Address | I/O tag type | Description | ||
---|---|---|---|---|
LOCK_REMOTE | Dout | Set the remote controller functionality: Lock (1) / Unlock (0). | ||
LOCK_REMOTE_RD | Di | Get | Di, Dout | Get/set the remote controller functionality: Lock (1) / Unlock (0). |
OPERATE_OUTPUT | Dout | Di, Dout | Set the device functionality: the device is stopped (0) / working (1). | |
OPERATE_OUTPUT_RD | Di | Get | Get/set the device functionality: the device is stopped (0) / working (1). | |
OPERATE_DHW | Dout | Set the domestic hot water heating in the built-in boiler: disabled (0) / enabled (1). | ||
OPERATE_DHW_RD | Di | , DoutGet | /set the domestic hot water heating in the built-in boiler: disabled (0) / enabled (1). | |
OPERATE_MODE | Ai, Ao | Ao | Set the mode of operation: 0=cooling, 1=dehumidification, 2=ventilation, 3=auto, 4=heating. | |
OPERATE_MODE_RD | Ai | Get the | Get/set the mode of operation: 0=cooling, 1=dehumidification, 2=ventilation, 3=auto, 4=heating. | |
TEMP_OUTPUT_SP | Ao | Set the desired outlet water temperature. | ||
TEMP_OUTPUT_RD | Ai | , AoGet | /set the desired outlet water temperature. | |
TEMP_DHW_SP | Ao | Set the desired temperature of the domestic water in the built-in boiler. | ||
TEMP_DHW_RD | Ai | , AoGet | /set the desired temperature of the domestic water in the built-in boiler. | |
TEMP_WATER_IN | Ai | Current inlet water temperature. | ||
TEMP_WATER_OUT | Ai | Current outlet water temperature. | ||
TEMP_ROOM | Ai | Current room temperature (external sensor connectable to the indoor heat pump unit). | ||
TEMP_TANK | Ai | The current temperature of the domestic water in the built-in boiler. | ||
TEMP_SOLAR | Ai | The current temperature of an optional external solar system (if connected). | ||
CONNECTED_IDU | Di | The indoor unit is connected (1) or disconnected (0). | ||
TGT_TEMP_SEL | Di | The current setpoint is the temperature of air TEMP_ROOM (0) or water TEMP_OUTPUT_SP (1). |
...
Note: it takes longer to set the values (approx. 12 seconds).
Example: TEMP_OUTPUT_SP has a value of 40 °C. After writing a value of 42, a reading follows which changes the value back to 40. Only only after approx. 12 seconds does the value of the I/O tag TEMP_OUTPUT_RD change to 42.