Aes256Sha256RsaPss - security policy Aes256Sha256RsaPss
None
Basic128Rsa15
Basic256
Basic256Sha256
Aes128Sha256RsaOaep
Aes256Sha256RsaPss
None

Kotva
sm
sm
SecurityMode

A mode of message security in OPC UA communication (only for Client Type = Secure; for Client TypeDefault a mode of message security None is used):

  • None - messages are not secured 
  • Sign - messages are signed (protected against modification, but not against eavesdropping)
  • Sign & Encrypt- messages are signed and encrypted (protected both against modification and eavesdropping)
None
Sign
Sign & Encrypt
None

Kotva
ppi
ppi
Preferred Policy Id

Identifier of preferred Security Policy (only for Client TypeDefault for password encryption). If the OPC UA offers several security policies, it is possible to select a specific one according to the identifier sent by the OPC server (the identifier can be found from in the logs). Examples of an identifier (text form is in parentheses):
PolicyId: 30 (0)
PolicyId: 31 (1)
PolicyId: 75 73 65 72 6E 61 6D 65 5F 62 61 73 69 63 31 32 38 52 73 61 31 35 (username_basic128Rsa15)
PolicyId: 75 73 65 72 6E 61 6D 65 5F 62 61 73 69 63 32 35 36 53 68 61 32 35 36 (username_basic256Sha256)
--

Kotva
rcd
rcd
Reconnect Delay

Waiting after the connection is broken before the connection is re-established.mm:ss.mss00:10.000

Kotva
ecd
ecd
Error Connect Delay

Waiting after an unsuccessful connection attempt.mm:ss.mss00:02.000

Kotva
ord
ord
Object Reinit Delay

Waiting after an unsuccessful attempt to create monitored items. If it is zero, the attempt is not repeated. If it is non-zero, the attempt is repeated after the defined wait.
Note: in the case of a specific OPC UA server (Simatic S-7), it could happen that after restarting the PLC the creation of monitored items failed, but after some time (after the complete initialization of the PLC?) the creation was already successful.

sec0

Kotva
dsf
dsf
Disconnect On ServiceFault

Terminating the connection after receiving a ServiceFault.YES/NONO

Kotva
dm
dm
Debug Mode

It changes the number of information about communication. We recommend enabling the Extended/Full modes only when detecting the problems and debugging the communication. The "Full + Trace (Secure only)" mode is valid only for Client Type = Secure.Normal/Extended/Full/
Full + Trace (Secure only)
Normal
Kotva
dt
dt
Debug Threads
The parameter defines the thread(s) that will send the debug info about the communication.Receiving/Sending/Others treads/All threadsAll threads

Note: all X509 certificates used in OPC UA communication can be found in the following subdirectories of the kom-opcua directory in the application directory:

  • own - a directory with the KOM process's own certificate (file file cert.der). If this file does not exist, it is generated
    Warning - this automatically generated certificate will only be valid for 1 year, so we recommend replacing it with a certificate valid for a longer period!
  • private - a directory with a private key for the KOM process own certificate (file private.pem)
  • rejected - a directory with rejected certificates
  • trusted - a directory with trusted certificates (the first time a connection is established to an OPC UA server, its certificate is stored in this directory)

...

The parameters on the level of the communication station correspond with the setting of one subscription. It means the that one communication station is equivalent to one instance of a subscription within the session.

...

Full nameDescriptionUnitDefault value
Kotva
subrpi
subrpi
Requested Publishing Interval

Defines the time interval for the server to send the information about the change of monitored items within the instance subscription by "Publish message".
Note: This parameter defines a proposed value that the OPC UA server can change, e.g. Bernecker-Rainer always returned a value of "Publishing Interval" at least 50 ms, although the requested interval was smaller.

mi:ss.mss00:05.000
Kotva
subrlc
subrlc
Requested LifeTime Count

If the client does not send the request for data till by the time defined by (LifeTime Count * Publishing Interval), the subscription expires. The value should be minimally 3 times higher than the "Requested Max KeepAlive Count".
Note: This parameter defines a proposed value that the OPC UA server can change, e.g. Bernecker-Rainer always returned as a value of "LifeTime Count" a maximum of 600, although the requested value was greater.

Number1000
Kotva
subrmkc
subrmkc
Requested Max KeepAlive Count

If the objects of the subscription are not changed, the server will send a keep-alive message after elapsing the time (Max Notifications Per Publish * Publishing Interval). The client will confirm this message when it sends a new request for data.
Note: This parameter defines a proposed value that the OPC UA server can change, e.g. Bernecker-Rainer has always returned as a value of "Max KeepAlive Count" a maximum of 200, although the requested value was greater.

