IEC 60870-5-104 Server communication protocol
Supported device types a and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Tell TELL commands
Literature
Document revisions
...
- Originator ASDU address is 1 byte, it is defined as a line number.
- ASDU address is 2 bytes, it is defined as station address. For each station on a line, a different ASDU address must be defined.
- Cause of transmission is 2 bytes (it also contains Originator ASDU address)
- Information object address IS 3 bytes, it is defined as an I/O tag address.
- The following ASDU types in the direction of monitoring are implemented (from the D2000 system to the control station and also vice-versa in balanced mode):
Kotva | ||||
---|---|---|---|---|
|
ASDU type | I/O tag type |
---|---|
1 - Single-point information | Dout |
2 - Single-point information with time tag | Dout |
3 - Double-point information | Dout,Cout |
4 - Double-point information with time tag | Dout,Cout |
5 - Step position information | Cout |
6 - Step position information with time tag | Cout |
7 - Bitstring of 32 bits | Cout |
8 - Bitstring of 32 bits with time tag | Cout |
9 - Measured value, normalized value | Ao |
10 - Measured value, normalized value with time tag | Ao |
11 - Measured value, scaled value | Cout |
12 - Measured value, scaled value with time tag | Cout |
13 - Measured value, short floating point value | Aout |
14 - Measured value, short floating point value with time tag | Aout |
15 - Integrated totals | Cout |
16 - Integrated totals with time tag | Cout |
20 - Packed single-point information with status change detection | Cout * |
21 - Measured value, normalized value without quality descriptor | Ai |
30 - Single-point information with time tag CP56Time2a | Dout |
31 - Double-point information with CP56Time2a tag | Dout,Cout |
32 - Step position information with CP56Time2a tag | Cout |
33 - Bitstring of 32 bits with CP56Time2a tag | Cout |
34 - Measured value, normalized value with CP56Time2a tag | Aout |
35 - Measured value, scaled value with CP56Time2a tag | Cout |
36 - Measured value, short floating point value with time tag CP56Time2a | Aout |
37 - Integrated totals with time tag CP56Time2a | Cout |
241 - 64-bit floating point value (Ipesoft & URAP implementation) | Ao |
243 - 64-bit floating point value with time tag CP56Time2a (Ipesoft & URAP implementation) | Ao |
251 - Archive data values (Ipesoft's implementation) | none ** |
252 - D2000 Unival (Ipesoft's implementation) | all |
...
Note: For setting individual bits of the quality byte (SIQ for ASDU 1,2,30; DIQ for ASDU 3,4,31; QDS for ASDU 5..14,20,32..36), the flags FLA A (0.bit), FLB B (1.bit) .. FLH H (7.bit) are used.
For example:
- for ASDU 4: FLAA=DPI bit 0, FLBB=DPI bit 1, FLCC=0, FLDD=0, FLEE=BL bit, FLFF=SB bit, FLGG=NT bit, FLHH=IV bit.
- for ASDU 16: FLAA..FLE E Sequence number bits 0..4, FLFF=CY bit, FLGG=CA bit, FLHH=IV bit
The exception is the bits, which are set directly by a value (e.g. for ASDU 1, the 0.bit is not set by the FLA A flag but by the value of output I/O tag).
If the Invalid attribute is set for a new value, the highest bit (IV) will be set in the status byte of for all ASDUs (except for ASDU 21, which does not have a status byte).
...
The following ASDU types in the direction of control are implemented (from the control station to D2000, also the opposite direction in balanced mode):
Kotva | ||||
---|---|---|---|---|
|
ASDU type | I/O tag type |
---|---|
45 - Single command | Di, Qi |
46 - Double command | Qi |
47 - Regulating step command | Di, Qi |
48 - Set point command, normalised value | Ai |
49 - Set point command, scaled value | Ci |
50 - Set point command, short floating point value | Ai |
51 - Bitstring of 32 bit | Ci |
58 - Single command with time tag CP56Time2a | Di, Qi |
59 - Double command with time tag CP56Time2a | Qi |
60 - Regulating step command with time tag CP56Time2a | Di, Qi |
61 - Set point command, normalised value with time tag CP56Time2a | Ai |
62 - Set point command, scaled value with time tag CP56Time2a | Ci |
63 - Set point command, short floating point value with time tag CP56Time2a | Ai |
64 - Bitstring of 32 bit with time tag CP56Time2a | Ci |
250 - Archive data request command (Ipesoft's implementation) | none ** |
252 - D2000 Unival (Ipesoft's implementation) | all (except Qi) |
...
