Get/set , Dout/set Get/set the , Ao/set , Ao/set
AddressI/O tag typeDescription
LOCK_REMOTEDout

Set the remote controller functionality: Lock (1) / Unlock (0).

LOCK_REMOTE_RDDi

Get

Di, Dout

Get/set the remote controller functionality: Lock (1) / Unlock (0).

OPERATE_OUTPUTDoutDi, Dout

Set the device functionality: the device is stopped (0) / working (1).

OPERATE_OUTPUT_RDDi

Get

the device functionality: the device is stopped (0) / working (1).

OPERATE_DHWDout

Set the domestic hot water heating in the built-in boiler: disabled (0) / enabled (1).

OPERATE_DHW_RDDi

Get

the domestic hot water heating in the built-in boiler: disabled (0) / enabled (1).

OPERATE_MODEAi, AoAo

Set the mode of operation: 0=cooling, 1=dehumidification, 2=ventilation, 3=auto, 4=heating.
Note: for a heat pump, modes 0, 3, 4 are relevant.

OPERATE_MODE_RDAi

Get the

mode of operation: 0=cooling, 1=dehumidification, 2=ventilation, 3=auto, 4=heating.
Note: for a heat pump, modes 0, 3, 4 are relevant.

TEMP_OUTPUT_SPAo

Set the desired outlet water temperature.

TEMP_OUTPUT_RDAi

Get

the desired outlet water temperature.

TEMP_DHW_SPAo

Set the desired temperature of the domestic water in the built-in boiler.

TEMP_DHW_RDAi

Get

the desired temperature of the domestic water in the built-in boiler.

TEMP_WATER_INAiCurrent inlet water temperature.
TEMP_WATER_OUTAiCurrent outlet water temperature.
TEMP_ROOMAi

Current room temperature (external sensor connectable to the indoor heat pump unit).

TEMP_TANKAiThe current temperature of the domestic water in the built-in boiler.
TEMP_SOLARAiThe current temperature of an optional external solar system (if connected).
CONNECTED_IDUDiThe indoor unit is connected (1) or disconnected (0).
TGT_TEMP_SELDi

The current setpoint is the temperature of air TEMP_ROOM (0) or water TEMP_OUTPUT_SP (1).

...

Note: it takes longer to set the values (approx. 12 seconds).
Example: TEMP_OUTPUT_SP has a value of 40 °C. After writing a value of 42, a reading follows which changes the value back to 40. Only only after approx. 12 seconds does the value of the I/O tag TEMP_OUTPUT_RD change to 42.