Possible risks
Data writing into the KOM Archive puts a minimal burden on the operating system (minimal disk operations, most operations are executed in the RAM). Sufficient free disk space is necessary to for the creation of the archive file. It is created immediately with the required size (parameter /KA) and its size will not be changed later.
A problem may occur in ArchivMode mode 1, if too many values are sent into the D2000 system and the D2000 Archiv is consequently overloaded and its functioning is hindered. Another problem may occur when the D2000 Archiv process is not running while sending values from the D2000 KOM process. In such cases, we recommend switching the ArchivMode mode to 2 and to control controlling the KOM Archive reading via a special event using the Tell command READKOMARC. The event should handle the abovementioned problems, e.g. monitoring of the D2000 Archiv process, batch reading of the KOM Archive, the D2000 Archiv load monitoring, etc.
...