...
The protocol is a modification of the protocol the IEC 870-5-104 protocol working on the basis of TCP network communication. The protocol has been modified specifically for redundant communication with the system Siemens Sinaut SpectrumSpectrum system. It supports the balanced mode and both active and passive establishing the establishment of the communication (a connecting party and a listening party) according to the station protocol parameters, and and therefore allows to interconnect not only the D2000 system with the Sinaut system but also two D2000 systems.
Picture: the D2000 redundant system communicating with Sinaut redundant system in a redundant network
Image RemovedImage Added
The picture above shown shows TCP connections - each process D2000 KOM (D2000 Hot, D2000 StandBy) with eachSinaut each Sinaut (Sinaut Hot, Sinaut StandBy)
...
- Originator ASDU address - is 1 byte, it is defined as a line number.
- ASDU address - is 2 bytes, it is defined as station address. Foe For each station on one line, there a different ASDU address must be defined different ASDU address.
Kotva |
---|
| NOTE_ASDUADDR |
---|
| NOTE_ASDUADDR |
---|
|
Note: Because of the Sinaut data model, the low and high address bytes are changed unlike exchanged (in contrast to the standard IEC 104 implementation), i.e. a big-endian instead of a little-endian is used.
Example:
station address=1, ASDU address is sent as bytes 0, 1 bytes
station address=513 (2*256+1), ASDU address is sent as 2, 1 bytes
For better orientation, station address may be defined in the form of ByteHI, ByteLO, i.e. address 2,1 is the same as 513 - Cause of transmission - is 2 bytes (it also contains Originator ASDU address)
- Information object address - 3 bytes, it is defined as I/O tag address
Note: Because of the Sinaut data model, the low and high address bytes are changed unlike are exchanged (in contrast to the standard IEC 104 implementation), i.e. a big-endian instead of a little-endian is used.
Example:
I/O tag address=1, ASDU address is sent as bytes 0, 0, 1 bytes.
I/O tag address=66051(1*65536+2*256+3), ASDU address is sent as bytes 1, 2, 3.
For better orientation, the I/O tag address may be defined in the form of ByteLO, ByteMIDDLE, ByteHI, i.e. address 1,2,3 is sent as bytes 1, 2, 3.
There are implemented the The following ASDU types in the monitoring direction of logging (from Sinaut system to D2000 system and also vice-versa in balanced mode) are implemented:
Table 1
ASDU type | I/O tag types |
---|
1 - Single-point information | Di, Qi (On/Off), Ai, Ci |
2 - Single-point information with a time tag | Di, Qi (On/Off), Ai, Ci |
3 - Double-point information | Qi, Ai, Ci |
4 - Double-point information with a time tag | Qi, Ai, Ci |
5 - Step position information | Ci, Ai * |
6 - Step position information with a time tag | Ci, Ai * |
7 - Bitstring of 32 bits | Ci, Ai |
8 - Bitstring of 32 bits with a time tag | Ci, Ai |
9 - Measured value, normalized value | Ai |
10 - Measured value, normalized value with time tag | Ai |
11 - Measured value, scaled value | Ci, Ai |
12 - Measured value, scaled value with time tag | Ci, Ai |
13 - Measured value, short floating point value | Ai |
14 - Measured value, short floating point value with time tag | Ai |
15 - Integrated totals | Ci, Ai |
16 - Integrated totals with time tag | Ci, Ai |
17 - Event of protection equipment with time tag | Ci, Ai, TiR ** |
18 - Packed start events of protection equipment with time tag | Ci, Ai, TiR *** |
20 - Packed single-point information with status change detection | Ci, Ai |
21 - Measured value, normalized value without quality descriptor | Ai |
30 - Single-point information with time tag CP56Time2a | Di, Qi (On/Off), Ai, Ci |
31 - Double-point information with CP56Time2a tag | Qi, Ai, Ci |
32 - Step position information with CP56Time2a tag | Ci, Ai * |
33 - Bitstring of 32 bits with CP56Time2a tag | Ci, Ai |
34 - Measured value, normalized value with CP56Time2a tag | Ai |
35 - Measured value, scaled value with CP56Time2a tag | Ci, Ai |
36 - Measured value, short floating point value with time tag CP56Time2a | Ai |
37 - Integrated totals with time tag CP56Time2a | Ci, Ai |
38 - Event of protection equipment with time tag CP56Time2a | Ci, Ai, TiR ** |
39 - Packed start events of protection equipment with time tag CP56Time2a | Ci, Ai, TiR *** |
40 - Packed output circuit information of protection equipment with time tag CP56Time2a | Ci, Ai, TiR *** |
Note: The individual bites Individual bits of the quality byte that inform us on quality (SIQ for ASDU 1,2,30; DIQ for ASDU 3,4,31; QDS for 5..14,20,32..36) are mapped to the flags FLA A (bit 0.bit), FLB B (bit 1.bit) .. FLH H (bit 7.bit).
