Device typeDevice codeData type
Special relaySMbit
Special registerSDword
InputXbit
OutputYbit
Internal relayMbit
Latch relayLbit
AnnunciatorFbit
Edge relayVbit
Link relayBbit
Data registerDword
Link registerWword
Timer ContactTSbit
Timer CoilTCbit
Timer Current valueTNword
Retentive Timer ContactSTSbit
Retentive Timer CoilSTCbit
Retentive Timer Current valueSTNword
Counter ContactCSbit
Counter CoilCCbit
Counter Current valueCNword
Link special relaySBbit
Link special registerSWbitword
Direct access inputDXbit
Direct access outputDYbit
Index register

Z

word
File register

R

word

...

For a specific type of device (device code), individual objects are identified by a number (device number). When using 3E and 4E frames, a 3-byte number is specified, when using a 1E frame, a 4-byte number is specified. Numbering starts from 0, the maximum number for a specific device type depends on the specific PLC.
Note 1: if the number starts with a hash sign (#), it is understood as hexadecimal, e.g. #A3 is 163 in decimal.
Note 2: if the number starts with "o", it is understood as octal, e.g. o17 is 15 in decimal. For several types of Mitsubishi PLCs, the octal system is used to number Inputs (X) and Outputs (Y).


Kotva
bit
bit
 Bit

Optional parameter - access to a specific bit. For device types (device code) that have word data, a specific bit (0-15) can be specified.
Note: writing is not yet implemented for the  I/O tag with a specified bit, only reading.

...

  • X10 - Input 10, interpreted as a BIT (default)
  • D0 - Data register 0, interpreted as a WORD (default)
  • M12, WORD - Internal relays 12-27, interpreted as a WORD
  • M#12, WORD - Internal relays 18-33 (0x12=18), interpreted as a WORD
  • D4, REAL - Data registers 4 and 5, interpreted as REAL
  • Y10, BIT, 20 - Inputs 10-29, interpreted as BIT (default), assigned to 20 items of the Destination column
  • D4, REAL, 10 -  Data Data registers 4-23, each couple interpreted as REAL,  assigned assigned to 10 items of the the Destination column
  • D4, WORD, 10 - Data register 4-13, interpreted as WORD, assigned to 10 items of the Destination column
  • R1000, , 3 - File registers 1000-1003, interpreted as WORD (default), assigned to 3 items of the Destination column