GETOLDVAL action
Function
Reading of values from the archive of the substation.
Declaration
Blok kódu | ||||
---|---|---|---|---|
| ||||
GETOLDVAL statIdent, fromTimeIdent_TmA, endTimeIdent_TmA, retIdent_Int, archIdent [MASK mask_txt] |
or
Blok kódu | ||||
---|---|---|---|---|
| ||||
GETOLDVAL statIdent, fromTimeIdent_TmA, endTimeIdent_TmA, retIdent_Int NOWAIT [MASK mask_txt] |
Parameters
statIdent | in | Reference to a Station type |
object. | ||
fromTimeIdent_TmA | in | Identifier of the AbsTime type - begin time for reading from the archive. |
endTimeIdent_TmA | in | Identifier of the AbsTime type - end time for reading from the archive. |
retIdent_Int | out | Return code identifier of the Int type. |
archIdent | in | Reference to a Process type object (archive). |
NOWAIT | in |
Keyword. If it is not entered, the action waits synchronously for the termination of data reading. | |
MASK | in |
Keyword. | ||
mask_txt | in | Identifier of Text type - text string that consists of a mask formed from the names of I/O tags for which the values are to be read. |
Description
The action will start the backward reading of values from the archive of a station. Time interval is given by the identifiers
fromTimeIdent_TmA
and endTimeIdent_TmA
. Return code (retIdent_Int
) gains one of the following values:- _ERR_TRANS_ABORT
- _ERR_TRANS_ERROR
- _ERR_TRANS_IGNORED
- _ERR_NO_ERROR
In case of the first declaration, the action waits for the termination of the reading and archiving of values, if these are archived. In this case it is necessary to archive all I/O tags in one archive. An archive is represented by the identifier archIdent
. The second declaration only starts the backward reading of values and doesn't wait for its termination. Return values is to be always _ERR_NO_ERROR.
If the key word keyword MASK and identifier mask_txt are defined, the action reads values only for those I/O tags that match the definition, which is entered in the identifier mask_txt. For example mask_txt := "M.RIADENIE*".
Note
If backward reading of communication station values is being performed, the flag A is set for the communication station value.