Editing of all objects in the process D2000 CNF is being performed in the configuration dialog box, a specific part of which is common for all editable objects and another part depends on the type of edited object.

Configuration The configuration dialog box of I/O tags consists of several parts (tabs) that contain the similar parameters. Display The display of particular tabs depends on the category of the particular I/O tag.

General properties
Groups
Process alarms
Destination
Address
Filter
Conversion
Output control
Default value
Polarity
Verification

...

A text string describing the I/O tag. Maximum: 128 characters.
It is possible to use the Dictionary (press CTRL+L to open).

Status text

Defines a status text for the I/O tag. Status The status text allows to redefine redefining labels of individual I/O tag values.

...

Technical units of the I/O tag. Maximum: 12 characters. Possibility to use the Dictionary (press CTRL+L to open).

Limits

Technological limits may be defined for I/O tags of Ai, Ao, Ci, Co, TiR, and ToR types.

Kotva
procesne_alarmy
procesne_alarmy
Process alarms

...

Image RemovedImage Added

Timeout

Time delay (in seconds) for the evaluation of process alarm. Process alarm is raised, if a the cause of raising the alarm is valid at least during this period.
Note: the time delay is applied only to status alarms - transition alarms occur immediately when the value is changed.

Block Alarms

The Block Alarms check box checkbox disables the evaluation of process alarms.

Ignore Invalid

If checked, it allows to remove removing invalid values when evaluating process alarms.

Example: Value change from S1 to S2 is executed as follows: S1 --> invalid --> S2.
If the parameter is checked, the alarm evaluation will be: S1 --> S2.
If the parameter is not checked, the alarm evaluation will be: S1 --> invalid --> S2.

...

  • Alarm - the column contains all possible causes of raising process alarm for the object.
  • State - the radio buttons allows to select allow selecting just one of the State, Transition, or None options. Enabled State option means, that the process alarm starts when the value of the I/O tag is at least within for the period defined by the Timeout parameter, in the particular state (the name of a particular state is placed in the particular respective row, in the Alarm column - pa_ValueStateName).
  • Transition - checked Transition option means , that the process alarm starts when the I/O tag value passes to a particular state (the name of a particular state is placed in the particular respective row, in the Alarm column - pa_ValueStateName).
  • None - process alarm is not evaluated when this option is enabled
  • ACK - checked ACK option means , that the process alarm must be acknowledged by an operator in process D2000 HI. "Transition" process alarm must be always acknowledged.
  • Critical - flag of critical this process alarm will have the critical flag.
  • Monitor - the option will write cause a particular change of the I/O tag value state to be written into the log database as a spontaneous value change.
  • Display mask - a selection of a display mask, that will be used in process D2000 HI (the Alarm list window - the Event description column) after changing the status of one of the defined process alarms to a particular state.

Raise SIGNAL

Raise SIGNAL parameter contains three checkboxes with the following function:

  • the first checkbox - is placed below the State and Transition columns. Enabling (checking) the optionWhen the option is enabled (checked), the system generates the a signal, if any of the configured process alarms occursoccur.
  • the second checkbox - is placed below the Critical column. Enabling (checking) the optionWhen the option is enabled (checked), the system generates the signal, if any of the configured critical process alarms occursoccur.
  • the third checkbox - is placed below the Monitor column. Enabling (checking) the optionWhen the option is enabled (checked), the system will generate the signal, if any of logged the changes of defined process alarms is are written into the log database.

Generating the signal means that the system tag Signal_Trigger is set to the TRUE value.

Kotva
ciel
ciel
Destination

...

It can contain the reference to a column of an object of the Structured variable type in the form ObjectName[0]^ColumnName. In such a case, the KOM process tries to copy the values of arrays with the start address which is configured in tab Address to the relevant column of the structured variable. There is no need to create individual I/O tags for each item of an array or for some other repeated address structure. Only selected communication protocols support this functionality. More additional information is mentioned in the description of a particular communication protocol.
Note: it is also possible to use a non-zero index, e.g. SV.MyVal[7]^MyCol - in this case, values are written into the structured variable starting with the specified row (in example 7).

The copying of values into the column of a structured variable is implemented only for input, the change of a particular value of a structured variable (e.g. in HI or via event) will not be transferred as output through the communication into the device.

The processing of values which that are inserted into a structured variable is limited. Following The following processing is applied:

All parameters which are to be processed (e.g. limit setting) are applied according to the setting of the I/O tag where the destination column is configured (i.e. "master" I/O tag). Time stamp The timestamps of the values inserted into the column of a structured variable is are identical to time stamp the timestamp of a "master" I/O tag. Value The value of the "master" I/O tag and its behavior is normal, and it is not influenced byt by the configuration of the destination column.