Bits of "status" byte (SCO fro ASDU 45,58; DCO for ASDU 46,59; RCO for ASDU 47,60; QOS for ASDU 48..50,61..63) causes setting the FLA A (0.bit), FLB B (1.bit) .. FLH H (7.bit) flags with an exception for the bits which are directly set by the value of a variable (SCO bit 0, DCO and RCS bits 0-1). After receiving a response (positive/negative), the FLAA .. FLH H flags are set according to the bits of the "status" byte.
When writing values, the value of 6 [Activation] is expected as CauseOfTransmission. The response of the controlled station depends on the setting of the CMDC parameter. Originator ASDU address will be used the same as is in the received command.
...
- Communication line category: TCP/IP-TCP
- TCP Parameters
- Required to define the server parameters
- Host: string containing at most 80 characters – the name of the network interface in form of INET (name or numerical address a.b.c.d, e.g. 192.168.0.1) used for receiving clients by the D2000 KOM process. If the name is ALL or *, the D2000 KOM process will listen on all network interfaces of the computer, where is running.
- Port: TCP port number (0..65535), where the D2000 KOM process is listening.
- Line number: will be used as Originator ASDU address (1 byte, 0-255).
...
Note: Starting from D2000 version 7.02.004 the flags FLA A to FLP P of the value of the communication line are used for informing about connected active clients. An active client is a client who after establishing the connection sent U-frame StartDT Act, i.e. asked for sending the data. The first connected active client will cause a change of flag FLA A to TRUE, the second flag FLBB, etc up to flag FLP P and continuing again with the first flag FLAA. If the client sends the StopDT Act U-frame (requesting the server to stop sending data) or disconnects, the value of its flag will be changed to FALSE.
...
- Communication protocol: IEC870-TCP Server.
- The station address is a decimal number within the range 0...65535, it defines the ASDU address. It can be specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
Note 2: The protocol supports sending long time stamps (CP56Time2a tag) in local time or UTC time with defined offset (see the Use monotonic UTC time+ parameter).
...
The following parameters can be defined as station protocol parameters:
Table nr. 3Table 3
Keyword | Full name | Meaning | Unit | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|---|
| Command Confirm | Confirmation of control ASDU. If CMDC=0, the D2000 KOM process does not confirm any control ASDU from the partner station by replying with an ASDU with an appropriate CauseOfTransmission. If CMDC=1, the D2000 KOM process confirms control ASDUs with CauseOfTransmission=7 (Activation Confirmation). If CMDC=2, the D2000 KOM process confirms control ASDUs with CauseOfTransmission=10 (Activation Termination). If CMDC=3, the D2000 KOM process confirms control ASDUs with CauseOfTransmission=7 and CauseOfTransmission=10. | - | 1 | ||||||
D2CPA D2VCO | The parameters are intended for the configuration of a communication station for communication between two D2000 systems using ASDU 252 - D2000 Unival (Ipesoft's implementation). more ... | |||||||||
| D2000 64-bit Historical Values | When sending historical values (as an answer to a request for historical data), ASDU 249 will be used, which uses a 64-bit representation of floating points (the same as D2000 internally), instead of default ASDU 251 (which encodes the values as 32-bit floating points) to improve precision. Note: Before enabling this parameter, you should verify that also the client supports ASDU 249. This support was implemented in November 2011 for D2000 v8.00.011. | - | False | ||||||
| Debug Input | A mask for debug levels of input data. The meaning of bits is as follows:
| - | 0 | ||||||
| Debug Output | A mask for debug levels of output data. The meaning of bits is as follows:
| - | 0 | ||||||
| End of initialization | If EOI=0, the D2000 KOM process doesn't send ASDU 70 (End of initialisation). If EOI=1 and a client sends StartDT U-frame Act, the D2000 KOM process responds by StartDT Con and sends ASDU 70. | - | 0 | ||||||
| GI Send New | If GISN=True, then the D2000 KOM process after receiving the General Interrogation command sends also values with newer times than is the time when the command is received. The value of the GI Send New parameter must be True to send values with future times in a reply to the General Interrogation command. | - | False | ||||||
| Ignore Control Field 3 bit 0 | Determines behavior if ASDU contains Control Field with bit 0 (test) set in the 3rd byte (Receive).
| - | False | ||||||
| Ignore Invalids on Interrogation | If this parameter is set on a station, the D2000 KOM process will not send values of I/O tags which are Invalid or Unknown, in a reply for ASDU 100 and 101 (Interrogation/Counter interrogation commands). The parameter can be used e.g. for control applications - if sending Invalid values causes problems in control. | - | False | ||||||
| Ignore Tests | Determines behavior if ASDU contains the highest 7th bit (Test) set in CauseOfTransmission.
