The protocol allows reading data from multifunctional calorimetric counters of the VKP and VKPs CALMEX II types by means of the M-Bus bus (originally used RS232/M-Bus Premex RS-M convertorconverter, after 15 years replaced by converter RS232toMBus-XL45 from www.prevodniky.sk).
...
- Communication line category: Serial (both convertorsconverters), SerialOverUDP Device Redundant (RS232toMBus-XL45 only).
- Mode 1: Baud rate 300, 8 bit, 1 stop bit, even parity, RTS=1, DTR=1 (RTS and DTR signals are not used by RS232toMBus-XL45).
...
- Communication protocol: Premex CALMEX II
- Station The station address is a decimal number within the range of 1..250 (or a hexadecimal number with a hash at the beginning, e.g. #0A) – it is a VKP address. By default, the address is set by the manufacturer according to the serial number (identification number) of the measuring device as the last three digits. If the last three digits are greater than 250, the higher digit of them is not taken into account. If the serial number is one of the numbers of 000, 300, 400, 500, 600, 700, 800, 900 then must be changed.
- Recommended polling parameters: Delay at least 1 minute.
...
Keyword | Full name | Meaning | Unit | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|---|
| Retry Count | Poll repetition Maximum count in case of of request retries. If no response returns after a request had been sent, the station's status will change to a communication error. | - | 2 seconds | ||||||
| Retry Timeout | Delay between poll repetition in case of a communication errorTimeout before resending a request if no response has been received. | ms | 100 ms | ||||||
| Wait Timeout | Delay The delay between the response readings till its finalization. | ms | 500 ms | ||||||
| Wait First Timeout | First waiting for response The delay after sending the request and before reading the pollresponse. | ms | 800 ms | ||||||
| Max Wait Retry | Repetition count of response readings till its finalizationThe maximum number of retries of the response reading. | - | 40 | ||||||
| WakeUp Length | Length (given in characters) of a so-called wake-up message sent before each pollrequest. | - | 20 | ||||||
| WakeUp Delay | Delay The delay between wake-up message and polla request. It is recommended to enable the option WaitTxEMPTY in the line mode configuration. | ms | 400 |
String A string containing the protocol parameters is being defined as follows:
Keyword=value;Keyword=value; ...
Example:
RC=1;RT=500;
If there is used a keyword with an invalid value in the initialization string , there will be used is used, the corresponding default value according the to table 1 will be used.
Kotva | ||||
---|---|---|---|---|
|
...
Possible I/O tag types: Ai, Ci, TiA
Address: A number fro from the following table must be entered (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A):
...
Address | Meaning | Type | Units |
---|---|---|---|
1 | Measuring device ID. | Ci | - |
2 | Access number (measurement number incremented by 1 for each data reading). | Ci | - |
3 | Status number, bit descriptions see the table 3, individual bits are sent to the value attributes. | Ci | - |
4 | Heat quantity. | Ai | MJ,GJ,kWh,MWh |
5 | Heat rate. | Ai | W,kW,MW |
6 | Volume overflow. | Ai | l,m3 |
7 | Volume flow. | Ai | l/h,m3/h |
8 | Forward temperature. | Ai | ºC |
9 | Return temperature. | Ai | ºC |
10 | Measuring device date+time. | TiA | - |
11 | Heat quantity on the 1st date. | Ai | MJ,GJ,kWh,MWh |
12 | Heat quantity on the 2nd date. | Ai | MJ,GJ,kWh,MWh |
13 | Volume overflow on the 1st date. | Ai | l,m3 |
14 | Volume overflow on the 2nd date. | Ai | l,m3 |
15 | 1st date of data. | TiA | - |
16 | 2nd date of data. | TiA | - |
Values saved on the 1st date or 2nd date are sent to the D2000 system with the save time of saving. Measuring The measuring unit of individual parameters depends on the measuring device type.
...
Kotva | ||||
---|---|---|---|---|
|
...
- Ver. 1.0 - March 13th, 2001 – document creation.
- Ver. 1.1 - 7. september September 2016 – support for SerialOverUDP Device Redundant line, information about RS232toMBus-XL45 convertor.
...