VONSCH VQfrem 400 protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Kotva
typy_verzie
typy_verzie
Supported device types and versions

...

Table 2 - quantities available for reading according to the documentation

AddressDescriptionMeaning
#0001Software version609h for ver. 6.09, (402h for ver. 4.02, 304h for ver. 3.04)

#0004

Voltage range190h for 400V, 191h for 400 ...M, 2b2h for 690V
#0025Freq. INV - the frequency of voltage on converter’s output (stator frequency) +/- XXX,XX Hz
#0026Revolves - output revolutions of the motor+/- XXXX rev/min
#0027Revol/i - evolutions behind gear/transmission+/- XXXX,X rev/min
#0028Freq.RT - rotor frequency (evaluated from speed encoder – IRC)+/- XX,XX Hz
#0029Freq.RF - required converter frequency+/- XX,XX Hz
#002A

MT Curr. - effective current value into the motor

XXX,X A
#002BR.torque - required mechanical motor torque +/- XXX,X Nm
#002CTorque - mechanical motor torque +/- XXX,X Nm
#002DMag. flux - rotor magnetic fluxX,XXX Wb
#002EVolt. MT - momentary motor supply voltage (100.0% responds to 400 V)XXX,X %
#002FVolt. DC - real voltage of converter’s unidirectional DC busXXX V
#0030Inp.pow. - momentary input power into the motorXXX,X kW
#0031

MT power - motor power

XXX,X kW
#0032kW hours - motor energy consumption in kWhXXXX kWh
#0033MW hours - motor energy consumption in MWhXXXX MWh
#0034Teplota chladiča meničaXX,X °C
#0035Temp.INV. - air temperature in the converterXX,X °C
#0036PR ref. - required value of process regulatorXX,X %
#0037PR real - feedback of process regulator (real value)XX,X %
#0038Inp. AIN1 - the value of analogue input AIN1 in % rangeXX,X %
#0039Inp. AIN2 - the value of analogue input AIN2 in % rangeXX,X %
#003AHodnota analógového vstupu 3 v % rozsahuXX,X %
#003B

BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). 

0=input is open
1=input is closed
#003C

RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4  (bits 8-10 from the received value - bit numbering is from 0 to 15). 

0=relay is open
1=relay is closed
#003DHours INV - converter operating time counterXXXX h
#003EHours MT - motor operating time counterXXXX h
#003FPos.ref. - required position in a case of „position“ variable+/- XXXX,X cm
#0040Position - real position+/- XXXX,X cm
#0041Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on+/- XXXX cm
#0042Deviation from zero position when calibrating the ARC position sensorXXXX d
#0043cos(fi ) - momentary value of motor power factor+/- X,XX
#0044See Warnings register 2-
#0045See Warnings register 1-
#0046

See Faults register

-
#0048
Okamžitá hodnota preťaženia
Overload - a momentary value of overloadXXX.X %
#0049
Servisná zobrazovaná veličina
Service SL - service displayed variable Slave+/- XXXX d
#004a
Servisná zobrazovaná veličina
Service MS - service displayed variable Master

+/- XXXX d

Všetky hodnoty sú prenášané ako All values are transmitted as 16-bitové čislabit numbers. KOM proces ich interpretuje ako znamienkové alebo kladné podľa adresy (znamienkové sú The KOM process interprets them as signed or positive by address
(signed are #0025-#0027, #002B, #002C, #003F-#0041, #0043, #0049- #004a#004a).

Pokiaľ je číslo desatinné, treba v konfigurácii meraného bodu v záložke Prevod zadať príslušný lineárny prevod (napr. koeficient If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g. coefficient A=0.1 pre #0030for #0030, A=0.01 pre #0028for #0028).

Kotva
register_poruch
register_poruch

...

Table  3 -

...

Faults register (values of the I/O tag with address #0045). If an arbitrary bit is set to logical 1, the corresponding fault/failure has arisen in the converter. 

BitMeaning
0Converter Overcurrent
1Converter Overload
2Converter Undervoltage
3Converter Overvoltage
4Motor Overheat
5Heatsink Temperature
6

Incorrect parameters of currents, motor constants, or speed

7Regulation error
8Identification error
9Output short circuit
10IRC failure
BitVýznam0Nadprúd meniča1Preťaženie meniča2Podpätie meniča3Prepätie meniča4Tepelný integrál motora5Teplota chladiča6

Nekorektné parametre prúdov, konštánt motora alebo rýchlosti

7Chyba regulácie8Chyba identifikácie9Skrat výstupov10Chyba snímača IRC
(ARC), RM-ARC
11
Prerušenie vstupnej alebo výstupnej fázy meniča

Input or Output phase loss

12
Externá porucha
External failure
13
Teplota v meniči
Temperature in inverter
14
Prerušenie
AIN1, AIN2
alebo
, or AIN3 disconnected
15
rezervované

reserved


Kotva
register_varovani1
register_varovani1

...

Table 4 - Warnings register

...

1 (values of the I/O tag with address #0045).

...

 If an arbitrary bit is set to logical 1, the converter generates a corresponding warning. 

