If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g. coefficient A=0.1 for #0030, A=0.01 for #0028).

Kotva
register_poruch
register_poruch
Table  3 - Faults register (values of the I/O tag with address #0045). If an arbitrary bit is set to logical 1, the corresponding fault/failure has arisen in the converter. 

BitVýznamMeaning
0Converter Overcurrent
1Converter Overload
2Converter Undervoltage
3Converter Overvoltage
4Motor Overheat
5Heatsink Temperature
6

Incorrect parameters of currents, motor constants, or speed

7Regulation error
8Identification error
9Output short circuit
10IRC failure (ARC), RM-ARC
11

Input or Output phase loss

12External failure
13Temperature in inverter
14AIN1, AIN2, or AIN3 disconnected
15

rezervovanéreserved


Kotva
register_varovani1
register_varovani1
Table 4 - Warnings register 1 (values of the I/O tag with address 

...

#0045

...

). If an arbitrary bit is set to

...

logical 1, the converter generates a corresponding warning. 

BitVýznamMeaning
0

some warnings W1-W5:
W1 - The converter reduces motor magnetic flux in order to achieve over-synchronous revolutions.
W2 - Magnetic flux has decreased to the minimal value at field suppression.
W3 - Regulator of magnetic flux is saturated (only in vector mode). 
W4 - Regulator of motor torque is saturated (only in vector mode).
W5 - Speed regulator is saturated (only in vector mode). 

1W6 - Motor cooler has reached an increased temperature (over 75 °C).
For VQFREM 400 005, 007, and 011 types, the module temperature is over 90 °C
2W7 - The converter switches itself into scalar mode due to IRC/ARC failure.
3W8 - Signalisation of reverse direction of IRC/ARC.
4F7 - The time needed for motor field suppression has not expired yet (before subsequent start).
5W12 - Process regulator is saturated. Converter frequency has reached its maximum value. 
6

F9 - Position calibration initiated by 9.4.3 command, or calibration of IRC encoder on the synchronous motor.
F10 - IRC zero pulse is being searched on the synchronous motor after the converter was connected to the power network and the START command was selected. 

7F11 - The speed decreased to zero by activating a software terminal switch. 
8F8 - Dynamic deceleration was activated as a result of a sharp decrease in speed.
9W16 - Sensored motor temperature has achieved nonpermissible value.
10W17 - Ak je EOPN panel aktívny If EWCP,(M),(I) panel is active (2.4.1), a prerušilo sa spojenie s meničomand the connection with the converter has failed.
11

F2 - Aktivuje sa regulátor max. prúdu  Maximal current regulator (par.13.3.1) a obmedzuje prúd na hodnotu par. is active. It limits the current to the value of parameter 9.10.1

12F3 - Menič je v režime kinetického zálohovania po výpadku elektrickej energie The converter is in kinetic backup mode after input power failure.
13F4 - Prebieha nafázovanie meniča na roztočený motor The converter is processing frequency for the spinning motor.
14F5 - Prebieha parkovanie procesného regulátora Sleep function of process regulator.
15

F6 - Brzdný modul je aktívny Braking unit is active.

Kotva
register_varovani2
register_varovani2
Table 5 - Warnings register

...

(values of the I/O tag with address #0044). If an arbitrary bit is set to

...

logical 1, the converter generates a corresponding warning. 

...

BitMeaningBitVýznam
0W23 - Pri povele ŠTART menič zistil neprítomnosť záťaže na výstupných svorkách  The converter recognized no load at output terminals U, V, W at START command. 
1F12 - Je zopnutý koncový spínač 1 alebo koncový spínač 2 Terminal switch 1 or terminal switch 2 is switched on.
2F13 - Funkcia „brzdenie tokom“ zvyšuje budenie motora úmerne rozdielu  The function „flux braking“ (8.3.1) increases motor excitation proportionally to UDC-UDCnom
3W9 - Prerušenie vstupnej fázy meniča Converter input phase was interrupted 
4rezervovanéreserved
5F14 - Prebieha OFF OFF-LINE identifikácia niektorého z parametrov motora identification of some motor parameters (Rs, Ls+Lm, UpočUinit).
6

W25 - Teplota vzduchu v meniči je vyššia ako 70 °CThe air temperature in the converter is more than 70 °C. 

7rezervovanéreserved
8W18 - Nastala chyba pri komunikácii po sériovej linke  Serial communication error has occurred - RS232 (RS485)
9F16 - Signalizuje, že Relé s funkciou „vypne, preťaženie“ práve rozoploIt signalizes, that relay with the function „shut-down, overload“ has just been released.


Kotva
literatura
literatura
Literature

...