If the number is fractional, the corresponding linear conversion must be entered in the I/O tag configuration in the Conversion tab (e.g. coefficient A=0.1 for #0030, A=0.01 for #0028).
| Kotva | ||||
|---|---|---|---|---|
|
| Bit | VýznamMeaning |
|---|---|
| 0 | Converter Overcurrent |
| 1 | Converter Overload |
| 2 | Converter Undervoltage |
| 3 | Converter Overvoltage |
| 4 | Motor Overheat |
| 5 | Heatsink Temperature |
| 6 | Incorrect parameters of currents, motor constants, or speed |
| 7 | Regulation error |
| 8 | Identification error |
| 9 | Output short circuit |
| 10 | IRC failure (ARC), RM-ARC |
| 11 | Input or Output phase loss |
| 12 | External failure |
| 13 | Temperature in inverter |
| 14 | AIN1, AIN2, or AIN3 disconnected |
| 15 | rezervovanéreserved |
| Kotva | ||||
|---|---|---|---|---|
|
...
#0045
...
). If an arbitrary bit is set to
...
logical 1, the converter generates a corresponding warning.
| Bit | VýznamMeaning |
|---|---|
| 0 | some warnings W1-W5: |
| 1 | W6 - Motor cooler has reached an increased temperature (over 75 °C). For VQFREM 400 005, 007, and 011 types, the module temperature is over 90 °C |
| 2 | W7 - The converter switches itself into scalar mode due to IRC/ARC failure. |
| 3 | W8 - Signalisation of reverse direction of IRC/ARC. |
| 4 | F7 - The time needed for motor field suppression has not expired yet (before subsequent start). |
| 5 | W12 - Process regulator is saturated. Converter frequency has reached its maximum value. |
| 6 | F9 - Position calibration initiated by 9.4.3 command, or calibration of IRC encoder on the synchronous motor. |
| 7 | F11 - The speed decreased to zero by activating a software terminal switch. |
| 8 | F8 - Dynamic deceleration was activated as a result of a sharp decrease in speed. |
| 9 | W16 - Sensored motor temperature has achieved nonpermissible value. |
| 10 | W17 - Ak je EOPN panel aktívny If EWCP,(M),(I) panel is active (2.4.1), a prerušilo sa spojenie s meničomand the connection with the converter has failed. |
| 11 | F2 - Aktivuje sa regulátor max. prúdu Maximal current regulator (par.13.3.1) a obmedzuje prúd na hodnotu par. is active. It limits the current to the value of parameter 9.10.1 |
| 12 | F3 - Menič je v režime kinetického zálohovania po výpadku elektrickej energie The converter is in kinetic backup mode after input power failure. |
| 13 | F4 - Prebieha nafázovanie meniča na roztočený motor The converter is processing frequency for the spinning motor. |
| 14 | F5 - Prebieha parkovanie procesného regulátora Sleep function of process regulator. |
| 15 | F6 - Brzdný modul je aktívny Braking unit is active. |
| Kotva | ||||
|---|---|---|---|---|
|
...
2 (values of the I/O tag with address #0044). If an arbitrary bit is set to
...
logical 1, the converter generates a corresponding warning.
...
| Bit | Meaning | Bit | Význam |
|---|---|---|---|
| 0 | W23 - Pri povele ŠTART menič zistil neprítomnosť záťaže na výstupných svorkách The converter recognized no load at output terminals U, V, W at START command. | ||
| 1 | F12 - Je zopnutý koncový spínač 1 alebo koncový spínač 2 Terminal switch 1 or terminal switch 2 is switched on. | ||
| 2 | F13 - Funkcia „brzdenie tokom“ zvyšuje budenie motora úmerne rozdielu The function „flux braking“ (8.3.1) increases motor excitation proportionally to UDC-UDCnom | ||
| 3 | W9 - Prerušenie vstupnej fázy meniča Converter input phase was interrupted | ||
| 4 | rezervovanéreserved | ||
| 5 | F14 - Prebieha OFF OFF-LINE identifikácia niektorého z parametrov motora identification of some motor parameters (Rs, Ls+Lm, UpočUinit). | ||
| 6 | W25 - Teplota vzduchu v meniči je vyššia ako 70 °CThe air temperature in the converter is more than 70 °C. | ||
| 7 | rezervovanéreserved | ||
| 8 | W18 - Nastala chyba pri komunikácii po sériovej linke Serial communication error has occurred - RS232 (RS485) | ||
| 9 | F16 - Signalizuje, že Relé s funkciou „vypne, preťaženie“ práve rozoploIt signalizes, that relay with the function „shut-down, overload“ has just been released. |
| Kotva | ||||
|---|---|---|---|---|
|
...