Kotva
address
address
Address

...

Address

I/O tag address. Address The address type depends on the communication protocol of the station, that which is the parent of a particular I/O tag. Address The address is stored in the configuration database in text form. Particular A specific communication protocol converts this address into a binary form. For internal communication protocols of the D2000 system, a protocol-dependent dialog box with the validity check of given a specified address is used during the I/O tag address configuration. For external communication protocols (OEM Protocol 1 up to OEM Protocol 16) of the D2000 system, the address is entered directly in text form.

During the saving of the I/O tag configuration, the uniqueness of its address is tested. If the address of the I/O tag is not unique (within a parent station), the system will inform you about the error.
kolizna adresaImage Removed
kolizna adresaImage Added

By choosing the option Yes, a new CNF dialog window opens. Only I/O tags with conflicting address addresses sharing a common parent are displayed in this window. The user can (but does not have to) change the address of these I/O tags.
merane body s rovnakou adresouImage Removed
merane body s rovnakou adresouImage Added

Minute correction

Parameter A parameter is an integer number within the range of 0 to 59. If the time stamps timestamps of receiving values should be rounded to minutes, this value is important for rounding either up or down.
If the value is 0, it means the time correction is ignored. The time stamps timestamps of values that are limited by interval (0 - parameter) will be rounded down, i.e. to the minute in which they were received. Other time stamps Higher timestamps will be rounded up by one to the next minute.

Kotva
filter
filter
Filter

...

Using the following group of parameters allows to define for defining a filtering method of analog inputs and outputs -  Ai, Ao, Ci, Co, TiR, ToR.

...

Values of I/O tags acquired from the communication, which have a new time and their values are not changed, will be represented as new values.

Limits by device

This option is available , if the device and communication protocols allow to detect detecting device limits. If the parameter is checked, then the limits gained obtained from communication with this device will be used.

None

Filtering The filtering of the I/O tag values is not enabled.

Value = New * K + Old * (1-K)

Weighed first-order filter.

  • Value- value after filtering
  • New - filtered value
  • Old - previous value
  • K - the weight of the new value - a real number from the interval (0,.0 ; .. ..1.;1,0).

The Repeat Parameter: This parameter provides compatible weighted filter behavior for change-based and server protocols (IEC-60870-5-101, IEC-60870-5-104, Modbus Server, TG809, BACnet, OPC, OPC UA ...). If a positive value of the Repeat parameter is specified, it determines the period of repeated generation of the value received by the I/O tag - similar to when the same value is repeatedly retrieved for periodically polling protocols (e.g. Modbus Client). So, if a one-time change of the I/O tag value occurs, the weighted filter will gradually progress towards toward the target value by repeating this value.

...

If a new value is less than the Min value, the system will assign the Min value to this new value. If a new value is greater than the Max value, the system will assign the Max value to this new value. This filter may be used to eliminate values, which technically may not break given limits (e.g. throttle stops), but the particular sensor (converter) may also generate values out of limits

...

If a new value is less than the Min value, the system will assign the SetMin value to this new value. If a new value is greater than the Max value, the system will assign the SetMax value to this new value.

...

If a new value is less than the Min value or greater than the Max value, it will be discarded.

...

I/O tag values, which are changed by defined Number times in defined time (Time spin button), will pass an cause the object value state change to Oscillate.

Value absorption

The system will assign the value from the Value option to a particular I/O tag , when its value belongs in <Value-Range ....Value+Range> interval .(this option is used to suppress the "noise" of I/O tag value)

Value delay

The system will assign a value (True or False - it is defined by selecting checking the particular buttonrespective checkbox) to a particular I/O tag only after it is was unchanged during a defined time [s]. This filter can be configured for Boolean and Quaternary values only.

Round value time to

Allows rounding the value time to the closest time with a defined period (parameters Hours, Minutesand Seconds).

Kotva
prevod
prevod
Conversion

...

Conversion to technical units may be defined for analogue analog and cardinal inputs and outputs - Ai, Ao, Ci, Co, TiR, and ToR.

Conversion typeConversion formula
None-
LinearOutput = A * Input + B
PolynomialOutput = A * Inputn *B x Input + C
Pt 100
Output =Image RemovedImage Added

a = -5.802E-05
b = 0.390802

Simatic S5Time
Conversion of the Siemens Simatic relative time structure.
Image Removed

A, B, C, n - conversion constants


Image Added
Absolute valueOutput = abs(Input )
Bitmask filter AND
Output = ((A + B<<32) & Input ) >> C
Note: the filter is configurable only for Integer inputs (Ci), constant A is a mask for the lower 32 bits, constant B is a mask for the upper 32 bits, and constant C indicates an optional shift of the result to the right by C bits. If C is negative, the result is shifted to the left by -C bits.

