Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

Advantech ADAM 5000 DeviceNet communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Kotva
typy_verzie
typy_verzie
Supported device types and versions

...

The protocol provides data input/output from the ADAM 5000 modules from the Advantech company via the CAN bus using the DeviceNet communication protocol. Communication requires the installation of the Advantech PCL-841 communication interface card. There are supported the The following object types are supported: digital input, digital output, analog input, analog output. There is required the installation Installation of the Advantech 32-bit dll driver is required. The driver versions 1.3 a 1.4 beta 4 were tested. In light of Considering the long-term communication stability, it is recommended to use the version 1.4 beta 4 or later (March 2001), the version 1.3 was not successful on tests (communication had failed in within 48 hours, required resetting reset of the ADAM 5000 system was required). Using the configuration tool Advantech IO Device Installation, it is necessary to define basic ADAM modules connected in to the CAN network. The following table shows the list of ADAM modules, which are supported by the communication protocol. The modules ADAM 5051 and ADAM 5017 were tested.

Table 1

ADAM moduleMeaning
ADAM 50178-channel Analog Input Module
ADAM 50187-channel Thermocouple Input Module
ADAM 50244-channel Analog Output Module
ADAM 505116-point Digital Input Module
ADAM 505616-point Digital Output Module
ADAM 50606-channel Relay Output Module

Communication DLL name:    PROTADAM5KDN.DLL

Kotva
komunikacna_linka
komunikacna_linka
Communication line configuration

...

  • communication line category: API.

Kotva
komunikacna_stanica
komunikacna_stanica
Communication station configuration

...

  • communication protocol: Advantech ADAM 5000 DeviceNet.
  • Station The station address requires:
    • the number allocated assigned to the corresponding CAN channel of the PCL-841 841 interface ("CAN Device ID interface").
    • the number allocated assigned to the corresponding ADAM module - ("ADAM module ID"). These identification numbers are allocated assigned by the installation tool "Advantech IO Device Installationinstallation tool. Numbers are allocated assigned from 000, 001, 002, ..etc.. .


Station protocol parameter

Table 2

KeywordFull nameMeaningUnitsDefault value
DELAYDelayDelay among readings of individual stations.ms100

String A string containing the protocol parameters is being written as follows :

Keyword=value;Keyword=value; ...

Example :

DELAY=300;

Kotva
merany_bod
merany_bod
I/O tag configuration

...

Possible I/O tag types : Ai, Ao, Ci, Co, Di, Dout.

The Ci and Co types allows allow reading of DI inputs or writing to DO outputs byte-by-byte (8 bits at once).

I/O tag address is the number of corresponding I/O channel within the frame of the ADAM module.

Kotva
literatura
literatura
Literature

...

Kotva
revizie
revizie
Document revisions

...

  • Ver. 1.0 - February 13th, 2001 - Document creation.
  • Ver. 1.1 - March 15th, 2002 - the protocol parameter DELAY added.

...