Number5
Kotva
mnpp
mnpp
Max Notifications Per Publish
The parameter defines the maximum number of notifications about the object change, which the server can send in one "Publish message". Zero indicates that the number of notifications is unlimited.Number0
Kotva
pe
pe
Publishing Enabled
The parameter enables/disables the publishing within the subscription.YES/NOYES
Kotva
p
p
Priority
It defines a the relative priority of a subscription. If the server should send more notifications, the subscription with higher priority is preferred.0-2550

Kotva
mqs
mqs
Samples Queue Size

This parameter enables creating an object queue with the defined length on the OPC UA server's side for each monitored item in a subscription.Number0

Kotva
rt
rt
Read Timestamp

Timestamps used while reading a value:

  • None - timestamp received from OPC server is not used (value will be timestamped by the current time)
  • Source - SourceTimestamp is used
  • Server - ServerTimestamp is used (default)
  • Newer - newer timestamp is used (SourceTimestamp or ServerTimestamp)
-Server

Kotva
wt
wt
Write Timestamp

Timestamps used to write a value:

  • None - no timestamp is set
  • Source - SourceTimestamp is set (equal to the timestamp of written value)
  • Server - ServerTimestamp is set (equal to current time)
  • Both - both SourceTimestamp and ServerTimestamp are set

Note: If the OPC server does not support the writing of timestamps, according to the standard it should return the Bad_WriteNotSupported (2155020288) error code.

-None

Kotva
wsc
wsc
Write Status Code

StatusCode item will be used when writing.
Note: According to the standard, the OPC UA Wrapper returns the Bad_WriteNotSupported (2155020288) error code if the StatusCode entry is used when writing to the OPC DA Server version 2.05a.
YES/NOYES

Kotva
wwa
wwa
Write Whole Array

When an item of an array is written, the entire array is read first and then written. If this parameter is set to NO, only a specific array item is written,
Note: According to the standard, if the OPC server does not support writing a specific array item, it should return the Bad_WriteNotSupported (2155020288) error code.
Note: If this parameter is active, the "Write only" parameter must not be set at the I/O tag which addresses an item of the array.
YES/NONO

Kotva
aot
aot
Accept Older Time

Values that are not older than the specified time interval (compared to the timestamp of the current value of the I/O tag) will be accepted. After writing, it may happen that the value read back is older (usually by several ms) compared to the time of writing unless the communication computer and the OPC UA server have exact time synchronization. Error messages may appear in the line log:
Ignoring value for I/O tag <name>, current timestamp=<current_time> is newer than received <old_time>
Increasing the value of the Accept Older Time parameter will cause such older values to be processed and the error message to be suppressed.

hh:mi:ss00:00:00

Kotva
rm
rm
Read Mode

A way of reading values:

  • Subscribe: communication via subscriptions and notifications (standard)
  • Subscribe + Read: like Subscribe, in addition, periodic Read requests are sent (according to the time parameters of the station)
  • Read: send Read requests only

Note: The Subscribe+Read and Read modes should only be used if there is a problem with standard communication, as they are less efficient and have a higher overhead.

Subscribe
Subscribe+Read
Read
Subscribe

Kotva
nf
nf
No Filter

Ignoring filter parameters in the I/O tag configuration (Sampling type, DeadBand type, Trigger type).
In the this specific case, the OPC UA server did not work correctly if if monitored items with the specified filter parameters were inserted into the subscription.

YES/NONO

Kotva
mpp
mpp
Max Pending Publish Requests

The maximum number of consecutive unconfirmed Publish requests  (to which the OPC UA server does not reply with a Publish Message), after which the connection will be closed. A value of 0 causes the connection to not be closed.
Note: This parameter can be used to speed up the detection of a broken connection to the OPC UA server.
-0

...

NameMeaningUnitDefault value
IDThe identifier in text format, which is, in dependence depending on the ID type, converted to the required native type.
Note: if an identifier %IGNORE is specified for ID type=String, the I/O tag is ignored.
String
ID typeEnumerated types of identifiers. They help to access the objects in the OPC UA address space.
Numeric-1B ID: Identifier limited to 1-byte value (0-255)
Numeric-2B ID: Identifier limited to 2-byte value (0-65535)
Numeric-4B ID: 4-byte identifier
String: Text identifier
Guid -16B ID: 16-byte (128-bit) number that is usually divided into four parts. For example 3F2504E0-4F89-11D3-9A0C-0305E82C3301.
ByteString: Identifier that is represented as a sequence of bytes.
Numeric-1B ID / Numeric-2B ID/ Numeric-4B ID/String/Guid -16B ID/ByteStringUndefined
Namespace
Kotva
namespace_index
namespace_index
Numerical identifier of the namespace of the OPC UA server. Each OPC UA server can have N namespaces. However, the object identifier must be unique in one namespace.Numeric
Variable typeThe value type of objects that can be processed by the OPC UA client. Variable type should be used only if the I/O tag is intended for writing. As regards the reading of the object value, the information about type is sent together with the value.Undefined / Boolean / Byte / SByte / Integer16 / Unsigned16 / Integer32 / Unsigned32 / Integer64 / Unsigned64 / Float / Double / String / UTC Time / Boolean array / Byte array / SByte array / Integer16 array / Unsigned16 array / Integer32 array / Unsigned32 array / Integer64 array / Unsigned64 array / Float array / Double array / String array / UTC Time array / LocalizedText / LocalizedText arrayUndefined
Array indexIf the object value is represented as a value array (Boolean array / Byte array / SByte array / Integer16 array / Unsigned16 array / Integer32 array / Unsigned32 array / Integer64 array / Unsigned64 array / Float array / Double array / String array / UTC Time array), the parameter defines its range or value of a particular item.  The The first element of an array is identified by index 0.
A text representation of an array index may be in several formats:
  • Separate integer, e.g. "6" or "0":- when you want to obtain a single value from the array.
  • Two integers separated by a colon, e.g. "6:7", - if you want to obtain the range of values.
  • The expression separated by a comma in the case of a multidimensional array, e.g. "6,7" - when you want to obtain the particular value of the item of a 2D array. If you want to define a range, you should use expressions separated by a comma, e.g. "6:8,7:10".

