Parameter | Description | Unit | Default value |
---|
| Analyzed profile. | - | P.01 |
Gorlitz PRM62 Module | Files from device Gorlitz PRM62 are analyzed. | YES/NO | NO |
Archive Subdirectory Time Mask | Mask for creating subdirectories in the main archive directory according to time of file processing or timestamp of the file (if the Input file parameter specifies a directory). | - | rrrrmmdd |
Formatted Codes (Annex C) | Numerical addresses of I/O tags are used according to the specification of IEC62056-21 standard, Annex C. If numerical addresses are used, the station address is acquired from the value of the object with address D000, the timestamp is acquired from the value of the object with address C001. | YES/NO | NO |
External Command File 1, 2 | The complete path to a periodically called external command file (.cmd). It is used only if a non-empty value has been configured. It is possible to configure two independently executed command files with different periods. | - | - |
External Command File Period 1,2 | Call period of the external command file 1 or 2. | mi:ss | 1:00 |
Call External Command File 1,2 Synchronously | Call external command file 1 or 2 synchronously. | YES/NO | YES |
Ext. Command File After Activation | The complete path to the external command file which is launched on change of redundancy status to HS. It is called only once and always synchronously. It is used only if a non-empty value has been configured. | - | - |
| Show debug information about processed files. | YES/NO | YES |
| Show debug information with the content of processed files. | YES/NO | YES |
| Show debug information with measured values of the measure points. | YES/NO | YES |
| Period of input directory content check (if the Input file parameter specifies a directory). | mi:ss | 1:00 |
Unknown Files Backup Directory | File, where unknown files are saved (if the Input file is directory). If it is not written, the files will be canceled. The unknown files are the files not-matching the configured mask (see Station protocol parameters) or the station with the required device number was not found. | - | - |
| Time data filter. If the timestamp of acquired values is newer from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter. | hours | 24 |
| Time data filter. If the timestamp of acquired values is older from the current time by more than the configured number of hours, they are ignored. Enter 0 (zero) to ignore the time filter. | days | 31 |
Abnormal Timestamp Data Dir | Directory where the files with ignored data by time filter will be saved (Future Data Filter and History Data Filter). | - | - |
| TimeoutA delay, it which is inserted after the file was analyzed. | ss.mss | 0.100 |
| Error file to write information about errors during processing (unknown file in directory, too old or too new values). Empty An empty value means that this error file will not be created. | - | - |
...
Parameter | Description | Unit | Default value |
---|
| If the Input file is a particular file, after this timeout passes without a file being processed, then the Station goes to a communication error. | min | 45 |
| Mask for the name testing of the processed files. The following digit placeholder can be used: {N} - electrometer number, beware of mind the number of figurefigures, e.g.{NNNNNNNN}, {yy} or {yyyy} - year, {mm} - month, {dd} - day, {hh} - hour, {mi} - minute, {ss} - second. Exmple of mask: "Meter_{NNNNNNNN}{yy}{mm}{dd}{hh}{mi}.abl". If a timestamp can be obtained from the file name, it is used for saving the file to the archive directory (see Communication line protocol parameter Archive subdirectory time mask). If the electrometer number can be obtained, it is used for searching for the proper station. In the mask is not used, leave the parameter empty. The station address is then acquired from the value of object 0.0.0, C.1.0, or ZNR1 (previously, ZNR1 was previously used only in the case ofGorlitz PRM62 Module, currently it is used also for other types of energy meters). | - | - |
| The complete path to a periodically called external command file (.cmd). The command file is called before accessing the input file. It is used only if a non-empty value has been configured. | - | - |
External Command File Period | Period of calling the external command file. | mi:ss | 1:00 |
Call Ext. Command File Synchronously | Call the external command file synchronously. | YES/NO | YES |
| All values from communication (even old ones) go to the system as new values. | YES/NO | NO |
| The parameter is only used when analyzing files from the Gorlitz PRM62 (see the Gorlitz PRM62 Module line parameter). When enabled, attributes Invalid (invalid value), ShortPeriod (data for the whole measurement period are not available to electrometer), and TimeSet (time has been set during the measurement period) are mapped into flags FA, FB, FC. | YES/NO | NO |
...
I/O address
...
Address The address of the I/O tag corresponds to standard IEC 62056-61:2002 Object Identification System (OBIS), "Annex A - Code presentation".
...