- Communication line category: Serial, SerialOverUDP Device Redundant, TCP/IP-UDP.
- Parameters of the serial line:
- Baud rate - 1200 Baud
- No parity, 8 data bits, 1 stop bit
- Parameters of UDP line:
- Host: IP address of the controller
- Port: UDP port of the controller where requests are sent.
Note: The parameters of the backup server (Host and Port) are not used in this protocol.
Kotva |
---|
| komunikacna_stanica |
---|
| komunikacna_stanica |
---|
|
Communication station configuration
...
- Communication protocol: Remia E3.
- Station The station address is set according to the address on a device (0 to 15) specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #6A).
Station protocol parameters
Configuration dialog The configuration dialog box of station - the tab "Protocol parameters".
Table 1
Key wordKeyword | Full name | Meaning | Unit | Default value |
---|
| Retry Count |
Number of retry calls when an error in communication occursMaximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error. | - | 2 |
| Retry Timeout |
Delay between the retry calls if an error in communication occursTimeout before resending a request if no response has been received. | ms | 100 |
millisec.First waiting on the response after sending a callThe delay after sending the request and before reading the response. | ms | 100 |
millisec.Delay The delay between the response readings |
of a response until it is completed millisec.Number of retry The maximum number of retries of the response reading |
until it is completed I/O tag configuration
...
I/O tag types: Ai, Ci, Co, Di, TiA, TiR.
The address is a number in the range from 0 to 300 (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A).
The meaning of the addresses is stated in the Table 2:
Table 2
Value type | Address | Description | Read/Write |
---|
Ai |
---|
Ai | 0 | Instantaneous power. | R |
Ai | 1 | Average power. | R |
Ai | 2 | Peak VT. | R |
Ai | 3 | Peak NT. | R |
Ai | 4 | Measurement 1 (main) - the last 1/4 hour (see Note). | R |
Ai | 5 | Measurement 2 (secondary) - the last 1/4 hour (see Note). | R |
Ci |
---|
Ci | 0 |
Number The number of electrometers. | R |
Ci | 1 |
Number The number of regulatory degrees. | R |
Ci | 2 |
Number The number of appliances. | R |
Ci | 3 | Regulatory degree. | R |
Ci | 4 | Tariff (0=VT, 1=NT). | R |
Ci | 5 | Current regulatory degree. | R |
Ci | 6 | Current average power (%). | R |
Co |
---|
Co | 0 | Regulated power VT. | R/W |
Co | 1 | Regulated power NT. | R/W |
Di |
---|
Di | 0 až 7 | Type of electro meter (FALSE=active power [kW], TRUE=reactive power [kVAr]). | R |
Di | 100 až 164 | Appliances (FALSE=idle state, TRUE=control state). | R |
Di | 200 až 264 | Status signal (FALSE=inactive, TRUE=active). | R |
TiR |
---|
TiR | 0 |
Time The time within a 15-minute interval. | R |
TiA |
---|
TiA | 0 | Date and time of initialization. | R |
TiA | 1 | Date and time of power failure. | R |
TiA | 2 | Date and time of the configuration change. | R |
TiA | 3 | Date and time of the last reset. | R |
TiA | 4 | Current date and time. | R |
TiA | 5 | Time to reach peak VT. | R |
TiA | 6 | Time to reach peak NT. | R |
TiA | 7 | Time of the last quarter-hour. | R |
Note: You can obtain also the values from an archive of
the device
per for the current and previous month for both the main and secondary measurement. The reading of archive values may be started in the station dialog box or by
Tell the GETOLDVAL Tell command
GETOLDVAL.