If the Init File line protocol parameter is specified for a line (at least one), then the My Station, COM Port, and COM Speed the protocol  protocol parameters will be ignored on all the stations. There will be used Instead, the configuration file on the disk (the path of which path is defined by the Init File line protocol parameter) will be used.
For further information on the file contents, see the ATOUCH32 online help.

Example: configuration file contents:

...

  • Kotva
    wid
    wid
    WID - the numerical name of the variable - it is a unique number within the DB-Net network. The permitted range is 0..65500, the value is assigned by the PSP3 tool or DetStudioThe number is specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #0A).
  • Kotva
    typ
    typ
    Type - value type of the variable - it can be the INT, LONG, FLOAT types, and the INT MATRIX, LONG MATRIX, or FLOAT MATRIX types. The INT and INT MATRIX types are 16 bit wide; and if they are configured as Ai/Ao value types, they are interpreted as signed numbers; and if they are configured as Ci/Co value types, they are interpreted as unsigned numbers.
    LONG and LONG MATRIX types (32 bit wide) configured as Ai/Ao value types are interpreted as signed numbers and if they are configured as Ci/Co value types, they are interpreted as unsigned numbers. The FLOAT and FLOAT MATRIX types are 32-bit float numbers within the range from ±10-36 to ±1038. DBNETTIME is LONG type interpreted as absolute time in DBNet format (number of seconds from 1-1-1980 0:0:0). INT MATRIX value type can be set for value types of TxtI and TxtO. Then the row from the INT matrix is interpreted as text, each INT element of the matrix represents one character. INT and LONG types can be represented as relative time - i.e. a number of seconds.

...

Error:DB-Net Station Address Error - 'StationName', Address : 'StationAddress'
Solution:Invalid station address - check the Address tab in the communication station configuration dialog box (in the D2000 CNF process) and eventually save the station configuration and restart the D2000 KOM process.
Error:DB-Net Point Address Error - 'PointName', Address : 'PointAddress'
Solution:Invalid I/O tag address - check the Address tab in the I/O tag configuration dialog box (in the D2000 CNF process) and eventually save the I/O tag configuration.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromStringA
Solution:Error when calling the ATOUCH32 function AtchInitFromStringA - check the station configuration and protocol parameters. During the start, the D2000 KOM process displays the configuration string (the communication tracing level at least Monitor must be enabled) - please check if it corresponds to your requirements.
Error:DB-Net ERROR - CreateSemaphore - ErrNr - Error description
Solution:System error of Windows API call. Restart the operating system.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchReqGetVariable
DB-Net ATOUCH32 ERROR - 0xXY - AtchReqPutVariable
Solution:Error when calling the ATOUCH32 functions AtchReqGetVariable or AtchReqGetVariable for reading/writing a DB-Net database variable value. Previous communication tracing logs allow us to detect which I/O tag is in troubles trouble and then its configuration can be checked.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=0 !
DB-Net ERROR - Reading 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Reading 'PointName' - TNRES=Invalid !
DB-Net ERROR - Writing 'PointName' - TNRES=0 !
DB-Net ERROR - Writing 'PointName' - TNRES=1 (reading on progress) !
DB-Net ERROR - Writing 'PointName' - TNRES=Invalid !
Solution:Transaction errors of reading/writing the DB-Net database variable. They should not occur.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=4 (station not responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station not responded) !
Solution:Transaction errors of reading/writing the DB-Net database variable. The station doesn't respond because it is switched off, there is a problem with the communication wire or a configuration error (e.g. wrong baud rate, address or port). The error could occur sporadically, especially at reading.
Error:DB-Net ERROR - Reading 'PointName' - TNRES=4 (station responded) !
DB-Net ERROR - Writing 'PointName' - TNRES=4 (station responded) !
Solution:Transaction errors of reading/writing the DB-Net database variable. The station responded with an error. Probably it is an attempt to read or write a variable, which does not exist in a device. Check the configuration of the corresponding I/O tag and compare it with the log from the AMiT PSP3 software tool.
Error:DB-Net ATOUCH32 ERROR - 0xXY - AtchInitFromFileA
Solution:Error when calling the ATOUCH32 function AtchInitFromFileA. Check if the protocol parameter INIFILE is configured just for one station and its value is a name of an existing file on a disk.

...