Porovnávané verzie

Kľúč

  • Tento riadok sa pridal
  • Riadok je odstránený.
  • Formátovanie sa zmenilo.

...

Object valueDescription
StONThe station is communicating.
StOFFThe station is not communicating. The communication is disabled by the operator (via control dialogues of the D2000 HI process) or in the station configuration in the D2000 CNF process.
StCOMERRThe occurrence of a "soft" error of communication. This error occurs after an unsuccessful data transmission.
StHARDERRThe occurrence of a "hard" error of communication. This error occurs , if the communication with the station is in the StCOMERR state for a period defined by a Time filter parameter. If the station value is StHARDERR, then all the I/O Tags of the station will pass to an undefined state (unless a /KKVOE start parameter is specified).
StSIMULCommunication with the station is simulated.
StWAITThe station is in AUTO mode. The communication is stopped. The control object value is TRUE. The requests for output are postponed and they will be executed when the control object value changes to FALSE.

Labels of station values, which are mentioned in the first table column, can be redefined by means of the configuration of system texts.

...