Parameter | Meaning | Unit | Default value | ||||||
---|---|---|---|---|---|---|---|---|---|
| Phone number for connection via modem with this station (only lines of MODEM category). | ||||||||
| Maximal waiting time on connection via modem (only lines of MODEM category). | sec | 60 | ||||||
| Maximum number of attempt to connect via modem (only lines of MODEM category). | 1..20 | 1 | ||||||
| Delay before attempting to dial after an unsuccessful connection attempt (only lines of MODEM category). | sec | 30 | ||||||
| Time delay between sending the request and reading the answer. Note: a device sends a 3-character manufacturer's identification in the identification message. Standard defines that if the 3-rd character is a lower case letter, (e.g. in identifications ELm or UNi), minimum reaction time for such device is 20 ms instead of 200 ms. If the 3-rd character is an upper case letter, this does not preclude supporting a 20 ms reaction time. | ms | 200 | ||||||
| Time delay between reading the answer till it is completed. See the note of parameter Wait First Timeout. | ms | 200 | ||||||
| Retry count of reading response till its completion. | 1 .. 100 | 20 | ||||||
| Delay between the request retry if the error communication occurs. | ms | 1000 ms | ||||||
| Retry count of request as far as the error communication. | 1 .. 20 | 3 | ||||||
| Timeout for waiting for answer to modem hangup operation (only lines of MODEM category). | sec | 15 | ||||||
| Delay after transmitting acknowledgement of received data (ACK). | ms | 100 | ||||||
| Value of parameter 'Z' - Baud rate identification (for baud rate changeover) of request Acknowledgement/option select message of protocol C mode. Option AUTO finds out automatic the value 'Z' from acknowledgement of answer and uses it. | 300 Baud 600 Baud 1200 Baud 2400 Baud 4800 Baud 9600 Baud 19200 Baud 38400 Baud 57600 Baud 115200 Baud AUTO | 2400 Baud | ||||||
| Permission to read the current values ("data readout"). | YES/NO | YES | ||||||
| Permission to read the "manufacturer specific table" values, 1-st block. Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read. | - 6 7 8 9 | - | ||||||
Manuf. Spec. Table Readout Nr.2 (Y) | Permission to read the "manufacturer specific table" values, 2-nd block. Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read. | - 6 7 8 9 | - | ||||||
Manuf. Spec. Table Readout Nr.3 (Y) | Permission to read the "manufacturer specific table" values, 3-rd block. Choice '-' means the values are not read, choice '6' to '9' means selected "manufacturer specific table" will be read. | - 6 7 8 9 | - | ||||||
| Permission to load the historical data from profile. | YES/NO | YES | ||||||
| Profile name - OBIS code of load profile used during loading of historical data from profile. | P.01 | |||||||
| Date and time mask used to read historical data from profile. The letter " z" is used to set the time and is replaced by a value of 0, 1 or 2 according to the parameter Session Recognition Flag. | zyymmddhhmi | |||||||
| Time depth of historical profile readings. | hour | 24 | ||||||
| Time round of data from profile. | min | 15 | ||||||
| Time range of data which is queried from profile in one request. It is entered as a multiple of the parameter "Time Round". | x Time Round | 2 | ||||||
| Access level used to read historical data from profile. | 0-9 | 5 | ||||||
| Password necessary for changing configuration of device (level 1) used to set the date and time. | "00000000" | |||||||
| Flag that indicates type of date/time used by the device. Electrometers LZQJ manufactured by EMH Elektrizitätszähler indicate type of date/time by this flag (0=Normal Time, 1=Summer Time, 2=UTC Time). This flag is used by parameters Time Mask and Date Mask to set the time and by parameter Profile Time Mask to read historical data from profile. Note: Both Normal Time and Summer Time values will cause the flag to be set depending on the time currently set or read. | Normal Time Summer Time UTC Time | Normal time | ||||||
| Register used to set the time. The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station. | 0.9.1 | |||||||
| Mask used to set the time. The letter " z" is used for time conversion according to the parameter Session Recognition Flag. The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station. Note: some meters are disturbed by summer / winter time ("z") flag and require mask hhmiss | zhhmiss | |||||||
| Register used to set the date. The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station. | 0.9.2 | |||||||
| Mask used to set the date. The letter " z" is used for dátumu conversion according to the parameter Session Recognition Flag. The parameter is important only if the synchronization is enabled on the tab "Time parameters" in the configuration of station. Note: some meters are disturbed by summer / winter time ("z") flag and require mask ddmmyy or require a year-month-day order (zyymmdd or yymmdd) | zddmmyy | |||||||
| Special settings used when setting the date and time. These may be required by some electricity meters.
| Normal (00000000) | Normal | ||||||
| A special initial string of modem 1 (only for MODEM lines). | AT&FE0V1Q0B0X3L0M0 | |||||||
| A special initial string of modem 2 (only for MODEM lines). Explanation of recommended settings: S37=5 1200bps DTE-DTE speed - limits the speed for modems. Many devices use modems with limited transfer speeds and this setting can speed-up the connection establishment process. Higher transfer speeds must be negotiated individualy. &D2 DTR drop to hangup - for matching with tha parameter of modem line (line configuration, tab "Modem - parameters", check the option "Use DTR for Hangup"). S0=0 Disable auto-answer. Auto-answer will not be used. S30=2 20 sec inactivity timeout - automatic hangup after idle timeout expired. Necessary for assuring connection termination after the communication with the last device is over. | ATS37=5&D2S0=0S7=60S30=2 | |||||||
| Full tracing of communication, loaded values of I/O tags and other debug information are shown. | YES/NO | NO | ||||||
| It activates data processing according to software implementation of protocol from Unicontrols. | YES/NO | NO | ||||||
| Activates reading of profile index (map of records stored in memory) within reading of historical data from profile (Unicontrols device only). Retrieved index is not processed further and serves only as debugging information for Unicontrols. | YES/NO | NO |
...