Bit
Význam
Meaning
0
niektoré z varovaní W1

some warnings W1-W5:
W1 -

Menič znižuje magnetický tok motora pre dosiahnutie nadsynchrónnych otáčok
W2 - Počas odbudzovania klesol magn. tok na minimálnu hodnotu
W3 - Regulátor magnetického toku je v nasýtení (len vo vektorovom režime)
W4 - Regulátor momentu motora je v nasýtení (len vo vektorovom režime)
W5 - Regulátor rýchlosti je v nasýtení (len vo vektorovom režime)

 The converter reduces motor magnetic flux in order to achieve over-synchronous revolutions.
W2 - Magnetic flux has decreased to the minimal value at field suppression.
W3 - Regulator of magnetic flux is saturated (only in vector mode). 
W4 - Regulator of motor torque is saturated (only in vector mode).
W5 - Speed regulator is saturated (only in vector mode). 

1W6 - Motor cooler has reached an increased temperature (over 75 °C).
For VQFREM 400 005, 007, and 011 types, the module temperature is over 90 °C
2W7 - The converter switches itself into scalar mode due to IRC/ARC failure.
3W8 - Signalisation of reverse direction of IRC/ARC.
4F7 - The time needed for motor field suppression has not expired yet (before subsequent start).
5W12 - Process regulator is saturated. Converter frequency has reached its maximum value. 
6

F9 - Position calibration initiated by 9.4.3 command, or calibration of IRC encoder on the synchronous motor.
F10 - IRC zero pulse is being searched on the synchronous motor after the converter was connected to the power network and the START command was selected. 

7F11 - The speed decreased to zero by activating a software terminal switch. 
8F8 - Dynamic deceleration was activated as a result of a sharp decrease in speed.
9W16 - Sensored motor temperature has achieved nonpermissible value.
10W17 - If EWCP,(M),(I) panel is active (2.4.1)and the connection with the converter has failed.
11

F2 - Maximal current regulator

1W6 - Chladič meniča má zvýšenú teplotu (viac ako 75 °C).
Pri typoch VQFREM 400 005, 007 a 011 je teplota modulu vyššia ako 90 °C2W7 - Menič sa prepol do skalárneho režimu pri výpadku IRC,ARC3W8 - Signalizácia opačného napojenia IRC alebo ARC4F7 - Pred ďalším štartom ešte neuplynul čas potrebný pre odbudenie motora5W12 - Procesný regulátor je v nasýtení; frekvencia meniča je na maximálnej hodnote6

F9 - Prebieha kalibrácia polohy od povelu 9.4.3 alebo sa kalibruje IRC (ARC) snímač na synchrónnom motore

F10 -Prebieha hľadanie nulového impulzu IRC na synchrónnom motore po zapnutí meniča na sieť a povele ŠTART

7F11 - Rýchlosť bola znížená na nulu aktivovaním softvérového koncového spínača8F8 - Prudký pokles rýchlosti aktivoval funkciu dynamický dobeh9W16 - Snímaná teplota v motore dosiahla nepovolenú hodnotu10W17 - Ak je EOPN panel aktívny (2.4.1), a prerušilo sa spojenie s meničom11F2 - Aktivuje sa regulátor max. prúdu

(par.13.3.1)

a obmedzuje prúd na hodnotu par.

is active. It limits the current to the value of parameter 9.10.1

12F3 -
Menič je v režime kinetického zálohovania po výpadku elektrickej energie
 The converter is in kinetic backup mode after input power failure.
13F4 -
Prebieha nafázovanie meniča na roztočený motor
 The converter is processing the frequency for the spinning motor.
14F5 -
Prebieha parkovanie procesného regulátora
 Sleep function of process regulator.
15

F6 -

Brzdný modul je aktívny

 Braking unit is active.

Kotva
register_varovani2
register_varovani2

...

Table 5 - Warnings register

...

(

...

values of the I/O tag with address #0044). If an arbitrary bit is set to logical 1, the converter generates a corresponding warning. 

BitMeaning
0W23 - The converter recognized no load at output terminals

...

BitVýznam0W23 - Pri povele ŠTART menič zistil neprítomnosť záťaže na výstupných svorkách
U, V, W at START command. 
1F12 -
Je zopnutý koncový spínač 1 alebo koncový spínač 2
 Terminal switch 1 or terminal switch 2 is switched on.
2F13 -
Funkcia „brzdenie tokom“ zvyšuje budenie motora úmerne rozdielu
 The function „flux braking“ (8.3.1) increases motor excitation proportionally to UDC-UDCnom
3W9 -
Prerušenie vstupnej fázy meniča
 Converter input phase was interrupted 
4
rezervované
reserved
5F14 -
Prebieha OFF
 OFF-LINE
identifikácia niektorého z parametrov motora
identification of some motor parameters (Rs, Ls+Lm,
Upoč
Uinit).
6

W25 -

Teplota vzduchu v meniči je vyššia ako 70 °C

The air temperature in the converter is more than 70 °C. 

7
rezervované
reserved
8W18 -
Nastala chyba pri komunikácii po sériovej linke
 Serial communication error has occurred - RS232 (RS485)
9F16 -
Signalizuje, že Relé s funkciou „vypne, preťaženie“ práve rozoplo
It signalizes, that relay with the function „shut-down, overload“ has just been released.