This protocol supports data reading from the dataloggers INMAT 64 and INMAT 65 dataloggers produced by ZPA Nová Paka (Czech republic).
...
- Communication line category: Serial, SerialOverUDP Device Redundant, RFC2217 Client.
- Parameters of the asynchronous line: 300 Baud, 8 data bits, no parity, 2 stop bits.
Note:
A device sends data spontaneously (without the request for data). A delay between the transmitted data blocks is 5 seconds.
Kotva | ||||
---|---|---|---|---|
|
...
- Communication protocol: ZPA INMAT 64/65.
- The station address is not used. On one serial line, there may be placed only one INMAT 64 or 65 can be connected.
Station protocol parameters
...
Kotva | ||||
---|---|---|---|---|
|
...
I/O tags: Ai
The address can be entered as a decimal number or a hexadecimal number with a hash at the beginning (e.g. #A).
The value meaning:
Address | Cycle | Meaning | Units |
---|---|---|---|
0 | 1 | Heat output | GJ/hour |
1 | 1 | 1/4 hourly maximum | GJ |
2 | 1 | Heat output sum | GJ |
3 | 1 | Instantaneous mass flow rate | t/hour |
4 | 1 | Mass flow rate sum | t |
5 | 1 | Temperature | °C |
6 | 1 | Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65 | - |
7 | 2 | Heat output | GJ/hour |
8 | 2 | 1/4 hourly maximum | GJ |
9 | 2 | Heat output sum | GJ |
10 | 2 | Instantaneous mass flow rate | t/hour |
11 | 2 | Mass flow rate sum | t |
12 | 2 | Temperature | °C |
13 | 2 | Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65 | - |