| - | 0 | ||||||
| Ignore Unknown Addresses | If IUA=TRUE, the D2000 KOM processD2000 Komwill process will not show an error on its console or write it into log files in case that incoming value has the address not matching any of the addresses of I/O tags defined in the D2000 system. | - | False | ||||||
| Implicit Interrogation | Balanced mode: After connecting the client, the values of all variables are automatically sent without any need for ASDU 100 and 101 [Interrogation/Counter Interrogation Command] requests. | - | False | ||||||
| Interrogation Covers Counter Interrogation | As a reply to Interrogation, ASDUs 15,16,37 (Integrated Totals) will be also sent, which are by default requested by ASDU 101 [Counter Interrogation]. | - | False | ||||||
| Interrogation Groups Objects | Optimization of sending values during General Interrogation (answer to Interrogation Command/Counter Interrogation Command). If IGO=True, multiple values will be sent inside a single ASDU (so that the length of ASDU is within maximum defined by the standard - 253 Bytes). This parameter does not influence change-based sending of values during normal communication. | - | False | ||||||
| Interrogation WithOut Timestamps | If Interrogation WithOut Timestamp=True then values sent as a response to ASDU 100 [Interrogation Command] will be sent as ASDUs without timestamps. For example instead of ASDU 2 (Single-point information with time tag) or ASDU 30 (Single-point information with time tag CP56Time2a) ASDU 1 (Single-point information) will be sent. This behavior is suitable in a situation when the values have been invalidated as a result of communication error and, after the communication is re-established, the values come with old timestamps which causes problems in the D2000 Archive (if the values change only rarely, calculated historical values depending on them will be also invalid till a new value arrives). At the same time, this behavior is strictly according to the IEC standard, which says that the response to Interrogation should not use ASDUs with time stamps. | - | False | ||||||
| K | Sending window size i.e. packet quantity, which is sent by the D2000 KOM process without receiving a confirmation (S-frame or I-frame). According to the standard, the default value is 12. | - | 12 | ||||||
| Maximum Clients | The maximum number of connected clients. The parameter is needed for D2000 OpenVMS, where a task pool containing 2 * MC tasks for client handling (one task for receiving data, one task for sending data) is created during KOM startup. If the value of the Maximum Clients parameter is equal to 0, the number of clients is not limited and threads are created dynamically as needed. | - | 0 | ||||||
| No Flags | If the value of the parameter is True, then the status byte of incoming ASDUs is ignored and not saved into the FAA .. .FH H flags. Flags of output I/O tags are also ignored and they don't influence the status byte. | - | False | ||||||
| Order of Counter IC | Balanced mode: Order of sending of ASDU 101 [Counter Interrogation Command] when initializing the connection. If OCIC<OIC, then ASDU 101 is sent before ASDU 100. If OCIC= 0, ASDU 101 is not sent. The parameter can be defined for each of the stations. | - | 0 | ||||||
| Order of IC | Balanced mode: Order of sending of ASDU 100 [Interrogation Command] when initializing the connection. If OIC<OCIC, then ASDU 100 is sent before ASDU 101. If OIC= 0, ASDU 100 is not sent. The parameter can be defined for each of the stations. | - | 0 | ||||||
| Pessimistic Write | Defines the evaluation of writing success in case of a connection of more than one client. If PW=0, writing a value is considered to be successful if at least one client confirms it (confirmation method is defined by the CMDC parameter). If PW=1, writing must be confirmed by all connected clients. If at least one client doesn't confirm it (e.g. connection failure occurs or the confirmation is negative), writing is considered to be unsuccessful. | - | 0 | ||||||
| Send sequence number | The initial Send sequence number after the TCP connection is established. According to the standard, having established the connection the Send sequence number is set to 0, other than zero could be appropriate e.g. for testing. | - | 0 | ||||||
| Standby Keep Open | If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), connections with clients will not be closed, and listening for new clients will not be aborted. | - | False | ||||||
| Standby Set Control Field | If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), the lowest bit of the 3rd Control Field byte of information APDUs (APDU containing data or commands) will be set to 1 instead of the standard value of 0. The behavior does not strictly follow the standard and we recommend using the Standby Set Test Bit parameter instead of this parameter if it is possible. | - | False | ||||||
| Standby Set Test Bit | If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), the Test bit will be set in Cause Of Transmission. | - | False | ||||||
