| Blok kódu | ||||
|---|---|---|---|---|
| ||||
; command Clearing Rotation Counters ; sent request (data part is bold, header/footer are normal) and received response:and received response (header is first 4 bytes, footer is last 2 bytes) ;L:L.Sensus_Mei REQ-<68><08><08><68><73><00><51><0F><02><1F><20><7A><8E><16> ;L:L.Sensus_Mei RSP-<E5> TEXT _stAdr = %Chr(%StrToI("16#00#")) ; station address TEXT _val _val := %Chr(%StrToI("16#73#")) + _stAdr + %Chr(%StrToI("16#51#")) + %Chr(%StrToI("16#0F#")) + %Chr(%StrToI("16#02#")) + %Chr(%StrToI("16#1F#")) + %Chr(%StrToI("16#20#")) + %Chr(%StrToI("16#7A#")) M.Mei_write := _val |
...
| Info | ||
|---|---|---|
| ||
O protokole M-Bus si môžete prečítať aj blogblogy: |
| Info | ||||||
|---|---|---|---|---|---|---|
| ||||||
Priložený ZIP obsahuje konfiguráciu linky, stanice a meraných bodov s M-Bus protokolom, ktoré komunikujú s prietokomerom Sensus MeiStream 150 s komunikačným modulom HRI-Mei a s použitím prevodníka EthMBus-5 firmy JC-e v UDP móde (prevodník má IP adresu 192.168.1.1 v konfigurácii linky).
|
| Kotva | ||||
|---|---|---|---|---|
|
...