General properties
Groups
Parameters

Kotva
zakladne_vlastnosti0
zakladne_vlastnosti0
General properties

...

A text string describing the user variable. Maximum: 128 characters.
Possibility to use the Dictionary (to open press CTRL+L).

Status text

Defines a status text for the given user variable. Status allows to redefine labels of individual user variable values.

...

Selection of a user variable type. Admissible value types are listed in the following table.

LabelUser variable type
BoBoolean - logical value
IntInteger - integer value
ReReal - real value
TmAAbsolute Time
TmRRelative Time (time interval)
TxtText - text string

Technical units

Technical units of the user variable. Maximum: 12 characters.

...

Technological limits may be defined for user variables of the types Int-Integer, Re-Real a TmR-Time interval. There are defined four limits: VHL, HL, LL a VLL. Limit can be defined either directly - by the value entry into the input field, or its value can be determined by a system object (dynamic limit) - the button placed right to the input field.

VHLVery High Limit - the highest limit
HLHigh Limit
LLLow Limit
VLLVery Low Limit - the lowest limit


Values of the individual limits determine the state of the object value according to its value. The relation user variable value - limits gives 6 possible states.

LimitObject status according to the relation Value - Limit
 

Above VHL (object value > VHL)
VHL
  


Above HL (HL < object value < VHL)
HL
 
 


Normal (LL < object value < HL)
LL
 
  


Below LL (VLL < object value < LL)
VLL
 


Below VLL (object value < VLL)

As the limits can be dynamic, i.e. determined by the object value, a situation, when the relation VLL<LL<HL<VHL is not valid (the limit crossing), may occur. The object value is then in the status Limits Problem.

Kotva
parametre0
parametre0
Parameters

...

The value, that is assigned to the object during system start. Maximum: 20 characters.
Description of the text string format by value type.


Example
absolute time: 17:03:16 18-03-2007
relative time: 156 14:23:25 - 156 days, 14 hours, 23 minutes, 25 seconds

...

Start value is saved in text form. During the system start, Server assigns values to individual objects according to the start value definition. In case of the successful conversion of a start value (text) to the required type, a value of the user variable is to be valid. If the conversion is not successful, then this value is invalid. It is able to save a start value that can not be converted to the required type. The button Start value checkout () checks the start value and, in case of unsuccessful conversion, reports it.

...

Occurrence time of the user variable value can be defined only if there is enabled saving the object value changes (the option Save start value). Clicking the button placed right from the input field inserts the current time into the input field.

...