For example:
for ASDU 4: FLA A=DPI bit 0, FLBB=DPI bit 1, FLCC=0, FLDD=0, FLEE=BL bit, FLFF=SB bit, FLGG=NT bit, FLHH=IV bit.
for ASDU 16: FLAA..FLE E = Sequence number bity bits 0..4, FLFF=CY bit, FLGG=CA bit, FLHH=IV bit
Moreover:
- if a bit is set to IV (Invalid) , bit is set, the value state status will be Invalid
- if some any of the bits are set to NT (Not topical), SB (Substituted), BL (Blocked), OV (Overflow), CA (Counter adjusted), CY (Counter overflow) bits are set for corresponding ASDU types, the value state status will be Weak.
* - T-bit of the value of these ASDUs is
in mapped to the
I flag
FI, a number
within in range -64 .. +63
is in goes to a variable of Ci/Ai type
** -
ASDU 17 and
38: SEP byte is in the flags
FLA A (
bit 0
.bit),
FLB B (
bit 1
.bit) ..
FLH H (
bit 7
.bit), following 2 bytes (CP16Time2a) are in a variable of Ci/Ai type as a positive number (0-60 000) or they are in a variable of TiR type as a relative time (0-60 seconds)
The following ASDU types are implemented in the control
course direction (from D2000 system to Sinaut system and vice-versa in balanced mode):
...
ASDU type | I/O tag type |
---|
45 - Single command | Dout |
46 - Double command | Dout, Co |
47 - Regulating step command | Dout |
48 - Set point command, normalised value | Ao |
49 - Set point command, scaled value | Co |
50 - Set point command, short floating point value | Ao |
51 - Bitstring of 32 bit | Co |
58 - Single command with time tag CP56Time2a | Dout |
59 - Double command with time tag CP56Time2a | Dout, Co |
60 - Regulating step command with time tag CP56Time2a | Dout |
61 - Set point command, normalised value with time tag CP56Time2a | Ao |
62 - Set point command, scaled value with time tag CP56Time2a | Co |
63 - Set point command, short floating point value with time tag CP56Time2a | Ao |
64 - Bitstring of 32 bit with time tag CP56Time2a | Co |
To set the bites bits of the "status" byte (SCO for ASDU 45,58; DCO for ASDU 46,59; RCO for ASDU 47,60; QOS for ASDU 48..50,61..63), there are used the flags FLA A (bit 0.bit), FLB B (bit 1.bit) .. FLH H (7.bit) are used except the bitesbits, which are directly set by the variable value ( SCO bit 0, DCO and RCS bites bits 0-1). Having received a response (positive/negative), the flags FLAA .. FLH H flags are set according to the bites bits of the "status" byte.
When sending commands (ASDU ASDUs 45-64), the value of 6 [Activation] is used as CauseOfTransmission. Expecting Whether a response is expected from the controlled station depends on the parameter CMDC parameter. There are the following possibilitiesThese options are available:
- write Writing is considered successful , if there is a packet with RSN confirming the SSN packet with the logwrite command is received.
- Writing is considered finished if write is finished, if there is a response with CauseOfTransmission=7 [Activation Confirmation] and/or 10 [Activation Termination] is received. Success/Unsuccess failure depends on the setting of the P/N bite bit in received CauseOfTransmission.
Redundant communication with Siemens Sinaut system -
...
basic features:
- One communication line of CP Redundant type a TCP/IP-TCP Redundant type communicates with two redundant Sinaut partners Sinaut, where one of them is HOT, the other is STANDBY.
- Communication to with each of the partners is performed through via two redundant networks (i.e. there are created two TCP connections are created for each Sinaut, together so altogether there are four TCP connections by every D2000 KOM process).
- Sending Only the HOT partner (D2000 or Sinaut) is allowed to send new values and replying reply to ASDU 100 [Interrogation Command] is allowed just HOT partner (D2000 eventually Sinaut). Having established the connection, the STANDBY partner only sends confirmations (S-frames) and test frames. However, the STANDBY partner may also send ASDU 100 [Interrogation Command].
