ZPA INMAT 64/65 communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions
| Kotva | ||||
|---|---|---|---|---|
|
...
- Communication line category: Serial, SerialOverUDP Device Redundant.
- Parameters of asynchronous line: 300 Baud, 8 data bits, no parity, 2 stop bits.
Note:
A device sends data spontaneously (without the request for data). A delay between the transmitted data blocks is 5 seconds.
| Kotva | ||||
|---|---|---|---|---|
|
...
- Communication protocol: ZPA INMAT 64/65.
- The station address is not used. On one serial line, there may be placed only one INMAT 64 or 65.
...
| Kotva | ||||
|---|---|---|---|---|
|
...
I/O tags: Ai
The address can be entered as a decimal number or a hexadecimal number with a hash at the beginning (e.g. #A).
The value meaning:
| Address | Cycle | Meaning | Units |
|---|---|---|---|
| 0 | 1 | Heat output | GJ/hour |
| 1 | 1 | 1/4 hourly maximum | GJ |
| 2 | 1 | Heat output sum | GJ |
| 3 | 1 | Instantaneous mass flow rate | t/hour |
| 4 | 1 | Mass flow rate sum | t |
| 5 | 1 | Temperature | °C |
| 6 | 1 | Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65 | - |
| 7 | 2 | Heat output | GJ/hour |
| 8 | 2 | 1/4 hourly maximum | GJ |
| 9 | 2 | Heat output sum | GJ |
| 10 | 2 | Instantaneous mass flow rate | t/hour |
| 11 | 2 | Mass flow rate sum | t |
| 12 | 2 | Temperature | °C |
| 13 | 2 | Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65 | - |