Supported device types and versions 
Communication line configuration
Communication line station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

...

The protocol supports the communication with devices ELCOR-2 and microELCOR-2 (made by company ELGAS) that recalculate a gas quantity.

...

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • Communication protocol: Elcor ELGAS-2 (CP II).
  • Station address:

Node address: value in the range of 0 to 65535.

...

Configuration dialog box  - tab „Parameters".
They influence some optional parameters of protocol. Following station protocol parameters can be set:

Table 1

Full nameMeaningUnitDefault value
Kotva
devt
devt
Device Type
Selection of device type.ELCOR-2 or microELCOR-2ELCOR-2
Kotva
rc
rc
Retry Count
Delay between request retry in case of a communication failure.
 

3
Kotva
wft
wft
Wait First Timeout
Delay after sending the request before reading the response.ms100 ms
Kotva
wt
wt
Wait Timeout
Delay between response readings till its completing.ms100 ms
Kotva
mwr
mwr
Max. Wait Retry
Retry count of response reading till its completing.
 

30
Kotva
srdtm
srdtm
Static Data Read Period
Static - configuration data read period (only microELCOR-2).min60 min
Kotva
hardp
hardp
Hourly Archive Periodic Reading
A period for reading value of hourly archives (0-60 min). Value 0 disables the reading.min0 min
Kotva
wusl
wusl
Wake Up Sequence Length
Length 'wake-up' of data which is entered before the call after longer communication pause.0 .. 50 bytes25 bytes
Kotva
wueq
wueq
Wake Up Each Query
Insert 'wake-up' data before each query.YES/NONO
Kotva
wuch
wuch
Wake Up Character
Form 'wake-up' data sequence from the characters that has this value.0 .. 255255
Kotva
ga
ga
Group Source Address
Group source address (address of D2000 KOM process).0 .. 655350
Kotva
sa
sa
Source Address
Source address (address of D2000 KOM process).0 .. 2550
Full DebugHigh level of communication tracking, the loaded values of I/O tags and other debug information are shown.YES/NONO

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible value types of I/O tags: Di, Ai, Ci, TxtI, TiA.

Device ELCOR-2

Table 2 contains the list of main parameters of device.
Tables 3 to 8 contains the list of variable configuration and informative data according to parameter type. DESC(ind) parameter represents the common data of all parameters. It describes the quantity. The current value of quantity can be acquired by configuration of the I/O tag with numerical address - index ind (number from 1 and more). To find out the technical units - configure text of I/O tag with address UNIT(ind).


Table 2 - Device parameters - Main device parameters

Object descriptionValue typeAddressUnits
Serial number of deviceCi, TxtISN
 

Referential temperatureAiTB°C
Referential pressureAiPBkPa
Firmware versionTxtIFW
 

Station nameTxtIDESC
 

CO2 concentrationAiTAB(0)%
N2 concentrationAiTAB(1)%
Heat of combustionAiTAB(2)MJ/m3
Relative densityAiTAB(3)
 

H2 concentrationAiTAB(4)%
H2S concentrationAiTAB(5)%
He concentrationAiTAB(6)%
H2O concentrationAiTAB(7)%
O2 concentrationAiTAB(8)%
Ar concentrationAiTAB(9)%
CO concentrationAiTAB(10)%
C1H4 concentrationAiTAB(11)%
C2H6 concentrationAiTAB(12)%
C3H8 concentrationAiTAB(13)%
iC4H10 concentrationAiTAB(14)%
nC4H10 concentrationAiTAB(15)%
iC5H2 concentrationAiTAB(16)%
nC5H2 concentrationAiTAB(17)%
C6H14 concentrationAiTAB(18)%
C7H16 concentrationAiTAB(19)%
C8H18 concentrationAiTAB(20)%
C9H20 concentrationAiTAB(21)%
C10H22 concentrationAiTAB(22)%

Table 3 - Device parameters - Analogue parameter

Object descriptionValue typeAddressUnits
Analogue parameter - transducer serial No.TxtI, CiSN(ind)
 

Analogue parameter - upper limit of measuring rangeAiHL(ind)
 

Analogue parameter - lower limit of measuring rangeAiLL(ind)
 

Analogue parameter - technical unitsTxtIUNIT(ind)
 

Analogue parameter - nameTxtIDESC(ind)
 

Table 4 - Device parameters - Counter

Object descriptionValue typeAddressUnits
Counter - serial number of gas meterTxtI, CiSN(ind)
 

Counter - technical unitsTxtIUNIT(ind)
 

Counter - nameTxtIDESC(ind)
 

Table 5 - Device parameters - Error counter

Object descriptionValue typeAddressUnits
Error counter - primary counter numberTxtI, CiCNT(ind)
 

Error counter - technical unitsTxtIUNIT(ind)
 

Error counter - nameTxtIDESC(ind)
 

Table 6 - Device parameters - Standard counter

Object descriptionValue typeAddressUnits
Standard counter - primary counter numberTxtI, CiCNT(ind)
 

Standard counter - calculation numberTxtI, CiCLC(ind)
 

Standard counter - technical unitsTxtIUNIT(ind)
 

Standard counter - nameTxtIDESC(ind)
 

