- accumulated work for 3 tariffs
- instantaneous power
- quarter-hour power take-offconsumption, including the archival data
...
- Communication protocol: Incos/VUVT PMEL 04.
- A station address is a decimal number (or a hexadecimal number with a hash at the beginning, e.g. #0A) - according to the settings of PMEL configuration jumpers.
- A time Time synchronization of the station is required.
Station protocol parameters
Communication station - configuration dialog box - tab "Protocol parameters".
They could influence some optional protocol parameters. You can set the following parameters:
Table 1
Key wordKeyword | Full name | Meaning | Unit | Default value |
---|
| Retry Count | Number The number of call request retries when an error in communication occurs. | - | 2 |
| Retry Timeout | Delay The delay between the retry call when an error in communication occurs. | ms | 1000 |
| Wait First Timeout | The first timeout for response reading after sending the message. | ms | 500 |
| Wait Timeout | Timeout between the response readings until it is completed. | ms | 500 |
| Max Wait Retry | Number The number of retries of response reading until it is completed. | - | 8 |
| Source Address | Communication address of the source (PCD2000 KOM). | 0 up to 254 | 126 |
| PMEL04B | Communication with PMEL04B device. | YES/NO | NO |
| Timestamp | There is used PMEL04B with the support of time stamp timestamp transmission is used. | YES/NO | NO |
| Allow Automatic Time Synchro | Real-time will be synchronized after the bit EM_TIM bit is set by a device (PMEL04B only PMEL04B). | YES/NO | YES |
I/O tag configuration
...
Table 2: I/O tag addresses distribution:
Electro meterElectrometer | Instantaneous power (Ai) | Accumulation work tariff 1 (Ai) | Accumulation work tariff 2 (Ai) | Accumulation work tariff 3 (Ai) | Quarter-hour power take-off (Ai) | Time difference between curr. and prev. state (TiR) |
---|
1 | 0 | 16 | 17 | 18 | 64 | 200 |
2 | 1 | 19 | 20 | 21 | 65 | 201 |
3 | 2 | 22 | 23 | 24 | 66 | 202 |
4 | 3 | 25 | 26 | 27 | 67 | 203 |
5 | 4 | 28 | 29 | 30 | 68 | 204 |
6 | 5 | 31 | 32 | 33 | 69 | 205 |
7 | 6 | 34 | 35 | 36 | 70 | 206 |
8 | 7 | 37 | 38 | 39 | 71 | 207 |
9 | 8 | 40 | 41 | 42 | 72 | 208 |
10 | 9 | 43 | 44 | 45 | 73 | 209 |
11 | 10 | 46 | 47 | 48 | 74 | 210 |
12 | 11 | 49 | 50 | 51 | 75 | 211 |
13 | 12 | 52 | 53 | 54 | 76 | 212 |
14 | 13 | 55 | 56 | 57 | 77 | 213 |
15 | 14 | 58 | 59 | 60 | 78 | 214 |
16 | 15 | 61 | 62 | 63 | 79 | 215 |
Table 3: Di values, status bits (PMEL04A only
...
):
Address | Meaning |
---|
0 | EPROM error. |
1 | RAM error. |
5 | Program restart on a process module. |
6 | Exceeding the time difference. |
7 | Acknowledgement Acknowledgment of time settings. |
Di values, digital inputs (only PMEL04B), addresses 0 up to 15.
...