AddressI/O tag typeDescription
LOCK_REMOTEDi, Dout

Get/set the remote controller functionality: Lock (1) / Unlock (0).

OPERATE_OUTPUTDi, Dout

Get/set the device functionality: the device is stopped (0) / working (1).

OPERATE_DHWDi, Dout

Get/set the domestic hot water heating in the built-in boiler: disabled (0) / enabled (1).

OPERATE_MODEAi, Ao

Get/set the mode of operation: 0=cooling, 1=dehumidification, 2=ventilation, 3=auto, 4=heating.
Note: for a heat pump, modes 0, 3, 4 are relevant.

TEMP_OUTPUT_SPAi, Ao

Get/set the desired outlet water temperature.

TEMP_DHW_SPAi, Ao

Get/set the desired temperature of the domestic water in the built-in boiler.

TEMP_WATER_INAiCurrent inlet water temperature.
TEMP_WATER_OUTAiCurrent outlet water temperature.
TEMP_ROOMAi

Current room temperature (external sensor connectable to the indoor heat pump unit).

TEMP_TANKAiCurrent The current temperature of the domestic water in the built-in boiler.
TEMP_SOLARAiCurrent The current temperature of an optional external solar system (if connected).
CONNECTED_IDUDiThe indoor unit is connected (1) or disconnected (0).
TGT_TEMP_SELDi

Current The current setpoint is the temperature of air TEMP_ROOM (0) or water TEMP_OUTPUT_SP (1).

...