- Each partner communicates to the other just through one participant communicates with a partner through a single TCP connection. It sends new values, command confirmations, ASDU 1000 100, and replies to ASDU 100 through the this connection. Second The second connection is standing not used (except for sending test frames through it) and it is only used when a failure on the first connection is detected.
Establishing a connection:
- In the active mode, the process D2000 KOM process connects to specified TCP ports. It sends to a StartDT Act U-frame to each of the ports an U-frame StartDT Act, and waits for a StartDT Con as reply.
- In the passive mode, the process the D2000 KOM process waits on a specified TCP port (see the parameters SP, SH parameters). When the clients are connected, the process waits for an a StartDT Act U-frame StartDT Act, and sends a StartDT Con as reply.
- Further communication is completely symmetrical one. Both partners can send ASDU 100 [Interrogation Command] in order to read all current values and then the partners receive and sends send changed values and commands.
Having established the connection, a partner may send I-frame with ASDU 100 [Interrogation Command] with CauseOfTransmission=6 [Activation] and with ASDUAddres=FFFF, whereby it requests the values of I/O tags for all stations. As a replay, the partner waits for:
- receiving an I-frame with ASDU 100 [Interrogation Command] and with CauseOfTransmission=7 and ASDUAddresASDU Address=FFFF
- receiving the current values of all I/O tags
- receiving an I-frame with ASDU 100 [Interrogation Command] and with CauseOfTransmission=10 and ASDUAddresASDU Address=FFFF
Forced disconnection: If all communication stations on the line are in the simulation mode or the communication is disabled stopped for them, the communication line will be disconnected (closing communication sockets will be closed). If When the simulation mode is not enabled and turned off or the communication is not disabled enabled for at least one one station (the the Parameters tab Parameters of object of the Station type object), the line will be reconnected (and Interrogation Command eventually and/or Counter Interrogation Command will be send sent to the this active station). Then after enabling each next station, there is send an Interrogation Command , when other stations are enabled, the Interrogation Command and/or Counter Interrogation Command is sent to the this station; see the next point.
Forced sending of Interrogation Command or Counter Interrogation Command: If a station is in the status, that it is not in the simulation mode and the communication is not disabled (the Parameters tab Parameters of object of the Station type object), the process D2000 KOM process sends Interrogation Command and/or Counter Interrogation Command (see the parameters OIC, and OCIC parameters).
The protocol IEC870-5-104 Sinaut protocol supports the balanced mode described in the communication protocol IEC 870-5-104 - it is partly a server in part, so it must comply to with the rules of server protocols.
...
- Communication line category: TCP/IP-TCP Redundant
- TCP parameters:
- Host: string containing at most 80 characters – two comma-separated server IP addresses in the form of a.b.c.d
In the active mode, they are the addresses of the server, where to which the process D2000 KOM process is connecting to.
In the passive mode (see the parameters SP, SH), they are the IP addresses of a clientclients, which are accepted by the process D2000 KOM process (if the client is connecting from other IP address, it will be disconnected). - Port: TCP port number (0...65535)
In the active mode, it is the server port, where the process D2000 KOM process is connecting to.
In the passive mode (see the parameters SP, SH parameters), the parameter will be ignored (but however it must be specified, set , it e.g. to the value of 0). - Line number: it is used as Originator ASDU address (1 byte, 0-255).
Kotva |
---|
| komunikacna_stanica |
---|
| komunikacna_stanica |
---|
|
Communication station configuration
...
- Communication protocol: IEC870-TCP Sinaut.
- Station The station address is a decimal number within the range of 0 až 65535, it defines the ASDU address.
For better orientation, the station address may be defined in the form of ByteHI, ByteLO, i.e. address 2,1 is the same as 513 (2*256 + 1). See a a note about the ASDU address.
Note: The protocol supports sending long time stamps timestamps (CP56Time2a tag) in local time or UTC time with defined offset (see the parameter the Use monotonic UTC time+ parameter ).
Kotva |
---|
| stanica_parametre |
---|
| stanica_parametre |
---|
|
Station protocol parameters
...
Station configuration dialog box - tab Protocol parameters.