Table 7 - Device parameters - Conversion factor

Object descriptionValue typeAddressUnits
Conversion factor - analogue (pressure) numberCiCNTP(ind)
 

Conversion factor - analogue (temperature) numberCiCNTT(ind)
 

Conversion factor - pressure error volumeAiDEFVALP(ind)kPa
Conversion factor - temperature error volumeAiDEFVALT(ind)°C
Conversion factor - compressibility error volumeAiDEFVALK(ind)
 

Conversion factor - technical unitsTxtIUNIT(ind)
 

Conversion factor - nameTxtIDESC(ind)
 

Table 8 - Device parameters - Standard flow rate

Object descriptionValue typeAddressUnits
Standard flow rate - primary flow numberCiCNT(ind)
 

Standard flow rate - calculation numberCiCLC(ind)
 

Standard flow rate - technical unitsTxtIUNIT(ind)
 

Standard flow rate - nameTxtIDESC(ind)
 


Device microELCOR-2

Address of I/O tag can be data from column "Address" or "Default address".

Table 9 - Actual values

Object descriptionValue typeAddressDefault addressUnits
Primary volumeAiOH.1Vm3
Standard volumeAiOH.2VNNm3
Error primary volumeAiOH.3VESTm3
Error standard volumeAiOH.4VNESTNm3
Primary flow rateAiOH.5Qm3/hour
Standard flow rateAiOH.6QNNm3/hour
Compressibility ratioAiOH.7K
 

Actual pressureAiOH.8PkPa
Actual temperatureAiOH.9TK
Calculation numberAiOH.10Z
 

Device temperatureAiOH.11TPR°C
Operating value - rest (only in VF input)AiOH.12VZB
 

Table 10 - Service data

Object descriptionValue typeAddressDefault addressUnits
Type + serial numberTxtISE.1VCE
 

Serial number of temperature sensorTxtISE.2VCT
 

Serial number of pressure transducerTxtISE.3VCP
 

Version SW+HWTxtISE.4VER
 

Customer numberTxtISE.5CZ
 

Serial number of gas meterTxtISE.6PVC
 

Network addressTxtISE.7ADR
 

Constant of gas meterCiSE.8KP0=1, 1=0.1, 2=0.01, 6=100, 7=10
Measuring intervalCiSE.9IM
 

Interval of data sending through serial lineCiSE.10IV
 

Start hour of gas dayCiSE.11CD
 

Start of measurementTiASE.12DSM
 

Date and time of deviceTiASE.13DAT
 

Battery capacityCiSE.14BAT%
Actual statusTxtISE.15OS
 

Configuration bytesTxtISE.16KB
 

Communication rate of serial numberCiSE.17RK4=4800, 5=9600, 6=19200
CRC 51CiSE.18C1
 

CRC MSP 430CiSE.19C2
 

CRC EEPROM1CiSE.20C3
 

CRC EEPROM2CiSE.21C4
 

CRC EEPROM3CiSE.22C5
 

Battery voltageAiSE.23UPRHEXV
Display configurationCiSE.24KDIS
 

Bits of permission to write the itemsTxtISE.25W_RUN
 

Customer's regionTxtISE.26REGION
 

Saving interval in hourly archiveCiSE.27IU
 

Quantity of diff. pulses between IMP and IMP1CiSE.28IMP1_PI0=off, 255=on permanently
Input pulse ratioCiSE.32I_V_DP
 

Bits of record permission in RUN by a userCiSE.33WU_RUN
 

Actual status 2CiSE.34OS2
 

Setting of pulse ratio of gas meter VF on m3CiSE.35KPVF
 

Table 11 - Parameters

Object descriptionValue typeAddressDefault addressUnits
Base pressureAiPA.1PNkPa
Base temperatureAiPA.2PT°C
Default pressureAiPA.3PESTkPa
Default temperatureAiPA.4TEST°C
Default compressibility levelAiPA.5SK
 

Min. pressure limitAiPA.6PMINkPa
Max. pressure limitAiPA.7PMAXkPa
Min. temperature limitAiPA.8TMIN°C
Max. temperature limitAiPA.9TMAX°C
Limit of max. flow rateAiPA.10QMAXm3/hour
Method of compressibility calculationCiPA.11MK
 

CO2 concentrationAiPA.12KCO2%
N2 concentrationAiPA.13KN2%
H2 concentrationAiPA.14KH2%
Relative densityAiPA.15KD%
Heat of combustionAiPA.16KHONkWh/m3

Table 12 - Minima/maxima

Object descriptionValue typeAddressDefault addressTechnical units
Pressure under rangeAiMI.1PMMINkPa
Time of pressure under rangeTiAMI.2DPMMIN
 

Pressure above rangeAiMI.3PMMAXkPa
Time of pressure above rangeTiAMI.4DPMMAX
 

Temperature under rangeAiMI.5TMMIN°C
Time of temperature under rangeTiAMI.6DTMMIN
 

Temperature above rangeAiMI.7TMMAX°C
Time of temperature above rangeTiAMI.8DTMMAX
 

Flow rate above rangeAiMI.9QMMAXm3/hour
Time of flow rate above rangeTiAMI.10DQMMAX
 

Time of reset time (minima/maxima)TiAMI.11DNUL
 

Parameters and minima/maxima are read in period which is set in protocol parameter value Static Data Read Period.

...