| Standby Write Values | If True, after changing the status of the D2000 Server process (the D2000 KOM process is connected to) from Hot to Standby state (in a redundant system), the server will send new values to clients. | - | False | ||||||
| W | The number of received I-frames, after which the D2000 KOM process sends an S-frame confirmation. According to the standard, the default value is 8. The relation W < K must be true, the standard recommends W = 2/3 * K. | - | 8 | ||||||
| Wait Timeout T1 | Timeout for receiving the confirmation of a sent I-frame (either confirmation within the I-frame or the S-frame itself) or a U-frame. If the D2000 KOM process does not receive the confirmation within Wait Timeout T1 time, it closes the TCP connection. According to the standard, the Wait Timeout T1 default value is 15000 ms | ms | 15 000 | ||||||
| Wait Timeout T2 | Timeout for sending the confirmation of a received I-frame. Wait Timeout T2 < Wait Timeout T1. If another I-frame (which confirms the received I-frame) is not sent within Wait Timeout T2 time since the I-frame was received, the D2000 KOM process sends an S-frame confirming the received I-frame to the partner. According to the standard, the Wait Timeout T2 default value is 10000 ms. | ms | 10 000 | ||||||
| Wait Timeout T3 | Timeout for sending test frames ( TEST ACT U-frame). If no data are sent in any direction for a long time, a TEST ACT U-frame will be sent after the expiration of the Wait Timeout T3 time by the D2000 KOM process, and a TEST CON U-frame is expected (within Wait Timeout T1 time after sending). If the Wait Timeout T3 on the partner side is set to a lower value, it sends the test frames, and the D2000 KOM process replies to them. According to the standard, the Wait Timeout T2 default value is 20000 ms. | ms | 20 000 | ||||||
| Wait Timeout No answer | Balanced mode: Timeout for receiving the confirmation of a sent value in a control direction (ASDUs 45 - 64). Receiving e.g. S-frame with RSN (Receive Sequence Number) confirming, that the other party received the previous I-frame doesn't mean, that the I-frame was processed. Within the Wait Timeout No answer time interval, the D2000 KOM process waits for receiving the response (e.g. after sending ASDU with TypeIdentificator=45 [Single Command] with CauseOfTransmission=6 [Activation], the receiving of Single Command with CauseOfTransmission=7 [Activation Confirmation] is expected. After the expiration of the Wait Timeout Tn, the D2000 KOM process closes the TCP connection. | ms | 60 000 |
...
If a keyword with an invalid value in the initialization string is found, a corresponding default value according to the table Table 3 will be used. Defined parameters, except for OIC, OCIC and FST are valid for the entire line - i.e. it is enough to define them for one station on the line.
...
- I/O tag address is mapped to the Information object address, i.e. it has 3 bytes and must within the range of 0..16777215. It can be specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
The I/O tag with an address starting with %IGNORE will be ignored. - Input tags must be of particular types (Input tags must be of particular types (Ai, Ci, Di, Qi) for received ASDU, see Table 1.
- For a particular type of output tag (Ao, Dout, Co), it is necessary to set an ASDU type, that has to be used, see Table 2 and also Table 1 in the balanced mode.
- Archive for providing old values: if the client requires archive values using ASDU 250, the server sends:
- the values of the historical value specified by this input entry field,
- if the input entry field is not filled, then the values of the historical value that archives the I/O tag,
- if the specified historical value does not exist, then the values of the I/O tag that archives the control object of the specified I/O tag,
- if the control object does not exist (or the archive is not available), the server returns an error.
Browse
...
- If the Destination Column is configured, then the values received from the address configured at the I/O tag and above are stored in the corresponding items (e.g. objects with addresses 10, 11, 12 ... according to the number of rows of the destination structure).
Browse
For the I/O tags, it is possible to discover the list of tags, it is possible to discover the list of objects, as long as the KOM process is running and communication with a station is established.
Clicking the Browse button opens the IEC870-TCPSRV Item Browser window and displays a list of objects that have been read so far. The object list is created dynamically as a result of received messages.
...
Kotva | ||||
---|---|---|---|---|
|
...
Info | ||
---|---|---|
| ||
See an example of communication for the IEC 870-5-104 protocol, which contains the configuration of the IEC 870-5-104 client and server. |
Info | ||
---|---|---|
| ||
You can read a blog about the IEC 870-5-104 protocol: |
Kotva | ||||
---|---|---|---|---|
|
...
- Ver. 1.0 – February 5th, 2004
- Ver. 1.1 – December 1st, 2004: extension - support of balanced mode
- Ver. 1.2 – June 15th, 2020: browsing support
- Ver. 1.3 – November 16th, 2023 (support for the Destination Column)
Info | ||
---|---|---|
| ||
...