The protocol allows reading data from multifunctional calorimetric counters of the VKP and VKPs CALMEX II types by means of the M-Bus bus (originally used RS232/M-Bus Premex RS-M convertorconverter, after 15 years replaced by converter RS232toMBus-XL45 from www.prevodniky.sk).

...

  • Communication line category: Serial (both convertorsconverters), SerialOverUDP Device Redundant (RS232toMBus-XL45 only).
  • Mode 1: Baud rate 300, 8 bit, 1 stop bit, even parity, RTS=1, DTR=1 (RTS and DTR signals are not used by RS232toMBus-XL45).

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: Premex CALMEX II
  • Station The station address is a decimal number within the range of 1..250 (or a hexadecimal number with a hash at the beginning, e.g. 250 #0A) – it is a VKP address. By default, the address is set by the manufacturer according to the serial number (identification number) of the measuring device as the last three digits. If the last three digits are greater than 250, the higher digit of them is not taken into account. If the serial number is one of the numbers of 000, 300, 400, 500, 600, 700, 800, 900 then must be changed.
  • Recommended polling parameters: Delay at least 1 minute.

...

The following station protocol parameters can be defined:

Table 1

KeywordFull nameMeaningUnitDefault value
Kotva
rc
rc
RC
Retry Count
Poll repetition
Maximum count
in case of a
of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.-2
seconds
Kotva
rt
rt
RT
Retry Timeout
Delay between poll repetition in case of a communication error
Timeout before resending a request if no response has been received.ms100 ms
Kotva
wt
wt
WT
Wait Timeout
Delay
The delay between the response readings
till its finalization
.ms500 ms
Kotva
wft
wft
WFT
Wait First Timeout
First waiting for response
The delay after sending the
poll
request and before reading the response.ms800 ms
Kotva
mwr
mwr
MWR
Max Wait Retry
Repetition count of response readings till its finalization
The maximum number of retries of the response reading.-40
Kotva
wul
wul
WUL
WakeUp LengthLength (given in characters) of a so-called wake-up message sent before each
poll
request.-20
Kotva
wud
wud
WUD
WakeUp Delay
Delay
The delay between wake-up message and
poll
a request. It is recommended to enable the option WaitTxEMPTY in the line mode configuration.ms400

String A string containing the protocol parameters is being defined as follows:

Keyword=value;Keyword=value; ...

Example:

RC=1;RT=500;

If there is used a keyword with an invalid value in the initialization string , there will be used is used, the corresponding default value according the to table 1 will be used.

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible I/O tag types: Ai, Ci, TiA

Address: It requires to enter one number, listed in the following tableA number from the following table must be entered (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A):

Table 2

AddressMeaningTypeUnits
1Measuring device ID.Ci-
2Access number (measurement number incremented by 1 for each data reading).Ci-
3Status number, bit descriptions see the table 3, individual bits are sent to the value attributes.Ci-
4Heat quantity.AiMJ,GJ,kWh,MWh
5Heat rate.AiW,kW,MW
6Volume overflow.Ail,m3
7Volume flow.Ail/h,m3/h
8Forward temperature.AiºC
9Return temperature.AiºC
10Measuring device date+time.TiA-
11Heat quantity on the 1st date.AiMJ,GJ,kWh,MWh
12Heat quantity on the 2nd date.AiMJ,GJ,kWh,MWh
13Volume overflow on the 1st date.Ail,m3
14Volume overflow on the 2nd date.Ail,m3
151st date of data.TiA-
162nd date of data.TiA-

Values saved on the 1st date or 2nd date are sent to the D2000 system with the save time of saving. Measuring The measuring unit of individual parameters depends on the measuring device type.

Meaning of status word bits (Ci address - 3)

Table 3

Bit numberMeaningValue attribute
0Always 0.A
10 - current value, 1 - stored value.B
2Low input power.C
3Constant error.D
4Temporary error.E
5Water-meter error.F
6Temperature pickups error.G
7Always 0.H

Kotva
literatura
literatura
Literature

...

Kotva
revizie
revizie
Document revisions

...

  • Ver. 1.0 - March 13th, 2001 – document creation.
  • Ver. 1.1 - 7. september September 2016 – support for SerialOverUDP Device Redundant line, information about RS232toMBus-XL45 convertor.

...