Note: Writing is only supported for I/O tags with a specific index, not for ranges.

String
Write onlyIt controls if the I/O tag is a part of the subscription. Its value will be sent periodically from the server in the "Publish message".Unchecked/checkedUnchecked
Expanded Node IDIf it is checked, it enables addressing the ExpandedNodeId. Unlike the classic identifier in the OPC UA address space, ExpandedNodeId is supplemented by NameSpace URI and Server index.
Note: ExpandedNodeId is not yet supported in the KOM process.
Unchecked/checkedUnchecked
NamespaceUriText identifier of the namespace of the OPC UA server that is used instead of the numerical representation of a namespace.String
ServerIndexA numerical identifier that addresses the server number when using the  ExpandedNodeID identifier.Numeric0

...

NameMeaningUnitDefault value
Sampling typeThe parameter defines the sampling frequency of the monitored objects. When using the "Publishing rate", the frequency is equivalent to time the Requested Publishing Interval, which is set on the communication station level.
"Practical fastest rate" sets the sampling frequency on the maximum value.
"Custom rate" enables to specify the specification of a custom sampling interval, which may be defined in "Sampling Time".
Publishing rate/Practical fastest rate/Custom ratePublishing rate
Sampling timeThe parameter allows you to set the custom sampling frequency if "Sampling type" is "Custom rate".ss.ms0.0
DeadBand typeDeadband is a band in which the change of value does not cause a Data Change Notification, which is the part of Publish Message. When using "None", this band is ignored. Otherwise, there is used the relative or absolute value ("Percent"/"Absolute") from the "DeadBand value".None/Absolute/PercentNone
DeadBand valueThe parameter defines the custom value of a deadband if you chose the relative/absolute value ("Percent"/"Absolute").
0.0
Trigger typeThe parameter specifies the condition which that causes Data Change Notification. When using "Status", only the status change is reported. Change of value and timestamp are ignored. When using "Status,Value", the change of timestamp is ignored. "Status,Value,Timestamp" ensures the reporting in all options, i.e. when changing the status, value, or timestamp.
Note: a specific Simatic S7-1500 did not send value changes if this parameter was set to default "Status, Value, Timestamp" - changing it to "Status, Value" helped.
Status/Status,Value/Status,Value,TimestampStatus,Value,Timestamp

...

Note: In versions from 17th December 2018 and newer, the recycling of browser dialog has been implemented. If the dialog is closed by the Close button or after selecting a tag, it is actually only hidden and it is available for browsing by another I/O tag within the same station so that the tree structure of the browsed objects is preserved. Clicking on the close icon at the top right corner will cause the dialog to be really closed.

Image RemovedImage Added

The "Copy tags" button or a keyboard shortcut shortcut Ctrl+C copies the names of tags in a selected branch into the Windows clipboard. All tags will be copied unless a specific tag is selected.

The "Copy tree" button or a keyboard shortcut shortcut Ctrl+Shift+C copies the names of tags and their addresses in all browsed branches into the Windows clipboard.

Checking the "Structured tagsShow all types" option causes that in addition to objects (nodes of Object type), all other types of nodes (nodes of type Unspecified, Method, ObjectType, VariableType, ReferenceType, DataType, View) are displayed in the tree structure, with the exception of tags (nodes of type Variable). To display tags, see the next option.

Checking the "Structured tags" option causes the variables - tags (nodes of Variable type) to the variables (tags) to appear in the tree structure in addition to the objects (nodes of Object type), and the KOM process also attempts to read their descendants. This is useful for browsing OPC UA servers that support structured tags. You can also insert a tag into the address the address dialog window of the I/O tag by tag by double-clicking the tag name in the tree structure.

Image RemovedImage Added

Kotva
tell_cmd
tell_cmd
Tell commands

...

  • Ver. 1.0 – May 10, 2012
  • Ver. 1.1 - December 17, 2018: Added browser dialog recycling and browsing of structured tags
  • Ver. 1.2 - April 4, 2024: Added support for browsing all tag types


Info
titleRelated pages:

Communication protocols

...