They influence some of the optional protocol parameters. There can be defined the The following station protocol parameters can be defined:
Table 3
Full name | Meaning | Unit | Default value |
---|
Command Confirm | Confirmation of control ASDUs. If CMDC=0, the process D2000 KOM process is not waiting for confirmation of control ASDUs from the partner station using backward sending a reply ASDU with other a different CauseOfTransmission, . The ASDU is consider considered to be confirmed when a packet containg containing the corresponding ReceiveSequenceNumber is received. If CMDC=1, the process D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 (Activation Confirmation). If CMDC=2, the process D2000 KOM process is waiting for confirmation with CauseOfTransmission=10 (Activation Termination). If CMDC=3, the process D2000 KOM process is waiting for confirmation with CauseOfTransmission=7 or 10 (if both of them are received, just the first of them is taken into account). Having received the corresponding confirmation means that writing is finished (the Transient attribute of written value is evaluated cleared and the WTn timeout stops elapsingtimer is reset). If there a confirmation is received confirmation with other CauseOfTransmission as the process D2000 KOM expect fora different CauseOfTransmission from the one that the D2000 KOM process is expecting, it will be ignored. Writing is successful if the received ASDU contains the P/N bit set to 0. Otherwise, writing is unsuccessful. The value from a received ASDU is backwardly written into the corresponding I/O tag and it is sent to the system. E.g. if an ASDU of type 50 (short floating point) with the value of 1200.0 is sent and the partner station sends an ASDU of type 50 as a reply, P/N bit=0, the value of 999.0 (e.g. due to physical limitations of the given parameter), the the value is to be send by the process D2000 KOM to the systemthen this value will be sent to the system by the D2000 KOM process. | - | 3 |
Debug Input | It is a A mask for a debug level of the input data. A meaning Meaning of the individual bits:- 10. bit - information about the number of points received within General Interrogation
- 21. bit - a information about received values of I/O tags
- 32. bit - balanced mode: Interrogation command was receivedinformation about received Interrogation command
- 3. bit - information about discarded values due to the setting of the Ignore Flagged parameter
| 0 .. 255 | 0 |
Debug Output | It is a A mask for a debug level of the output data. A meaning Meaning of the individual bits:
- 10.bit - balanced mode: a information about the number of points sent within General Interrogation
- 21.bit - it shows a information about sent values of I/O tags
| 0 .. 255 | 0 |
| It allows a flag mapping which that is compatible to with the Sinaut Spectrum ICCP OPC communication. For more information see ICCP compatible flag mapping. | YES/NO | NO |
| The parameter allows to specify specifying the flags of values (data ASDU ASDUs 1-40), which - if set - will cause the incoming value to be discarded. The parameter was implemented when it was necessary to filter out the "Non-topical" flag values that came from the communication partner. The mapping of individual flags from ASDU to A..H flags is as follows: - A - Overflow (OV) - ASDU 5-14, 20, 32-36
- B - no mapping (according to standard this bit should be 0)
- C - no mapping (according to standard this bit should be 0)
- D - Elapsed Time Invalid (EI): ASDU 17-19, 38-40
- E - Blocked (BL) - ASDU 1-14, 17-20, 30-36, 38-40
- F - Substituted (SB) - ASDU 1-14, 17-20, 30-36; Counter overflow (CY) - ASDU 15, 16, 37
- G - Non-topical (NT) - ASDU 1-14, 17-20, 30-36; Counter adjusted (CA) - ASDU 15, 16, 37
- H - Invalid (IV) - ASDU 1-20, 30-40
| A..H | - |
Ignore Unknown Addresses | If IUA=TRUEthis parameter is set to True, the process D2000 KOM process will not show report an error (display an error on its console or write it into the line log files file) in case that incoming value has the an address that does not matching match any of the addresses of I/O tags defined in the D2000 system. | - | False |
Interrogation Covers Counter Interrogation | As a reply to Interrogation, there are also sending ASDU also values of I/O tags configured as ASDUs 15,16,37 (Integrated Totals) will be sent, which are standard usually requested by ASDU 101 [Counter Interrogation]. | - | True |
K (max outstanding I APDUs) | Sending window size i.e. packet quantitynumber of packets, which is are sent by the process D2000 KOM process without receiving a confirmation (S-frame or I-frame). According to the standard, the default value is 12. | - | 12 |
No Flags | If the parameter is True, then the status bit byte of incoming ASDUs is ignored and not saved into the flags FAA...FHH. Flags of output I/O tags are also ignored and they not set written to the status bitbyte. | - | False |
