The protocol supports communication with ESC 8800 dataloggers.
...
Measurement type | I/O tag type | Communication function | Documentation |
---|---|---|---|
Current values | AI | PRINT MINUTE | Command Response String 6 – 16, 17 |
Current values flags | DI | PRINT MINUTE | Command Response String 6 – 16, 17 |
1m averages | AI | PRINT MINUTE | Command Response String 6 – 16, 17 |
1m average flags | DI | PRINT MINUTE | Command Response String 6 – 16, 17 |
30m averages | AI | PRINT AUX | Command Response String 6 – 14, 15 |
30m average flags | DI | PRINT AUX | Command Response String 6 – 14, 15 |
60m averages | AI | PRINT HOUR | Command Response String 6 – 7, 8 |
60m average flags | DI | PRINT HOUR | Command Response String 6 – 7, 8 |
Digital inputs | DI | SENSE IN | Command Response String 6 – 9, 10 |
Calibrations | AI | PRINT CAL | Command Response String 6 – 12, 13 |
Real-time – writing | TOA | SET TIME | Command Response String 6 – 20 |
Kotva | ||||
---|---|---|---|---|
|
...
- Communication line category: Serial
- Baud rate according to the ESC datalogger settings - the command CENTRAL SPEED,
- 1 stop bit,
- 8 data bits,
- No parity,
- No handshaking.
Kotva | ||||
---|---|---|---|---|
|
...
- Communication protocol: ESC 8800.
- The station address is a number within the range of 0..255 specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A). The station address must be identical to the datalogger settings - the SET ID command.
...
- Current values: the delay at least 1 second, station priority 0. Current measurements of channels and digital inputs are configured at this station. This is a logical station with the lowest priority, the delay parameter may not be less than 1 second.
Note: Datalogger 8800 does not provide any current data - the data are acquired from one-minute averages. Therefore it is not necessary to create the station. - 1m averages - the period 1 minute, the offset 5..10 seconds, station priority 1. One-minute averages of channel measurements are configured at this station. This is a logical station with a higher priority, the parameter offset shouldn't be less than 5 seconds - this is the time provided for the datalogger for processing values.
- 30m averages - the period 30 minute, the offset 5..10 seconds, station priority 2. Thirty-minute averages of channel measurements are configured on this station. This is a logical station with even higher priority, the parameter offset shouldn't be less than 5 seconds - this is the time provided for the datalogger for processing values. Setting the period to 30 minutes must be initialized in the datalogger by using the command "SET INT 30".
- Calibrations – station with a required period for reading calibration results.
Station protocol parameters
The following station protocol parameters can be defined:
...
If a keyword with an invalid value is used in the initialization string, the corresponding default value according to the table 2 will be used.
Kotva | ||||
---|---|---|---|---|
|
...
Support of communication with ESC 8800 comprises acquisition and setting of the following values:
- reading of current values of measured parameters with flags,
- reading of 1m, 30m, and 60m averages with their respective flags,
- reading of current states of digital inputs,
- reading of calibration results.
- setting the real-time.
Current value configuration
I/O tag type is Ai, measurement type is ACTUAL. The channel number is defined as a number within the range of 0..99 either specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
Configuration of current value flags
Current values flags are DI type (Digital Input). The measurement type is ACTUAL Flag.
Note: The No missing data <blank> flag can be configured using the character _ (underline) for clarity.
Configuration of 1m, 30m, and 60m averages
The averages are values of AI type (Analog Input). Measurement type is 1m AV for one-minute averages, 30m AV for half-hour averages, and 60m AV for hour averages. Channel number is defined as a number within the range of 0..99 either specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
Flag configuration of 30m and 60m averages
Flags of averages are values of DI type (Digital Input). The measurement type is 30mAV FLAG for half-hour averages and 60mAV FLAG for hour-averages.
Note: The No missing data <blank> flag can be configured using the character _ (underline) for clarity.
Digital input configuration
Digital inputs are values of DI type (Digital Input). The measurement type is Dig.Input. The number of Digital input is defined as a decimal number within the range of 0..999.
Configuration of calibration results
Calibration results are values of AI type (Analog Input). The measurement type is CAL-Ph1 for the first calibration phase or CAL-Ph2 for the second calibration phase. Channel number is defined as a number within the range of 0..99 either specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
Real-time I/O tag configuration
For each station (for each physical ESC8800 logger), one I/O tag of TOA type containing real-time can be configured. The I/O tag is necessary for real-time synchronization - datalogger -> computer.
Acquisition of archived (stored) values
The ESC 8800 datalogger performs local archiving of measured values. The values can be requested automatically when a dispatcher system breakdown is detected or directly by the dispatcher (D2000 HI, D2000 EventHandler) to complete the D2000 dispatcher system archive.
The method described above allows acquiring calibration values, which are at most 30 days old, 30m averages for the last 31 days, and 1m averages for the last 60 minutes.