%EcoAve function
Old name
%EcoAveR
Function
The function returns the average of the specified object's values in an elapsed time period (given by the parameter
ResetTrigger
) according to the methodology based on flags of individual values entering the calculation. The result is a real value. Eval tag An eval tag must be evaluated on a change (Evaluation method parameter set to On change parameter value). Function value occurrence evaluation time is rounded to a minute, i.e. second seconds and milliseconds = 0. Declaration
Blok kódu | ||||
---|---|---|---|---|
| ||||
REAL %EcoAve( REAL in Arg, REAL in ValidCriterion, BOOL in ResetTrigger ) |
Parameters
Arg |
A parameter, average of which |
is to be calculated. | |
ValidCriterion | Validation criterion value [%]. |
Impulse | Change of the parameter into the TRUE state causes evaluating the average, |
which is to be assigned to the eval tag value. At the same time, input values for the next period of time (Arg) are to be processed. |
Note
Flag type | Flag name | Meaning | Description for ESC Datalogger |
CF | A | Measurement invalidity | < |
B | Unsteady operation | F | |
VF | C | Calibration | C |
D | Malfunction | B | |
E | Maintenance | M | |
F | Power supply failure | P | |
G | Disabled – disable (switching stopped) | D | |
H | Missing measurement |
TF | I | Layoff | F |
J | Start |
K | Putting out of operation |
L | Fuel change (unsteady process) |
M | Desulphurization failure |
N | Reserve |
IF | O | Reserve - fuel type - coal |
P | Reserve |
Types of flags for Automated measurement systemsystems:
- CF - complex flags (input attributes of value validity)
- VF- validated flags (input attributes for measurement validity) - they condition A flag
- TF- technological flags (input attributes of operation status) - they condition B flag
- IF- informative flags
The value is valid if the A flag is not set, i.e. A=FALSE. The operation is stabilized if the B flag is not set, i.e. B=FALSE.
The following validation criteria are applied on CF flags of processed values:
- Flag A Resultant value of the flag is TRUE, if the sample count containing at least one of VF flags (with TRUE value), is bigger than 100 -
ValidKriterium
ValidCriterion
(%) of all measurements in specific a specified time period. - Flag B Resultant value of the flag is TRUE, if the sample count containing at least one of TF flags (with TRUE value), is bigger than 100 -
ValidKriterium
ValidCriterion
(%) of all measurements in specific sa pecified time period.
Condition of flags processing:
- Value with set at least one of VF flags is not included into average but a flag counter is added into it.
- The processed values should have time with step of maximum 10 sec. If the value is missed during more than 10 seconds, the flag count „D“ - the counter for invalid measurements, is incremented.
- If the resultant flag „A“ is „A“ TRUE, all flags that appeared in time period, are included in VF flags of calculated average.
- If the resultant flag „A“ is „A“ FALSE, all VF flags are FALSE, even if some of them appeared in the processed data.
- If the resultant flag „B“ is „B“ TRUE, all flags that appeared in time period, are included TF flags of calculated average.
- If the resultant flag „B“ is „B“ FALSE, all TF flags are FALSE, even if some of them appeared in the processed data.