The Allen-Bradley CSP/PCCC protocol supports communication with the Allen-Bradley devices of the SLC-500 series using a TCP connection.
It also supports communication via the DF1 gateway with SLCs that communicate via DH+ or DH485.
Communication was tested e.g. with the following SLC:
- SLC 5/05 1747-L551/C Ethernet Processor
- SLC 5/05 1747-L552/C Ethernet Processor
- SLC 5/05 1747-L553/C Ethernet Processor
Note: PCCC message encapsulation is also supported within the Ethernet/IP Protocol (communication with MicroLogix 1100 or SLC 5/05 1747-L553/C Ethernet Processor)
Kotva |
---|
| komunikacna_linka |
---|
| komunikacna_linka |
---|
|
Communication line configuration
...
Parameter | Description | Unit | Default Value |
---|
| Timeout to receive a response from PLC. | s | 1.000 |
| The number of the request retries in case of a communication failure. | - | 3 |
| If using a DF1 gateway, the node address of the destination device (node) on a DH+ or DH485 bus. If the DF1 gateway is not in use, the default value of 0 must be used. | - | 0 |
| Activates the block reading mode (for Integer, Binary, Status, Float, Timer, and Counter types). Input and Output types don't support block reading mode. | YES/NO | NO |
| Maximum block size (2-255 bytes) if a block reading mode is active. | bytes | 40 |
| Activates detailed listings about sending and receiving values. | - | False |
...
The address of the I/O tag is a text in a an SLC-500 format. The address format is:
...