Communication supports reading and writing data by means of the UNIP protocol (© IpeSoft Ipesoft Žilina).
Kotva |
---|
| komunikacna_linka |
---|
| komunikacna_linka |
---|
|
Communication line configuration
...
- Communication protocols: UNIP, UNIP Input Only, UNIP Time Synchro, UNIP Input Only Time Synchro, UNIP SCAN.
- Station The station address is a decadis decimal number within the range 1...230, or a hexadecimal number with a hash at the beginning (e.g. #1A).
- The UNIP Time Synchro and UNIP Input Only Time Synchro protocols execute the real-time synchronisation synchronization for stations (time is included in pollthe request).
Note:
The UNIP SCAN protocol is a passive protocol that tracks the active communication of other another UNIP master/slaves system. It doesn't send polls , but decode decodes the tracking tracked communication.
Kotva |
---|
| stanica_parametre |
---|
| stanica_parametre |
---|
|
Station protocol parameters
...
Parameter | Meaning | Unit | Default value |
---|
| Poll repetition Maximum count in case of of request retries. If no response returns after a request had been sent, the station's status will change to a communication error. | - | 3 |
| Delay between poll repetition in case of a communication errorTimeout before resending a request if no response has been received. | ms | 2000 ms |
| First waiting for response The delay after sending the request and before reading the pollresponse. | ms | 500 ms |
| Delay The delay between the response readings readings till its finalization. | ms | 500 ms |
| Repetition count of response readings till its finalizationThe maximum number of retries of the response reading. | - | 8 |
| First waiting for a response after writing, the ACK acknowledge is expected. | ms | 700 ms |
| Waiting for a response after a request to read archive data. | s | 1 s |
| In D2000 V5.00.017 Rel.A020430541, the interpretation of I/O tags of the AI and AO types of the forms of 3, 5, 6, and 7 has been modified to signed ones. The value of AIBC=YES enables backward compatibility and these I/O tags will be interpreted as unsigned. | - | NO |
| For the UNIP SCAN protocol only – time (in seconds) within which the response for a given station must be received, otherwise the station passes to a communication error. | s | 600 s |
Use Daylight Saving Time in TS Req. | Setting the parameter to YES activates the use of daylight saving time in the timestamped requests. | - | NO |
String A string containing the protocol parameters is being defined as follows:
Keyword=value;Keyword=value; ...
Example:
RC=1;RT=500;
If there is used a keyword with an invalid value in the initialization string , there will be used is used, a corresponding default value according the to table 1 will be used.
I/O tag configuration
...
Ai, Ci, Di for the UNIP Input Only and UNIP Input Only Time Synchro protocols.
Ai, Ao, Ci, Co, Di, Dout for the UNIP, UNIP Time Synchro, and UNIP SCAN protocols.
Address: Decimal number within the range of 0...255.
...