| oic | oic | Order The order for sending of sending ASDU | 100 101 [Counter Interrogation Command] when the station | initializes starts to communicate or when | creating a new station is created. If | OIC<OCICOCIC<OIC, ASDU | 10 101 will be | send sent before ASDU | 101100. If | OICOCIC=0, ASDU | 100 101 will not be sent. The parameter can be set | extra separately for each station. | - | 10 |
ocicocic Counter | Order of The order for sending ASDU 101 100 [Counter Interrogation Command] when initializing the connection. OCIC<OIC, ASDU 101 the station starts to communicate or when a new station is created. If OIC<OCIC, ASDU 100 will be sent before ASDU 100101. If OCICOIC=0, ASDU 101 100 will not be sent. The parameter can be set extra separately for each station. | - | 01 |
| Number A number of repetitions, after which the IP address not responding to ping is to be known as non-functional. See the parameter PTOPing TimeOut. | - | 3 |
Ping TimeOut | If the parameter is other than non-zero, then it defines the timeout (in milliseconds) of a server response for to a ping (ICMP echo) packet. In the background, the process D2000 KOM process sends ping packets to all defined four configured IP addresses. If some of the addresses an IP address repeatedly does not respond for PCNTfor Ping Count-times, it is designated marked as non-functional and the connection is terminated. If the parameter PTO=0, sending ping packet packets to IP addresses is disabled. | - | 0 |
Post Start Delay | When initializing the connection is being established, this parameter defines the delay between receiving StartDT Con response and sending Interrogation Command and/or Counter Interrogation Command. | ms | 0 |
Ssequence | Initial SSN. According to the standard, after establishing the connection the SSN is set to 0, values other than zero could be appropriate used e.g. for testing. | - | 0 |
Server Port, Server Host | The port number and IP address of the interface , where the process D2000 KOM is to be listening process should listen (in a listening mode). If both the parameters are defined, the process D2000 KOM is working process works as passive (it is waiting for connecting Sinaut clients). If the process should listen on all network interfaces, there Server Host must be set SH=to ALL or *. | - |
|
Standby Keep Open | If True, after changing this parameter is set to True, the connection to the partners will not be closed when the status of process the D2000 Server process (the process D2000 KOM is connected to) is changed from Hot into to Standby state (in a redundant D2000 system), connection with partner will not be closed. | - | True |
Station Communication Error | Number The number of unsuccessful attempts to connect after communication breakdown. The , after which the station status is changed into the state St_CommErr after reaching the numberstate. For redundant lines, the communication must be either failed for both TCP connections or a TCP connection with standby-server must be functioning (see the parameters ICF3 and IT), i.e. data from the server are ignoredfail on both TCP connections. | - | 2 |
Station Hard Error | Number The number of unsuccessful attempts to connect after communication breakdown. The connect after a communication error, after which the station status is changed into the state St_HardErr after reaching the numberstate. For redundant lines, communication must be either failed for both TCP connections or working a TCP connection with standby-server must be functioning (see the parameters ICF3 and IT), i.e. data from the server are ignoredthe communication must fail on both TCP connections. | - | 5 |
Strict Redundancy Connection Signalisation | Number The number of TCP connections, which must be opened so that the line could be considered as OK. There are 4 connections (2x Sinaut servers, each of them has 2 network addresses). | - | 4 |
Tcp Keep Init | The parameter is implemented for use on OpenVMS platforms only. If it is other than zero, then defines the timeout (in seconds) for opening a new connection to the server. For OpenVMS, the default value is 75 seconds, for Windows, it is 20 seconds. | - | 0 |
TCP NoDelay | TND parameter sets a low-level parameter of TCP_NODELAY sockets which switch off disables a default TCP packet linkingcoalescing. |
|
|
W (ack after receiving W APDUs) | Quantity The number of received packets, after which the process D2000 KOM process sends an S-frame confirmation. According to the standard, the default value is 8. There It must be true that W < K, the standard recommends W = 2/3 * K. | - | 8 |
Wait Timeout T1 | Timeout The timeout for receiving the a confirmation of a sent I-frame sent (either the a confirmation within the a received I-frame or the an individual S-frame itselfis expected) or a sent U-frame. If the process D2000 KOM process does not get receive the confirmation in the time within WT1 limit, it closes the TCP connection. According to the standard, the WT1 default value of WT1 is 15000 ms. | ms | 15 000 |
