  • Communication protocol: VONSCH VQfrem 400.
  • The station address is a 16-bit number (1-32767). It can be entered decimally (e.g., 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).
    Address 32768 (#8000) serves as a broadcast for commanding - all devices receive it, but none respond to it.

...

The address of the I/O tag is a 16-bit number (1-65535). It can be entered decimally (e.g. 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).

A special symbolic address STATUS is also supported, which indicates the inverter status register in the form of an integer variable (for the meaning of individual bits, see Table 2).

Table 2 - Status register of a converter

BitMeaningLogical 0Logical 1
0Motor voltagedisconnectedconnected

1

Converter is ready for START via serial linknot readyready
2Converter is reset via serial linkOFFON
3Reverse - required frequency or position is negative OFFON
4Motor readynot readyready
5Active setSET1SET2
6Converter is resetOFFON
7Terminal switch 2not readyready
8Faultdidn’t occuroccurred
9Warningdidn’t occuroccurred
10Start / Stopin stopin start
11End of trial operationOFFON
12Critical warning didn’t occuroccurred
13Frequency change at the output of ramp generatornot finishedfinished
14Position calibration commandnot receivedreceived
15Password authorizationnot validvalid



Table 3 - Quantities - quantities available for reading according to the documentation

AddressDescriptionMeaning
#0001Software version609h for ver. 6.09, (402h for ver. 4.02, 304h for ver. 3.04)

#0004

Voltage range190h for 400V, 191h for 400 ...M, 2b2h for 690V
#0025Freq. INV - the frequency of voltage on converter’s output (stator frequency) +/- XXX,XX Hz
#0026Revolves - output revolutions of the motor+/- XXXX rev/min
#0027Revol/i - evolutions behind gear/transmission+/- XXXX,X rev/min
#0028Freq.RT - rotor frequency (evaluated from speed encoder – IRC)+/- XX,XX Hz
#0029Freq.RF - required converter frequency+/- XX,XX Hz
#002A

MT Curr. - effective current value into the motor

XXX,X A
#002BR.torque - required mechanical motor torque +/- XXX,X Nm
#002CTorque - mechanical motor torque +/- XXX,X Nm
#002DMag. flux - rotor magnetic fluxX,XXX Wb
#002EVolt. MT - momentary motor supply voltage (100.0% responds to 400 V)XXX,X %
#002FVolt. DC - real voltage of converter’s unidirectional DC busXXX V
#0030Inp.pow. - momentary input power into the motorXXX,X kW
#0031

MT power - motor power

XXX,X kW
#0032kW hours - motor energy consumption in kWhXXXX kWh
#0033MW hours - motor energy consumption in MWhXXXX MWh
#0034Teplota chladiča meničaXX,X °C
#0035Temp.INV. - air temperature in the converterXX,X °C
#0036PR ref. - required value of process regulatorXX,X %
#0037PR real - feedback of process regulator (real value)XX,X %
#0038Inp. AIN1 - the value of analogue input AIN1 in % rangeXX,X %
#0039Inp. AIN2 - the value of analogue input AIN2 in % rangeXX,X %
#003AHodnota analógového vstupu 3 v % rozsahuXX,X %
#003B

BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). 

0=input is open
1=input is closed
#003C

RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4  (bits 8-10 from the received value - bit numbering is from 0 to 15). 

0=relay is open
1=relay is closed
#003DHours INV - converter operating time counterXXXX h
#003EHours MT - motor operating time counterXXXX h
#003FPos.ref. - required position in a case of „position“ variable+/- XXXX,X cm
#0040Position - real position+/- XXXX,X cm
#0041Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on+/- XXXX cm
#0042Deviation from zero position when calibrating the ARC position sensorXXXX d
#0043cos(fi ) - momentary value of motor power factor+/- X,XX
#0044See Warnings register 2-
#0045See Warnings register 1-
#0046

See See the Faults register

-
#0048Overload - a momentary value of overloadXXX.X %
#0049Service SL - service displayed variable Slave+/- XXXX d
#004aService MS - service displayed variable Master

+/- XXXX d

All values are transmitted as 16-bit numbers. The KOM process interprets them as signed or positive by address
(signed are #0025-#0027#0029,  #002B#002B,  #002C#002C, #003F-#0041,  #0043#0043,  #0049#0049-#004a).

