Siemens SIMATIC 3964(R) CW communication
...
protocol
Supported device types and versions
Communication line configuration
Line protocol parameters
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
...
On the link layer, this protocol implements the Siemens SIMATIC 3964R protocol and uses it to read from and write to the PLC. The protocol only supports database block (DB) addressing 0-255.
The protocol contains the following header defined by Control Web:
Byte | Name | Description |
---|---|---|
1 | Id | Zone identifier ('D' = data block) |
2 | DB | Number of zone (data block) |
3-4 | DW | Word address within a zone (lower byte, upper byte) |
5 | Cmd | Command ('R' - reading, 'W' - writing) |
6-7 | Count | Number of read / written words (lower byte, upper byte) |
The protocol supports reading data from control PLC automats of Siemens SIMATIC of the S5 and S7 series. PLC Simatic must be equipped with the serial communication point-to-point modules - for more details see the decription of Siemens SIMATIC 3964(R) protocol.
...
Parameter | Meaning | Unit / size | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|
| A mode of communication:
Note: Active communication is used when Control Web is replaced by D2000. | Active Passive Passive (duplex) | Active | ||||||
| Maximum size (in bytes) of data read by a single requestl. Add to this size a 7-byte Control Web header to obtain full length of response (without duplicated DLE bytes) according to the SIMATIC 3964(R) standard. | 4 až 249 B | 128 B | ||||||
| Maximum number of request retries in case of communication error. | - | 2 | ||||||
| A delay before resending a request in case of communication error. | ms | 100 ms | ||||||
| Activates a debug info about the loaded values of I/O tags. Use this parameter only when communication must be debug because it highly uses CPU and slows down the communication. | YES/NO | NO |
...
Identifier <type> | Description |
---|---|
X | Bit (boolean). Specify a bit number 0 to 7 - e.g. DB9,X8.3 |
B | Byte (8 bits unsigned). |
W | Word (16 bits unsigned). |
D | Double word (32 bits unsigned). |
CHAR | Character (8 bits signed). |
INT | Integer (16 bits signed). |
DINT | Double integer (32 bits signed). |
BCD | BCD-coded 2-byte number (0-9 999) |
LBCD | BCD-kódované 4-byte number (0-99 999 999) |
REAL | Floating point number (32 bits according to IEEE754 standard). |
LREAL | Long floating point number (64 bits according to IEEE754 standard). |
DT | Date and Time, 8 bytes in BCD format. |
TIME | Time (32 bits signed) in ms. |
TOD | Time of day (32 bits unsigned) in ms. |
...
- Ver. 1.0 - January 16th, 2020 - document creation.
- Ver. 1.1 - July 10, 2020 - Support for BCD and LBCD.