Wait Timeout T2 | Timeout The timeout for sending the a confirmation of a received I-frame received. WT2 < WT1. If another I-frame (which confirms the the received I-frame received) is not sent in within the time WT2 limit since the I-frame was received, so then the process D2000 KOM process sends an S-frame confirming the received I-frame to the partner. According to the standard, the WT2 default value of WT2 is 10000 ms. | ms | 10 000 |
Wait Timeout T3 | Timeout The timeout for sending test frames (U-frame TEST ACT). If no data are sent in any direction for a long longer time than WT3, an a TEST ACT U-frame TEST ACT will be sent to by the process D2000 KOM after expiration of the WT3 time and there process and a U-frame TEST CON is expected (in within the WT1 time after sending) receiving a U-frame TEST CONlimit). If the WT3 on the partner side is partner's WT3 is set to a lower value, it sends the test frames and the process D2000 KOM process replies to them. According to the standard, the WT2 default value of WT3 is 20000 ms. Setting the value to 0 disables sending test frames. | ms | 20 000 |
Wait Timeout N | Timeout for The timeout for receiving the confirmation of a sent value sent. Receiving e.g. S-frame with RSN (Receive Sequence Number) confirming , that the other party received the previous I-frame doesn't mean , that the I-frame was processed. In Within the WTn time limit, the process D2000 KOM waits for receiving the process expects a response (e.g. after sending ASDU with TypeIdentificator=45 [Single Command] with CauseOfTransmission=6 [Activation] there is expected receiving it expects to receive a Single Command with CauseOfTransmission=7 [Activation Confirmation]. After the expiration of the WTn time timeout, the process D2000 KOM process closes the TCP connection. | ms | 60 000 |
The defined parameters, except for , with the exception of Order of IC and Order of Counter IC, are valid for the entire communication line, i.e. they can have to be set only for one a single station on the line.
ICCP compatible flag mappingA status byte of ASDU, unlike Unlike ICCP OPC communication, enables a status byte of individual ASDUs permits the transmission only of a limited group of flags. In Table 4 you can see a conversion of bits of the status byte to the flags which are compatible with ICCP OPC communication (see the ICCP compatible flags parameter).
Table 4
Bits of status byte | Description | ICCP OPC mapping |
---|
8 [IV invalid] | 7 [NT non topical] | 6 [SB substituted] | 5 [BL blocked] | 1 [OV overflow] |
1 | x | x | x | x | INVALID | FH H (NotValid) |
0 | x | 0 | 0 | x | VALID | FA A (Actual) |
0 | x | 0 | 1 | x | BLOCKED | FD D (Blocked) |
0 | x | 1 | 0 | x | SUBSTITUTED | FC C (Entered) |
0 | x | 1 | 1 | x | SUBSTITUTED + BLOCKED | FF F (Blocked Manual) |
IO tag configuration
...
- I/O tag address is mapped to the Information object addressObject Address, i.e. contains 3 bytes and must be within the interval of 0...16777215.
For better orientation, the I/O tag address may be defined in the form of ByteHI, ByteMIDDLE, ByteLO, i.e. address 1,2,3 is the same as 66051 (1*256*256 + 2*256 + 3). See a a note about the IOA address.
The I/O tag with an address starting with %IGNORE will be ignored. - Input The input I/O tags must have corresponding types (Ai, Ci, Di, Qi) for received ASDU, see the see table 1.
- For a particular type of output I/O tag (Ao, Dout, Co), it is necessary to set an ASDU type of ASDU that should be used, see the table see Table 1 and table Table 2.
- It is possible to configure one input I/O tag and more multiple output I/O tags on the same address, while as long as the output I/O tags have different ASDUs. Example:
- I/O tag M1, Di type, address 1,
- I/O tag M2, Dout type, address 1, ASDU 1 (single-point information)
- I/O tag M3, Dout type, address 1, ASDU 45 (single command)
Configuration on partner's side:- I/O tag P1, Dout type, address 1, ASDU 1 (single-point information)
- I/O tag P2, Di type, address 1
Writing into the I/O tag P1 from the partner's side gives a new value to the I/O tagM1. Writings of the I/O tags M2, M3 gives a new value to the I/O tag P2on the partner's sideresults in a new value written to the I/O tag M1. Writing to the I/O tags M2, M3 results in a new value to the I/O tag P2 on the partner's side. - If the Destination Column is configured, then the values received from the address configured at the I/O tag and above are stored in the corresponding items (e.g. objects with addresses 10, 11, 12 ... according to the number of rows of the destination structure).
Tell commands
...
- Ver. 1.0 – December 15th, 2004
- Ver. 1.1 – February 21st, 2011
- Ver. 1.2 – November 16th, 2023 (support for the Destination Column)
...