- Input file - complete path to the file or directory with data.
In the case of analyzing the a particular file, its size is tested with a period of 1 second period. If the file does not increase in size during two consecutive periods, it is processed.
If a directory is entered (in the case of a Win32 platform with a backslash (\) at the end), all files that match the mask are processed (see Station protocol parameters).
...
Parameter | Description | Unit | Default value |
---|
| Analyzed profile. | - | P.01 |
Gorlitz PRM62 Module | Files from device Gorlitz PRM62 are analyzed. | YES/NO | NO |
Archive Subdirectory Time Mask | Mask for creating subdirectories in the main archive directory according to time of file processing or timestamp of the file (if the Input file parameter specifies a directory). | - | rrrrmmdd |
Formatted Codes (Annex C) | Numerical addresses of I/O tags are used according to the specification of the IEC62056-21 standard, Annex C. If numerical addresses are used, the station address is acquired from the value of the object with address D000, the timestamp is acquired from the value of the object with address C001. | YES/NO | NO |
External Command File 1, 2 | The complete path to a periodically called external command file (.cmd). It is used only if a non-empty value has been configured. It is possible to configure two independently executed command files with different periods. | - | - |
External Command File Period 1,2 | Call period of the external command file 1 or 2. | mi:ss | 1:00 |
Call External Command File 1,2 Synchronously | Call external command file 1 or 2 synchronously. | YES/NO | YES |
Ext. Command File After Activation | The complete path to the external command file which is launched on change of redundancy status to HS. It is called only once and always synchronously. It is used only if a non-empty value has been configured. | - | - |
| Show debug information about processed files. | YES/NO | YES |
| Show debug information with the content of processed files. | YES/NO | YES |
| Show debug information with measured values of the measure points. | YES/NO | YES |
| Period of input directory content check (if the Input file parameter specifies a directory). | mi:ss | 1:00 |
Unknown Files Backup Directory | File, where unknown files are saved (if the Input file is a directory). If it is not written, the files will be canceled. The unknown files are the files not-matching the configured mask (see Station protocol parameters) or the station with the required device number was not found. | - | - |
| Time data filter. If the timestamp of acquired values is newer from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter. | hours | 24 |
| Time data filter. If the timestamp of acquired values is older from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter. | days | 31 |
Abnormal Timestamp Data Dir | Directory where the files with ignored data by time filter will be saved (Future Data Filter and History Data Filter). | - | - |
| A delay, which is inserted after the file was analyzed. | ss.mss | 0.100 |
| Error file to write information about errors during processing (unknown file in directory, too old or too new values). An empty value means that this error file will not be created. | - | - |
...
- C - Value group C (number within the range of 0..99 or symbols 'C', 'F', 'L' or 'P').
- D - Value group D (number within the range of 0..99 or symbols 'C', 'F', 'L' or 'P').
- E - Value group E (number within the range of 0..255).
- F - Value group F (number within the range of 0..255).
A special I/O tag with the address "$SW" acquires the value of the profile status word.
Note: if the D2000 KOM process is required to send all values from the file (even recurring ones), it is necessary to set the New time => new value parameter in the Filter tab.
File example
...
[HEADER]
PROT = 0
ZNR1 = 00359487
TIME = 10:02:05
DATE = 22.10.04
[PDATA]
/EMH4\@01QJKB0660L0C1
0.0.0(00359487)
0.0.1(00359487)
0.9.1(100208)
0.9.2(041022)
F.F(00000000)
P.01(041022094500)(00000000)(15)(4)(1.5)(MW)(2.5)(MW)(3.5)(Mvar)(4.5)(Mvar)
(00.000)(00.000)(00.000)(00.000)
(00.000)(00.000)(00.000)(00.000)
!
...
P.01 - profile
(041022094500) - the timestamp of the first row with values
(00000000) - the profile status word
(15) - period of measurement in minutes
(4) - number of channels
(1.5) - first channel, 1 = Value Group C = Reactive power+, 5 = Value Group D = Last average 1
(MW) - unit of the first channel
etc.
Next The next rows contain the values of measurement.
...