A, B, C, n - conversion constants

The above table shows the conversion performed when The above table shows the conversion performed when processing the value received from the device. An inverse conversion is performed when writing to the output I/O tag.

Therefore for I/O tags of output type (Ao, Co, and ToR), it's possible to configure only the linear conversion , because only there exists unique in this case there is an unambiguous inverse function used during value writing into a particular device.

Kotva
ovladanie_vystupu
ovladanie_vystupu
Output control

...

  • If the option is enabled, then a value must be entered into the Start value input box and a control object must be defined - Control object input box. Valid The valid mode is defined by means of Manual/Auto radio buttons. Mode A mode may be changed in process the D2000 HI process and its changes are to will be stored in the system database. Operator The operator can change the required value in Manual mode. Its change is also stored in the system database.
  • If the option is disabled, then only one of the Auto or Manual modes may be enabled. OperatorThe operator's right to change the required value is defined by means his/her of their access rights. Changing a required value in process the D2000 HI process is allowed to an operator with Control access right level (or higher).

Save mode changes

A mode change (from Manual mode to Auto mode and vice-versa) is stored into in the configuration database.

...

Each start value change performed through the control window in process D2000 HI is written into the configuration database.

Start value

Start The start value is saved in text form. Then it is converted to a corresponding value type and it is set as the value of the I/O tag. If it is not entered or the conversion has not been executed successfullysuccessful, the initialization of output I/O tags' values is not executedperformed.

Start value checkout Image Removed Image Added

The button Start value checkout (Image RemovedImage Added) checks the defined start value and reports failure if the conversion is not successful.

...

Enabling the option causes the value of the output I/O tag to copy the value of the control object.

Manual

Enabling the option causes the value of the I/O tag to use the value specified in the parameter Start value or the operator sets it manually in process D2000 HI.

...

I/O tag output mode.

  • Value - I/O tag with its own value acquired from the communication. Writing a new value of the I/O tag into a particular device is accompanied with the by a transient state. New The new value is confirmed after the communication verifies the writing.
  • Command - Output I/O tag, that may not have its own value (cannot acquire it by means of the communication with a particular device). Writing a A new value written into the device do does not pass go through the transient state. Control windows in process the D2000 HI process also allow to write a writing the same value several times (e.g. enabled ON and OFF buttons at the same time - for value outputs, there is always enabled unlike the value output tags where only the button of the opposite value to than the current one is enabled).

Execution timeout

The parameter defines the command execution timeout - writing a value of the I/O tag. If the value of the parameter is different from zero and writing an I/O tag value is not confirmed during the timeout, the writing is not consider as considered successful and there is occurred a process alarm ErrorWriteCmd occurs if it is defined (the item ErrorWriteCmd in the tab Process alarms).

...

The parameter Use D2000 Server time allows to use using the time of the computer where the process D2000 Server is running as the time for output I/O tag's value. Otherwise, the time acquired by the communication with the device , is used.

Maximum step size for a change

The parameter "The parameter Maximum step size for a change" allows to limit limiting the maximum change of value for manual contolcontrol. This limitation has the character of a recommendation and a user is able to override it.

Kotva
nahradna_hodnota
nahradna_hodnota
Default value

...

Default The default value allows to replace replacing an I/O tag value acquired by process the D2000 KOM by process, with another one in some cases, (e.g. sensing the sensor device breakaway, a failure of the communication with whole the device). An I/O tag value may be replaced by a value of other another object (so-called control object) , or adjusted manually by the operator of process the D2000 HI process via the control window.

Use default value

Enables the use of default value. Default The default value for a particular I/O tag is used automatically after starting process from the beginning - since the D2000 KOM process is started.

Save changes of the default value mode

If the option Use default value is checked, then a change of the use of default value or disabling the default value from the control window in process the D2000 HI process is to be stored in the configuration database (it enables or disables the option Use default value).

...

If the communication process evaluates an I/O tag value as unknown (acquired from the communication or failure of the communication with the station), then the default value will be used. After the communication is recovered, the default value is cancelled will be ignored and the I/O tag gets a value acquired from the communication. This change into the default value or cancelling ignoring of the default value is will not to be written into the configuration database (even if the option Save default value changes is enabled).