If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g., coefficient A=0.1 for #0030, A=0.01 for #0028).

Kotva
register_poruch
register_poruch
Table 

...

4 - Faults

...

register (values of the I/O tag with address #0045). If an arbitrary bit is set to logical 1, the corresponding fault/failure has arisen in the converter. 

BitMeaning
0Converter Overcurrent
1Converter Overload
2Converter Undervoltage
3Converter Overvoltage
4Motor Overheat
5Heatsink Temperature
6

Incorrect parameters of currents, motor constants, or speed

7Regulation error
8Identification error
9Output short circuit
10IRC failure (ARC), RM-ARC
11

Input or Output phase loss

12External failure
13Temperature in inverter
14AIN1, AIN2, or AIN3 disconnected
15

reserved


Kotva
register_varovani1
register_varovani1
Table

...

5 -

...

Warnings register 1 (values of the I/O tag with address #0045). If an arbitrary bit is set to logical 1, the converter generates a corresponding warning. 

BitMeaning
0

some warnings W1-W5:
W1 - The converter reduces motor magnetic flux in order to achieve over-synchronous revolutions.
W2 - Magnetic flux has decreased to the minimal value at field suppression.
W3 - Regulator of magnetic flux is saturated (only in vector mode). 
W4 - Regulator of motor torque is saturated (only in vector mode).
W5 - Speed regulator is saturated (only in vector mode). 

1W6 - Motor cooler has reached an increased temperature (over 75 °C).
For VQFREM 400 005, 007, and 011 types, the module temperature is over 90 °C
2W7 - The converter switches itself into scalar mode due to IRC/ARC failure.
3W8 - Signalisation of reverse direction of IRC/ARC.
4F7 - The time needed for motor field suppression has not expired yet (before subsequent start).
5W12 - Process regulator is saturated. Converter frequency has reached its maximum value. 
6

F9 - Position calibration initiated by 9.4.3 command, or calibration of IRC encoder on the synchronous motor.
F10 - IRC zero pulse is being searched on the synchronous motor after the converter was connected to the power network and the START command was selected. 

7F11 - The speed decreased to zero by activating a software terminal switch. 
8F8 - Dynamic deceleration was activated as a result of a sharp decrease in speed.
9W16 - Sensored motor temperature has achieved nonpermissible value.
10W17 - If EWCP,(M),(I) panel is active (2.4.1)and the connection with the converter has failed.
11

F2 - Maximal current regulator (par.13.3.1) is active. It limits the current to the value of parameter 9.10.1

12F3 - The converter is in kinetic backup mode after input power failure.
13F4 - The converter is processing the frequency for the spinning motor.
14F5 - Sleep function of process regulator.
15

F6 - Braking unit is active.

Kotva
register_varovani2
register_varovani2
Table

...

6 -

...

Warnings register 2 (values of the I/O tag with address #0044). If an arbitrary bit is set to logical 1, the converter generates a corresponding warning. 

BitMeaning
0W23 - The converter recognized no load at output terminals U, V, W at START command. 
1F12 - Terminal switch 1 or terminal switch 2 is switched on.
2F13 - The function „flux braking“ (8.3.1) increases motor excitation proportionally to UDC-UDCnom
3W9 - Converter input phase was interrupted 
4reserved
5F14 - OFF-LINE identification of some motor parameters (Rs, Ls+Lm, Uinit).
6

W25 - The air temperature in the converter is more than 70 °C. 

7reserved
8W18 - Serial communication error has occurred - RS232 (RS485)
9F16 - It signalizes, that relay with the function „shut-down, overload“ has just been released.

...