| Kotva | ||||
|---|---|---|---|---|
|
...
The protocol ensures handles the reading of ID datasheet data from RFID modules , of ID series by ID-Innovations.
...
Table 1
| Parameter | Meaning | Unit /sizeSize | Default value | ||||||
|---|---|---|---|---|---|---|---|---|---|
Moxa Redundancy Check Timeout | A switching period of Moxa redundant equipment in case of longer communication pause. It is relevant only on SerialOverUDP Device Redundant line. | sec | 30 sec |
...
- Communication protocol "ID-Innovations RFID ASCII Protocol".
- Any address parameters are not required. Only one ID-Innovations sensor may be connected to the line. Because of a random module sending only in the moment of card loading, some conflicts could occur on the transmission line.
| Kotva | ||||
|---|---|---|---|---|
|
...
| I/O tag | Address | Meaning |
|---|---|---|
| TxtI | 1 | This text input acquires the value of ID read from the RFID card. The ID of the card is a hexadecimal number. |
| Ci | 1 | A cardinal input value incremented with every a new ID published in a text I/O tag. |
| Co | 1 | After the ID published in TxtI is processed, the same value, as is in Ci, must be written into this I/O tag. This handshaking ensures that no information about the received ID will be lost. |
...