Allow switchover to default value in HI

Operator The operator may switch an I/O value into the default value and vice-versa in process the D2000 HI process.

Enabled mode change

The option allows us to enable or disable mode change (from Manual mode to Auto mode and vice-versa) on the operator level in process the D2000 HI process. If the option is enabled, a control object must be entered - Control object item.

...

A change of the default value, adjusted manually in a particular control window, is to be stored in the configuration database.

Kotva
default_value
default_value
Default value

Default The default value is stored in text form. It is converted to a required value type and then is used as the value of the I/O tag.
If it is not defined or conversion has failed, the initialization of the values of the output I/O tag will not be executed (more info...).

Default value verification Image Removed Image Added

The Default value verification (Image RemovedImage Added) button will verify entered default value and if is not valid, the system will display the report on it.

Kotva
riadiaci_objekt
riadiaci_objekt
Control object

A The value of this object will replace a the value of the I/O tag in Auto mode.

Auto

Enabling the option , will cause the default value of the I/O tag default value will be copied a to follow the value of the control object.

Manual

Enabling the option , will cause the default value of the I/O tag default value will to use a number value in the Default value input box or it will can be adjusted manually entered by the operator in process the D2000 HI process.

Kotva
polarita
polarita
Polarity

...

Logical The logical polarity of the I/O tag is adjusted for digital I/O tags - Di, DooutDout.

  • Normal - an I/O tag value is not to be changed.
  • Inverse - an I/O tag value is to be inverted.

...

The tab Verification allows to set setting confirmation for writing the output (verified) I/O tag (verified) using an input object (verifying). Verifying The verifying object can be an object of I/O tag, Switch, or other types (e.g. Eval tag). For the I/O tag with enabled verification to be written successfully, it is not enough to send a value to the communication (and receiving receive the confirmation of successful writing from the partner station, if the communication protocol allows it), but a value of the verifying object must be received, that confirms the writing.
Verification is meaningful, useful if the D2000 system is part of a distributed control system (e.g. in energetics), where successful writing of an I/O tag (e.g. setting the setpoint for the generator output) needndoesn't mean that the real value was set changed to a required level value (the generator can be in the manual mode with the regulator disconnected, so the setpoint change of the regulator does not have any effect on the generator output). Only the new after a new value of the I/O tag which represents the real value of the measured generator output, that will be if it is the same (with the Delta tolerance) as the value set, means that writing was successful.

...

  • Writing a verified output I/O tag is successful , if a new value of the verifying object that confirms the value written will comes come within the execution timeout (the Output control tab). Values of the verifying object, which do not meet the condition, will not cause any action (i.e. they do not cause unsuccessful writing).
  • If the execution timeout is 0, there is waiting without limitwaiting is not time-limited.
  • If the execution timeout expires, writing to the output I/O tag is not considered to be successful unsuccessful and the alarm ErrorWriteCmd occurs, if it is configured.
  • Within the execution timeout, several values of the verifying object may come. The values, which are not equal to the value written (with the Delta tolerance) do not cause the writing to be treated as unsuccessful, i.e. writing to the I/O tag is unsuccessful when only after the execution timeout exceeds.
  • If the value of the verifying object is equal with to the written value (with the Delta tolerance) of the output I/O tag when writing(with the Delta tolerance) when the value was written, the writing is acting like as if the verification is not enabled, i.e. it does not wait for a new value of the verifying object, but writing is successful immediately after sending the value to the communication (and after confirmation, if the protocol supports it).

Table: evaluation of equation and validity of the tolerance parameter Delta for various type combinations of verifying object and verified output I/O tag.

...

An I/O tag (or Eval tag, Switch, ...), the value of which is the reaction to writing to the verified output I/O tag.

...

A number that determines the permitted deviation of the values of the verified output I/O tag and the verifying object. If the absolute value of the value difference is lower smaller or equal to Delta, the writing is successfully confirmed (Abs(Out-In)<Delta, details for various type combination combinations are shown in the table above). For I/O tags of TxtO type (text output), the parameter is not used.

...

Delta is a percent of range (the range is the difference between the high and low limits of the verified object, i.e. HL - LL ). If the limits are defined dynamically and they are crossed, verification is evaluated according to the last valid Deltaand low limits of the verified object, i.e. HL - LL ). If the limits are defined dynamically and they are crossed, verification is evaluated according to the last valid Delta.


Follow the verifying object value

If this option is active, the output I/O tag copies the value of the verifying object (but without performing writes in the communication). It is thus possible to ensure e.g. initialization after the start or controlling from the scheme by entering changes relative to the current value (e.g. +/- buttons on the scheme).


Info